2005-04-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) WATER HEATER REQUIRES A PAN PER
 SECTION 504.8
 2) PAN DRAIN SHALL EXTEND FULL-SIZE AND
 TERMINATE OVER A SUITABLY LOCATED
 INDIRECT WASTE RECEPTOR. SECTION 504.8.
 THE SANT TRAP OF THE SINK IS NOT
 APPROVED. SECTIONS 802.3 & 802.3.2.
 3) THE RELIEF VALVE SHALL DISCHARGE
 FULL SIZE TO A SAFE PLACE OF DISPOSAL,
 SHALL NOT SHALL NOT HAVE ANY TRAPPED
 SECTIONS, AND SHALL HAVE A VISIBLE AIR
 GAP OR AIR GAP FITTING LOCATED IN THE
 SAME ROOM AS THE WATER HEATER. SECTION
 504.7.
 4) WHERE DEVICES SUCH AS FILTERS
 DISCHARGE NONPOTABLE WATER TO THE
 BUILDING DRAINAGE SYSTEM, THE DISCHARGE
 SHALL BE THROUGH AN INDIRECT WASTE PIPE.
 SECTION 802.1.4 - SUBMIT A DETAIL
 SHOWING HOW THIS WILL BE ACCOMPLISHED.
 5) SHT P-1 AIR HAMMER ARRESTORS ARE
 REQUIRED AT THE DISHWASHER AND THE ICE
 MAKER, AND SHALL BE LOCATED NEAR THE
 FIXTURES IN AN "EFFECTIVE RANGE" NOT IN
 THE CEILING. PDI-WH 201 AND MANUF.
 INSTALLATION INSTRUCTIONS. SECTION 604.9
 5) SHT A-3.0 DETAIL 01 INDICATE
 COMPLIANCE WITH SECTIONS 11-4.24.6 &
 11-4.24.7, EXPOSED PIPES AND SURFACES
 AND FAUCETS.
 6) WATER HEATERS SHALL BE LOCATED AND
 CONNECTED SO AS TO PROVIDE ACCESS FOR
 OBSERVATION, AMINTENANCE, SERVICING AND
 REPLACEMENT. PLEASE SUBMIT A DETAIL
 SHOWING COMPLIANCE.
  