| 2005-06-23 00:00:00 | ************* UNSAT ************** |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDDRESSED AND |
| | NEW NOTES DUE TO CHANGES IN PLANS. |
| | |
| | 1)NOTE: PLEASE SEE SEE 2 MCB PANELS ARE |
| | NOW INDICATED ON RISER, HOWEVER ONLY ONE |
| | PANEL "A" IS SHOWN ON PLANS. PLEASE |
| | LOCATION OF PANEL "B". PLEASE SEE 230.72 |
| | FOR GROUPING OF MAINS. |
| | PLEASE SEE PANELS ARE INDICATED AS 42 |
| | CIRCUIT ON RISER, HOWEVER PANEL |
| | SCHEDULES INDICATE 30 CIR? |
| | |
| | 2)NOTE: PLEASE SEE SIZE OF GROUNDING |
| | ELECTRODE CONDUCTOR IS MISSING. PLEASE |
| | SEE 250.50,250.66 FOR SIZING. #2 MIN. |
| | |
| | 3)NOTE: PLEASE SEE PANEL SCHEDULES ARE |
| | NOW SHOWN, HOWEVER PLEASE SEE LOADS FOR |
| | EACH ARE NOT SHOWN. PLEASE SHOW LOAD FOR |
| | EACH. 220,215.5 |
| | PLEASE ALSO COIRRELATE PANEL SCHEDULES |
| | AND LOAD CALCULATIONS. PLEASE SEE THERE |
| | ARE ITEMS LISTED ON LOAD CALCS, BUT NOT |
| | ON PANEL SCHEDULE AND ITEMS ON PANEL |
| | SCHEDULES, BUT NOT ON LOAD CALCS. |
| | PLEASE SEE REDLINED SET. |
| | COOKTOP,OVEN, SMALL APPL |
| | |
| | 4)NOTE: PLEASE SEE NEC 220.31 ETC FOR |
| | MIN LOADS TO BE INDICATED. PLEASE SEE |
| | ALL CONTINUOUS LOADS ARE TO BE SHOWN AT |
| | 125%. POOL PUMP, POOL HEAT PUMP,, |
| | 215.3,230.42 ETC. |
| | |
| | 5)NOTE: PLEASE SEE TANKLESS WATER |
| | PRODUCT CUT SHEETS STILL NEED TO SHOW |
| | SOME SORT OF LISTINGS FROMA NRTL. |
| | 110.3 PLEASE SEE A MIAMI-DADE PRODUCT |
| | APPROVAL IS NOT ON THE LIST OF A NRTL. |
| | NATIONALLY RECOGNIZED TESTING |
| | LABORATORY; UL, CSA, ETL, MET, TUV, ETC |
| | ** NOTE, IF LOCATED UNDER SINK, ALL MIN |
| | CLEARENCE SHALL BE MAINTAINED AND IF OCP |
| | IS PROVIDED IN RFEQUIRED DISCONNECTING |
| | MEANS, CLEARENCE PER 110.26 SHALL BE IN |
| | EFFECT. A DISC IS REQUIRED, HOWEVER NOT |
| | OCP AT THAT LOCATION. |
| | PLEASE ALSO SEE TANKLESS WATER HEATER IS |
| | SHOWN ON A 30A 120V CIRCUIT, THIS WOULD |
| | BE 50+ AMPS. PLEASE CORRELATE KW RATING |
| | WITH SPEC SHEETS, PLEASE ALSO SEE IF |
| | THIS UNIT IS INDEED 220V PLEASE ADJUST |
| | PANEL SCHEDULE. |
| | PLEASE SEE SOME SHEETS STILL SHOW UNIT |
| | IN CLOSET. |
| | |
| | 6)NOTE:PLEASE SEE RECEPTS STILL MISSING |
| | UNDER 210.52 THESE HAVE BEEN REDLINED |
| | FOR ALL LOCATIONS. |
| | |
| | 7)NOTE: PLEASE VERIFY KITCHEN AREA WHICH |
| | APPEARS TO HAVE A COUNTERSPACE W/OUT A |
| | GFI. ?? 210.52C1 |
| | |
| | 8)NOTE: PLEASE SEE 210.11C1,220.16 |
| | 210.52B WHICH REQUIRES A MIN OF TWO |
| | SMALL APPLIANCE CIRCUITS. PLEASE SEE |
| | ONLY ONE IS SHOWN ON LOAD CALCS AND |
| | PANEL SCHEDULE DOES NOT INDICATE SM APPL |
| | ??KITCHEN OUTLETS?? |
| | |
| | PLEASE BE SURE TO REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO SETS. ONE COPY OF OLD SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | |
| | |
| | PLEASE SEE MANY OF THE ABOVE ITEMS HAVE |
| | BEEN REDLINED ON PLANS FOR LOCATIONS OF |
| | NOTES. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |