| 2005-04-01 00:00:00 | ************* UNSAT ************ |
| | |
| | 1)NOTE: PLEASE SUBMIT COMPLETED PLANS: |
| | PANEL SCHEDULE(S) SHOWING ALL MIN |
| | REQUIRED CIRCUITING PER 2002 NEC. |
| | PLEASE INCLUDE OCP/AWG'S ETC. |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE SEE RISER SHOWS AN |
| | ADDITIONAL 150A MCB PANELAND MENTIONS |
| | "IF REQUIRED" PLEASE CLARIFY. |
| | PLEASE ALSO INCLUDE THIS PANEL"B" ON |
| | PLANS IF IT WILL BE USED/INSTALLED. |
| | UNABLE TO VERIFY THIS DUE TO PREVIOUS |
| | COMMENT. |
| | PLEASE SEE BOTH OF THESE 150A MCB PANELS |
| | ARE SHOWN WITH #10 AWG. PLEASE SEE THIS |
| | BEING A POSSIBLE MISPRINT. |
| | 310.15B6,215.5 |
| | |
| | 3)NOTE: PLEASE SEE NUMEROUS RECEPTS |
| | SHOWN ON PLANS WHICH ARE NOT SHOWN AS |
| | GFI, OR GFI PROTECTED. |
| | PLEASE SEE 210.8 FOR GARAGE, FRONT/ REAR |
| | OUTSIDE, 6' OF SINKS, ETC ETC. |
| | |
| | ** THIS IS ONLY A NOTE** |
| | PLEASE SEE THERE IS ONLY ONE RECEPT |
| | SHOWN ON OUTSIDE/REAR SMALL PATIO. |
| | |
| | 4)NOTE: PLEASE SEE MISSING RECEPTS PER |
| | 210.52 IN LIV RM. |
| | |
| | 5)NOTE: PLEASE SUBMIT MANUFACTURE SPEC |
| | SHEETS FOR "TANKLESS WATER " SHOWN IN |
| | CLOTHES CLOSET. PLEASE SEE THIS IS NOT |
| | PERMITTED IN CLOSET PER 422.17 |
| | PLEASE BE SURE PAPERWORK INCLUDE NRTL |
| | LISTING. |
| | |
| | 6)NOTE: PLEASE SEE PLANS SHOWS A PANEL |
| | FOR "STRUCTURE WIRING"?? |
| | PLEASE SUBMIT INFORMATION ON THIS |
| | SYSTEM, INCLUDING ALL SPECS FROM |
| | MANUFACTURE. MUST SUBMIT ALL INFORMATION |
| | UNDER THESE PLANS OR SEPARATE PERMIT |
| | WILL BE REQUIRED. |
| | |
| | 7)NOTE: PLEASE INCLUDE LOAD CALCULATIONS |
| | AS REQUIRED UNDER 220.31, ETC. |
| | PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | 215.5 |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | INSERT NEW REVISED SHEETS INTO TWO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |