Text |
| 2005-05-19 00:00:00 | DENIED |
| | |
| | 1)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) THE TYPICAL WALL SECTION ON SHEET A2 |
| | SPECIFIES 2X8 #2 SYP FOR THE CEILING |
| | JOISTS AND SECTION 3 ON A3 CALLS FOR |
| | 2X10 #2 DENSE SYP. REVISE PLANS TO |
| | INDICATE WHICH ONE IS TO BE USED. |
| | |
| | 3) THE ROOF NOTES ON A3 REFER TO ROOF |
| | TRUSSES AND STATE THAT TRUSS ENGINEER IS |
| | RESPONSIBLE FOR THE FINAL ROOF AND FLOOR |
| | TRUSS LAYOUT. IF MANUFACTURED TRUSSES |
| | ARE NOT BEING USED PLEASE REVISE OR |
| | REMOVE THESE NOTES AS THEY DO NOT |
| | PERTAIN TO THE DESIGN OF THIS PROJECT. |
| | |
| | 4) SPECIFY COLLAR BEAMS OF 1X6 BOARDS |
| | INSTALLED TO EVERY THIRD PAIR OF RAFTERS |
| | AS REQUIRED BY FBC 2309.1.7. |
| | |
| | 5) FLOOR JOISTS ARE REQUIRED TO BE |
| | SUPPORTED LATERALLY AT THE ENDS BY SOLID |
| | BLOCKING OR DIAGONAL STRUTS OR OTHER |
| | METHOD. PLEASE SPECIFY METHOD THAT WILL |
| | BE USED. SEE FBC 2307.3.4. |
| | |
| | 6) SUBMIT THE NOA OR EVALUATION REPORTS |
| | AND INSTALLATION INSTRUCTIONS IN |
| | ADDITION TO THE STATE COVERSHEETS FOR |
| | THE SINGLE HUNG WINDOWS AND THE STORM |
| | PANELS. |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. |