| 2005-04-08 00:00:00 | MECH. PLAN REVIEW. | | | | | | 1. PROVIDE BUILDING ENERGY | | | CALCULATION.FBC CHAPTER 13 . | | | 2. PROVIDE FOR R/A OUT MASTER BEDROOM | | | AREA.2003 FBC/M 601.4 BALANCED RETURN | | | AIR. | | | 3. AUXILIARY DRAIN PAN REQUIRED UNDER | | | A.H.U. .2003 FBC/M 307.2.3. . | | | 4. PROVIDE INFORMATION ON GAS H.W.H., | | | AND COMBUSTION AIR FOR CONFINE SPACE. | | | 5. PROVIDE FOR COMBUSTION AIR FOR GAS | | | DRYER IN CLOSIT. | | | 6. PROVIDE INFORMATION ON KITCHEN HOOD | | | , AND EXHAUST FROM HOOD. | | | 7. ADDITIONAL PERMIT REQUIRED FOR GAS. | | | PLEASE PROVIDE ISOMETRIC DRAWING | | | INDICATING DEVELOPED LENGTH AND BTU'S OF | | | ALL GAS APPLIANCES. | | | PAT RAFTER 805/6728 OR 805/6719 PATTY | | | KRAUSS. | | | PLEASE CALL IF THEAR ANY QUESTIONS. |
|