| 2005-04-23 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | |
| | 1) WATER HEATER REQUIRES A PAN PER |
| | SECTION 504.8 |
| | 2) PAN DRAIN SHALL EXTEND FULL-SIZE AND |
| | TERMINATE OVER A SUITABLY LOCATED |
| | INDIRECT WASTE RECEPTOR. SECTION 504.8. |
| | THE SANT TRAP OF THE SINK IS NOT |
| | APPROVED. SECTIONS 802.3 & 802.3.2. |
| | 3) THE RELIEF VALVE SHALL DISCHARGE |
| | FULL SIZE TO A SAFE PLACE OF DISPOSAL, |
| | SHALL NOT SHALL NOT HAVE ANY TRAPPED |
| | SECTIONS, AND SHALL HAVE A VISIBLE AIR |
| | GAP OR AIR GAP FITTING LOCATED IN THE |
| | SAME ROOM AS THE WATER HEATER. SECTION |
| | 504.7. |
| | 4) WHERE DEVICES SUCH AS FILTERS |
| | DISCHARGE NONPOTABLE WATER TO THE |
| | BUILDING DRAINAGE SYSTEM, THE DISCHARGE |
| | SHALL BE THROUGH AN INDIRECT WASTE PIPE. |
| | SECTION 802.1.4 - SUBMIT A DETAIL |
| | SHOWING HOW THIS WILL BE ACCOMPLISHED. |
| | 5) SHT P-1 AIR HAMMER ARRESTORS ARE |
| | REQUIRED AT THE DISHWASHER AND THE ICE |
| | MAKER, AND SHALL BE LOCATED NEAR THE |
| | FIXTURES IN AN "EFFECTIVE RANGE" NOT IN |
| | THE CEILING. PDI-WH 201 AND MANUF. |
| | INSTALLATION INSTRUCTIONS. SECTION 604.9 |
| | 5) SHT A-3.0 DETAIL 01 INDICATE |
| | COMPLIANCE WITH SECTIONS 11-4.24.6 & |
| | 11-4.24.7, EXPOSED PIPES AND SURFACES |
| | AND FAUCETS. |
| | 6) WATER HEATERS SHALL BE LOCATED AND |
| | CONNECTED SO AS TO PROVIDE ACCESS FOR |
| | OBSERVATION, AMINTENANCE, SERVICING AND |
| | REPLACEMENT. PLEASE SUBMIT A DETAIL |
| | SHOWING COMPLIANCE. |
| | |
| | REVIEW BY KEN STEVENS |