| Date |
Text |
| 2005-04-06 00:00:00 | ************ UNSAT ************** |
| | |
| | 1)NOTE: PLEASE INCLUDE INFORMATION FOR |
| | MAIN. IS PANEL A MCB ? IS MAIN LOCATED |
| | WITH METER? |
| | 215.5,240.4B,225.30 ETC. |
| | |
| | 2) NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 3)NOTE: PLEASE SEE IF MAIN IS NOT |
| | LOCATED AT METER, PLEASE SEE 250.6, |
| | 250.24, AN EQUIPMENT GROUNDING CONDUCTOR |
| | IS NOT INSTALLED FROM METER TO FIRST |
| | MEANS OF DISCONNECT. |
| | PLEASE SEE RISER SHOWS AN EQUIPMENT |
| | GROUNDING CONDCUTOR FROM METER TO MAIN. |
| | |
| | 4)NOTE: PLEASE SEE RISER INDICATES A |
| | POSSIBLE SUB-PANEL IF REQUIRED. IF THIS |
| | IS INSTALLED, PLANS BE NEED TO BE |
| | REVISED TO REFLECT ACTUAL INSTALLATION |
| | TAKEN. |
| | PLEASE ALSO SEE PANEL IS SHOWN WITH #5 |
| | AS FEEDERS. PLEASE SEE AWG'S AVAILABLE, |
| | THIS IS NOT A SIZE. PLEASE SEE 310.16 |
| | |
| | 5)NOTE: PLEASE SEE MISSING RECEPTS ALONG |
| | KITCHEN COUNTERSPACE PER 210.52C1 |
| | PLEASE SHOW ALL RECEPTS SERVING KITCHEN |
| | COUNTERSPACE AS GFI/GFI PROTECTED PER |
| | 210.8A-6 |
| | |
| | |
| | 6)NOTE: PLEASE CORRELATE PANEL SCHEDULE |
| | AND LOAD CALCAULTIONS. PLEASE SEE THERE |
| | ARE NUMEROUS ITEMS THAT DO NOT |
| | CORRELATE. |
| | IE: WELL PUMNP, DISPOSAL, FRIG, A/C |
| | UNITS, DISHWASHER, WASHER/LANUDRY, |
| | RANGE, ETC. |
| | |
| | 7)NOTE: PLEASE ALSO SEE MANY "MISPRINTS" |
| | ON PANEL SCHEDULE. PLEASE SEE 2-POLE |
| | CIRCUITS, SHOWING A REDUCED AWG AND OCP |
| | ON "B" PHASE. |
| | |
| | 8)NOTE: PLEASE CORRELATE PLANS, PANEL |
| | SCHEDULE AND LOAD CALCULATIONS FOR |
| | RANGE, OVENS. |
| | PLEASE SEE PLANS INDICATE DOUBLE OVENS, |
| | YET THIS IS NOT ON PANEL SCHEDULE OR |
| | LOAD CALCS. PLEASE SEE PLANS INDICATE A |
| | SEPARATE COOKTOP ALSO, YET THIS IS NOT |
| | ON PANEL SCHEDULE OR LOAD CALCS. |
| | PLEASE SEE PANEL SCHEDULE SHOWS 13KW2-P |
| | 60A FOR RANGE??? |
| | PLEASE SEE LOAD CALCS SHOWS 8KW? |
| | ETC. |
| | |
| | 9)NOTE: PLEASE SEE PLANS FOR MISSING |
| | RECEPTS PER 210.52 |
| | |
| | 10)NOTE: PLEASE SEE MISSING DISCONNECT |
| | FOR A/C COND UNIT PER 440.11 |
| | PLEASE SHOW. |
| | |
| | 11)NOTE: PLEASE SEE FBC 104.2.1, WHICH |
| | REQUIRES THE PRINTED NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR PLANS. |
| | PLEASE THE PLANS ONLY NEED THE PRINTED |
| | NAME. |
| | |
| | 12)NOTE: PLEASE SEE ONE SET OF PLANS HAS |
| | BEEN REDLINED AT LOCATIONS FOR THE ABOVE |
| | COMMENTS. PLEASE SEE THESE LOACTIONS |
| | SHOWN ON PLANS. |
| | |
| | 13)NOTE: PLEASE REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETED SETS FOR |
| | REVIEW AND STAMPING. |
| | PLEASE SUBMIT ONE SET OF OLD/VOIDED |
| | SHEETS FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |