| 2005-04-05 00:00:00 | ************** UNSAT ************* |
| | |
| | 1)NOTE: PLEASE SUBMIT A COMPLETED RISER |
| | DIAGRAM, INCLUDING ALL CONDUCTOR SIZES, |
| | CONDUIT SIZES ETC. |
| | 215.5,310.16, 310.15B6 |
| | |
| | 2)NOTE: PLEASE INCLUDE ALL OCP ON |
| | METER/MAIN COMBO FOR SUB PANELS. |
| | 215.5,240.4 ETC |
| | |
| | 3)NOTE: PLEASE IDENTIFY "FOOTER STEEL" |
| | AS PART OF THE GROUNDING ELECTRODE |
| | SYSTEM. SHOWS BLDG STEEL? IS THERE BLDG |
| | STEEL ALSO? |
| | 250.50 |
| | |
| | 4)NOTE: PLEASE INCLUDE GEC FOR GROUNDING |
| | ELECTRODE SYSTEM PER 250.66 |
| | |
| | 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 6)NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | PLEASE SEE CIRCUITING FOR BATHS IS SHOWN |
| | ON OTHER BRANCH CIRCUITS. |
| | |
| | 7) NOTE: PLEASE SHOW OUTLET SPACING PER |
| | 210.52. 2',6`,12` RULE. |
| | PLEASE SEE MISSING WAL SPACE IN STUDY. |
| | |
| | 8)NOTE: PLEASE SEE MISSING REQ'D EGRESS |
| | LIGHTING AND/OR CLARIFY EGRESS LIGHTING |
| | PER 210.70 AND LS-101 5-8 |
| | PLEASE SEE CONTROL/SWITCHES, TO BE |
| | INDICATED AS3-WAY'S. PLEASE SEE SOME |
| | SHOWN AS SP SW. |
| | PLEASE SEE PLANS ARE MISSING LIGHTING IN |
| | BATHRM SECOND FLR "BONUS AREA". |
| | 210.70 |
| | |
| | 9)NOTE: PLEASE SEE IF STUDY HAS A DOOR |
| | TO ENCLOSE RM, A SD WILL BE REQUIRED AS |
| | IT IS CONSIDERED AN ADAPTABLE SLEEPING |
| | ROOM W/ CLOSET. |
| | PLEASE ALSO SEE SD LOCATION AT MAASTER |
| | BEDRM. SD IS REQUIRED TO BE MOVED "INTO" |
| | BEDRM, OR ADD ADDITIONAL SD AS HEADER IS |
| | SHOWN AT DOORWAY. |
| | SMOKE DETECTORS ARE REQUIRED INSIDE AND |
| | OUTSIDE ALL SLEEPING ROOMS. ON EACH |
| | LEVEL OF A MULTI-LEVEL DWELLING UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4, |
| | 8-1.4.2.1.6.2 |
| | PLEASE SEE MISSING SD'S ON EACH LEVEL AT |
| | "BONUS RM" AND AREA LEADING TO FLR |
| | ABOVE. |
| | |
| | 10)NOTE: PLEASE SEE MISSING KITCHEN |
| | COUNTERSPACE RECEPT PER 210.52C1, PLEASE |
| | ALSO SEE 210.8A6 FOR REQUIRED GFI |
| | PROTECTION. |
| | |
| | 11)NOTE: PLEASE SEE COOKTOP IS SHOWN AS |
| | 1-P 20A ON PANEL SCHEDULE. PLEASE |
| | CLARIFY IF "GAS". |
| | |
| | 12)NOTE: PLEASE SEE AHU #2 DOES NOT NEED |
| | TO BE INDICATED ON PANEL SCHEDULE OR |
| | LOAD CALCULATIONS IF THE ELECTRICAL IS |
| | NOT GOING TO BE INSTALLED AT THIS TIME. |
| | |
| | 13)NOTE: PLEASE PROVIDE ROOM |
| | DESIGNATIONS ON ELECTRICAL PLANS. |
| | 215.5 |
| | |
| | PLEASE COMPLETE PLANS FOR REVIEW. |
| | PLEASE SEE ONE SET OF PLANS ARE REDLINED |
| | AT AREAS OF COMMENTS ABOVE. |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO TWO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | PLEASE SUBMIT ONE SET OF OLD/VOIDED |
| | SHEETS FOR REFERENCE ONLY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |