Plan Review Notes
Plan Review Notes For Permit 05031638
Permit Number 05031638
Review Stop E
Sequence Number 2
Notes
Date Text
2005-06-23 00:00:00************* UNSAT **************
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDDRESSED AND
 NEW NOTES DUE TO CHANGES IN PLANS.
  
 1)NOTE: PLEASE SEE SEE 2 MCB PANELS ARE
 NOW INDICATED ON RISER, HOWEVER ONLY ONE
 PANEL "A" IS SHOWN ON PLANS. PLEASE
 LOCATION OF PANEL "B". PLEASE SEE 230.72
 FOR GROUPING OF MAINS.
 PLEASE SEE PANELS ARE INDICATED AS 42
 CIRCUIT ON RISER, HOWEVER PANEL
 SCHEDULES INDICATE 30 CIR?
  
 2)NOTE: PLEASE SEE SIZE OF GROUNDING
 ELECTRODE CONDUCTOR IS MISSING. PLEASE
 SEE 250.50,250.66 FOR SIZING. #2 MIN.
  
 3)NOTE: PLEASE SEE PANEL SCHEDULES ARE
 NOW SHOWN, HOWEVER PLEASE SEE LOADS FOR
 EACH ARE NOT SHOWN. PLEASE SHOW LOAD FOR
 EACH. 220,215.5
 PLEASE ALSO COIRRELATE PANEL SCHEDULES
 AND LOAD CALCULATIONS. PLEASE SEE THERE
 ARE ITEMS LISTED ON LOAD CALCS, BUT NOT
 ON PANEL SCHEDULE AND ITEMS ON PANEL
 SCHEDULES, BUT NOT ON LOAD CALCS.
 PLEASE SEE REDLINED SET.
 COOKTOP,OVEN, SMALL APPL
  
 4)NOTE: PLEASE SEE NEC 220.31 ETC FOR
 MIN LOADS TO BE INDICATED. PLEASE SEE
 ALL CONTINUOUS LOADS ARE TO BE SHOWN AT
 125%. POOL PUMP, POOL HEAT PUMP,,
 215.3,230.42 ETC.
  
 5)NOTE: PLEASE SEE TANKLESS WATER
 PRODUCT CUT SHEETS STILL NEED TO SHOW
 SOME SORT OF LISTINGS FROMA NRTL.
 110.3 PLEASE SEE A MIAMI-DADE PRODUCT
 APPROVAL IS NOT ON THE LIST OF A NRTL.
 NATIONALLY RECOGNIZED TESTING
 LABORATORY; UL, CSA, ETL, MET, TUV, ETC
 ** NOTE, IF LOCATED UNDER SINK, ALL MIN
 CLEARENCE SHALL BE MAINTAINED AND IF OCP
 IS PROVIDED IN RFEQUIRED DISCONNECTING
 MEANS, CLEARENCE PER 110.26 SHALL BE IN
 EFFECT. A DISC IS REQUIRED, HOWEVER NOT
 OCP AT THAT LOCATION.
 PLEASE ALSO SEE TANKLESS WATER HEATER IS
 SHOWN ON A 30A 120V CIRCUIT, THIS WOULD
 BE 50+ AMPS. PLEASE CORRELATE KW RATING
 WITH SPEC SHEETS, PLEASE ALSO SEE IF
 THIS UNIT IS INDEED 220V PLEASE ADJUST
 PANEL SCHEDULE.
 PLEASE SEE SOME SHEETS STILL SHOW UNIT
 IN CLOSET.
  
 6)NOTE:PLEASE SEE RECEPTS STILL MISSING
 UNDER 210.52 THESE HAVE BEEN REDLINED
 FOR ALL LOCATIONS.
  
 7)NOTE: PLEASE VERIFY KITCHEN AREA WHICH
 APPEARS TO HAVE A COUNTERSPACE W/OUT A
 GFI. ?? 210.52C1
  
 8)NOTE: PLEASE SEE 210.11C1,220.16
 210.52B WHICH REQUIRES A MIN OF TWO
 SMALL APPLIANCE CIRCUITS. PLEASE SEE
 ONLY ONE IS SHOWN ON LOAD CALCS AND
 PANEL SCHEDULE DOES NOT INDICATE SM APPL
 ??KITCHEN OUTLETS??
  
 PLEASE BE SURE TO REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO SETS. ONE COPY OF OLD SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
  
  
 PLEASE SEE MANY OF THE ABOVE ITEMS HAVE
 BEEN REDLINED ON PLANS FOR LOCATIONS OF
 NOTES.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  