| Notes |
| Date |
Text |
| 2005-06-24 00:00:00 | ********* NOTES REDLINED ************ | | | | | | MISSING RECEPTS PER 21.52, 210.52E, | | | | | | MISSING DEDICATED BATH(S) CIRCUIT(S) PER | | | 210.52D,210.11C3, MUST BE 20A, #12. | | | | | | CIRCUIT #'S ON PANEL SCHEDULE DO NOT | | | CORRELATE WITH 2-POLE CIRCUITS. | | | | | | SUB PANEL NOT INCLUDED IN SCOPE OF WORK. | | | IF INSTALLED, PLEASE REVISE RISER AND | | | PROVIDE PANEL SCHEDULE | | | | | | | | | THE ABOVE ITEMS WERE REDLINED ON PLANS. |
|