Plan Review Notes
Plan Review Notes For Permit 05031759
Permit Number 05031759
Review Stop E
Sequence Number 1
Notes
Date Text
2005-04-05 00:00:00************** UNSAT *************
  
 1)NOTE: PLEASE SUBMIT A COMPLETED RISER
 DIAGRAM, INCLUDING ALL CONDUCTOR SIZES,
 CONDUIT SIZES ETC.
 215.5,310.16, 310.15B6
  
 2)NOTE: PLEASE INCLUDE ALL OCP ON
 METER/MAIN COMBO FOR SUB PANELS.
 215.5,240.4 ETC
  
 3)NOTE: PLEASE IDENTIFY "FOOTER STEEL"
 AS PART OF THE GROUNDING ELECTRODE
 SYSTEM. SHOWS BLDG STEEL? IS THERE BLDG
 STEEL ALSO?
 250.50
  
 4)NOTE: PLEASE INCLUDE GEC FOR GROUNDING
 ELECTRODE SYSTEM PER 250.66
  
 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 6)NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
 PLEASE SEE CIRCUITING FOR BATHS IS SHOWN
 ON OTHER BRANCH CIRCUITS.
  
 7) NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE.
 PLEASE SEE MISSING WAL SPACE IN STUDY.
  
 8)NOTE: PLEASE SEE MISSING REQ'D EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210.70 AND LS-101 5-8
 PLEASE SEE CONTROL/SWITCHES, TO BE
 INDICATED AS3-WAY'S. PLEASE SEE SOME
 SHOWN AS SP SW.
 PLEASE SEE PLANS ARE MISSING LIGHTING IN
 BATHRM SECOND FLR "BONUS AREA".
 210.70
  
 9)NOTE: PLEASE SEE IF STUDY HAS A DOOR
 TO ENCLOSE RM, A SD WILL BE REQUIRED AS
 IT IS CONSIDERED AN ADAPTABLE SLEEPING
 ROOM W/ CLOSET.
 PLEASE ALSO SEE SD LOCATION AT MAASTER
 BEDRM. SD IS REQUIRED TO BE MOVED "INTO"
 BEDRM, OR ADD ADDITIONAL SD AS HEADER IS
 SHOWN AT DOORWAY.
 SMOKE DETECTORS ARE REQUIRED INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS. ON EACH
 LEVEL OF A MULTI-LEVEL DWELLING UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4,
 8-1.4.2.1.6.2
 PLEASE SEE MISSING SD'S ON EACH LEVEL AT
 "BONUS RM" AND AREA LEADING TO FLR
 ABOVE.
  
 10)NOTE: PLEASE SEE MISSING KITCHEN
 COUNTERSPACE RECEPT PER 210.52C1, PLEASE
 ALSO SEE 210.8A6 FOR REQUIRED GFI
 PROTECTION.
  
 11)NOTE: PLEASE SEE COOKTOP IS SHOWN AS
 1-P 20A ON PANEL SCHEDULE. PLEASE
 CLARIFY IF "GAS".
  
 12)NOTE: PLEASE SEE AHU #2 DOES NOT NEED
 TO BE INDICATED ON PANEL SCHEDULE OR
 LOAD CALCULATIONS IF THE ELECTRICAL IS
 NOT GOING TO BE INSTALLED AT THIS TIME.
  
 13)NOTE: PLEASE PROVIDE ROOM
 DESIGNATIONS ON ELECTRICAL PLANS.
 215.5
  
 PLEASE COMPLETE PLANS FOR REVIEW.
 PLEASE SEE ONE SET OF PLANS ARE REDLINED
 AT AREAS OF COMMENTS ABOVE.
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE SET OF OLD/VOIDED
 SHEETS FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  
  
  