| Date |
Text |
| 2005-12-13 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FBC-2001 BUILDING |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | CITY WPB CODE |
| | |
| | 1) PLUMBING PLANS ARE INCOMPLETE THIS |
| | SUBMITTAL AND MORE COMMENTS MAY BE |
| | FORTHCOMING ON THE NEXT REVIEW. SUBMIT |
| | THE FOLLOWING: - SEE NEW COMMENTS. |
| | A. EMERGENCY WATER HEATER PAN BUILDING |
| | ISOMETRIC AND RISER DIAGRAMS. SHOW |
| | MATERIAL TO BE USED. SHOW PIPE SIZE. |
| | SHOW TERMINATION POINT. - RESPONSE NOTED |
| | BUT HUB DRAIN INDICATED ON PAN DRAIN |
| | RISER DIAGRAM NOT FOUND ON ANY SYSTEM. |
| | PLEASE CLARIFY. SECTION 104.2.1. |
| | C. CONDENSATE BUILDING DRAIN ISOMETRIC |
| | AND RISER DIAGRAMS. SHOW MATERIAL TO BE |
| | USED. SHOW PIPE SIZE. SHOW TERMINATION |
| | POINT AND VENT TERMINATION. - RESPONSE |
| | NOTED, BUT CONDENSATE VENT SHALL NOT |
| | CONNECT TO THE SANITARY SYSTEM. ALSO |
| | CONDENSATE SYSTEM REQUIRES A RELIEF VENT |
| | (GOOSENECK) AS IT EXITS THE BUILDING. |
| | (SECTIONS 104.2.1, 504.7.1, 504.7.2, |
| | 504.8.1, 504.8.2, CITY CODE 90-125(5). |
| | 3) SHTS P3.03, P3.04, & P3.05. |
| | B. EVERY VENT STACK SHALL CONNECT TO THE |
| | BASE OF THE DRAINAGE STACK. THE VENT |
| | SHALL CONNECT AT OR BELOW THE LOWEST |
| | HORIZONTAL BRANCH. SECTION 903.4. - |
| | RESPONSE NOTED, BUT SOME VENTS ARE |
| | CONNECTED TO BRANCH LINES AND NOT THE |
| | BASE OF THE STACK AS REQUIRED. |
| | I. RISER S/9-S/34 DOES NOT REFLECT THE |
| | FLOOR PLAN AT THE 8TH FLOOR- RISER AND |
| | FLOOR PLANS STILL DO NOT REFLECT EACH |
| | OTHER.. |
| | 4) MORE INFORMATION REQUIRED. ARE THERE |
| | TOWNHOUSE UNITS ON SHT P2.001? PIPING |
| | SEEMS TO INDICATE THAT THERE ARE, BUT NO |
| | FLOOR PLAN SHOWN FOR THESE UNITS. IF NOT |
| | IS THE PIPING IN THE CEILING FOR THE |
| | NEXT FLOOR? SHEETS P2.01.1 & P2.01.2 |
| | STATE "PARTIAL 1ST LEVEL PARKING, 1ST |
| | LEVEL TOWNHOUSE FLOOR PLAN. IS THE LOWER |
| | PARKING FLOOR PLAN AT GRADE LEVEL? IF SO |
| | IS THE 1ST LEVEL TOWNHOUSE ON THE 2ND |
| | FLOOR? PLEASE CLARIFY. - PIPING STILL |
| | INDICATES KITCHEN SINKS ARE ON THE |
| | GROUND FLOOR. PLEASE CLARIFY. (SEE NEW |
| | COMMENT CONCERNING PIPING LAYOUTS) |
| | 5) SHTS P2.00.1 & P2.00.2 SHOW ALL PIPE |
| | SIZES, INDICATE RISER NUMBER ON ALL |
| | RISERS, SHOW FIXTURE UNITS AS THEY |
| | ACCUMULATE IN THE SYSTEM, SHOW SQUARE |
| | FOOTAGE AS IT ACCUMULATES IN THE SYSTEM. |
| | - THESE ITEMS STILL NOT ADDRESSED FULLY. |
| | SECTION 104.2.1, AND TABLES 710.1(1), |
| | 1106.2 & 1106.3. |
| | 6) SHTS P2.01.1 & P2.01.2 SHOW ALL PIPE |
| | SIZES, RISER DESIGNATION NUMBERS. SANT. |
| | PIPING SHOWN ON FLOOR PLAN OF TOWNHOUSES |
| | DOES NOT SEEM TO CONNECT TO ANY |
| | FIXTURES. PLEASE CLARIFY. - RESPONSE |
| | NOTED, BUT ALL PIPING LAYOUTS SHALL BE |
| | SHOWN ON THE FLOOR PLAN FOR EACH FLOOR. |
| | SHOWING THE PIPING ON PREVIOUS SHEETS |
| | (BELOW THE SLAB) IS NOT OF SUFFICIENT |
| | CLARITY. SECTION 104.2.1. - SOME SHEETS |
| | SHOW SOME OF THE PIPING ON THE FLOOR |
| | PLAN AND SOME OF THE PIPING BELOW THE |
| | FLOOR PLAN. |
| | 7) SHTS P2.02.1 & P2.02.2 SHOW THE |
| | LOCATION OF ALL RISERS FOR ALL SYSTEMS. |
| | SECTION 104.2.1. - RESPONSE NOTED, BUT |
| | ALL RISERS SHALL BE SHOWN INCLUDING W/M |
| | AND RWL RISERS. |
| | 8) SHTS P2.03.1 & P2.03.2 SHOW THE COL. |
| | LINES SO RISERS CAN BE TRACED FROM ONE |
| | FLOOR TO THE NEXT. SHOW ALL RISERS AND |
| | INDICATE LOCATION AND RISER NUMBER. SHOW |
| | ALL PIPE SIZES. MOST OF THESE FIXTURES |
| | ARE NOT SHOWN ON THE RISER DIAGRAMS. |
| | PLEASE CLARIFY. SECTION 104.2.1. - |
| | RESPONSE NOTED, BUT RWL RISERS ARE NOT |
| | SHOWN AND THE PIPING FOR THE FIXTURES |
| | SHALL BE SHOWN. (SEE COMMENT #6). |
| | 9) SHTS P2.04.1 & P2.04.2THESE |
| | FIXTURES ARE NOT SHOWN ON THE RISER |
| | DIAGRAMS OR THE SANT. BUILDING DRAIN |
| | ISOMETRICS. SHTS P3.060 & P3.061. SUBMIT |
| | RISER DIAGRAMS SHOWING THESE FIXTURES. |
| | SHOW ALL PIPE SIZES. SECTIONS 104.2.1, |
| | AND 104.3.1.1. RESPONSE NOTED, BUT PIPE |
| | SIZES ARE NOT SHOWN AND THE PIPING |
| | LAYOUTS SHALL BE SHOWN FOR THE FLOOR |
| | PLAN SUPERIMPOSED OVER THE FIXTURES THEY |
| | CONNECT TO. SHOW RWL RISERS. |
| | 10) SHTS P2.05.1 & P2.05.2 RISERS 2/4, |
| | S/5, S/13, S/26, S/28, & S/37 DO NOT |
| | REFLECT THE FLOOR PLAN. RISERS S/13, |
| | S/25, & S/40 SHOW ALL PIPING. SECTION |
| | 104.2.1. - SUBMIT CALCULATIONS FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS FOR |
| | THE 4TH FLOOR ELEVATION. SHOW SF OF EACH |
| | AREA AND SHOW 1/2 AREA OF ALL VERTICAL |
| | WALLS INCLUDING PARAPETS ADDED TO |
| | CALCULATIONS AS WELL AS AREA OF ANY ROOF |
| | THAT DRAINS ONTO THE AREAS FROM ABOVE. |
| | SECTIONS 1106 & 1107 AND ALL |
| | SUBSECTIONS. SHOW THE LOCATION OF ALL |
| | PRIMARY AND SECONDARY DRAINS. - RESPONSE |
| | NOTED, BUT THE CALCULATIONS REQUESTED |
| | WERE NOT SUBMITTED. ALSO SHOW THE |
| | LOCATIONS FOR ALL SECONDARY DRAINS. |
| | 11) SUBMIT THE FOLLOWING: RISER DIAGRAMS |
| | FOR THE TOWNHOUSE UNITS. UNITS ON THE |
| | 1ST, 2ND, AND THIRD FLOORS. THE |
| | FOLLOWING RISER DIAGRAMS WERE NOT |
| | LOCATED: S/3, S/27, ALL W/M RISERS. |
| | SECTIONS 104.2.1, & 104.3.1.1. |
| | 12) SHTS P2.06.1 & P2,06.2 SHOW RISER |
| | S/25 NUMBER DESIGNATION. - SHOW PIPING |
| | FOR RISER S/25, S/13, S/37, & S/40 - |
| | RISERS S/4, S/5, S/13. S/26, S/28, & |
| | S/37 DO NOT REFLECT THE RISER DIAGRAM. |
| | SECTION 104.2.1. RESPONSE NOTED, BUT NO |
| | FIXTURES WERE SHOWN ON THE FLOOR PLAN |
| | FOR RISER S/40 AND S/13-S/37 SHOW NO |
| | PIPING TO THE W/C'S. |
| | 13) SHTS P2.07.1 & PS.07.2 RISERS DO NOT |
| | REFLECT THE RISER DIAGRAMS: S/4, S/13, |
| | S/28, & S/37. FOLLOWING RISERS SHALL |
| | SHOW DWV PIPING ON THE FLOOR PLAN: S/4, |
| | S/13, S/15, S/16, S/17, S/19, S/20, |
| | S/21, S/22, S/23, S/24, S/25, S/28, |
| | S/37, & S/40. RISER S/29 MISLABLED AS |
| | S/19. SECTION 104.2.1. - RESPONSE NOTED, |
| | BUT S/28 STILL DOES NOT REFLECT THE |
| | PIPING LAYOUT ON THE FLOOR PLAN. |
| | 14) SHTS P2.08.1 & P2.08.2 RISERS S/1, |
| | S/13, S/28, & S/37 DO NOT REFLECT THE |
| | RISER DIAGRAMS. SHOW THE DWV PIPING FOR |
| | THE FOLLOWING RISERS: S/4, S/9, S/12, |
| | S/13, S/29, S/34, S/37, & S/38. - SHOW |
| | THE LOCATIONS FOR THE FOLLOWING VTR'S AS |
| | SHOWN ON RISER DIAGRAMS: S/16, S/19, |
| | S/20, S/21, S/22, S/23, S/25, & S/40. |
| | SECTION 104.2.1. - RESPONSE NOTED, BUT |
| | THE VENTING ROUTE SHALL BE SHOWN ON THE |
| | FLOOR PLAN, AND RISER VENT ROUTED TO |
| | SHALL BE INDICATED SO AS TO SIZE THE |
| | VENTS PER TABLE 916.1. |
| | 16) SHTS P2.10.1 & P2.10.2 SUBMIT |
| | CALCULATIONS FOR PRIMARY AND SECONDARY |
| | ROOF DRAINS. SHOW SQUARE FEET OF EACH |
| | AREA AND SHOW 1/2 AREA OF ALL VERTICAL |
| | WALLS AS WELL AS ALL ROOF AREA THAT |
| | DRAINS DOWN TO ROOF FROM ABOVE IN |
| | CALCULATIONS PER SECTIONS 1106 & 1107 |
| | AND ALL SUBSECTIONS. SHOW THE LOCATION |
| | OF ALL SECONDARY DRAIN AND/OR SCUPPERS. |
| | SUBMIT A DETAIL FOR SCUPPERS SHOW HEIGHT |
| | AND WIDTH TO SHOW SQ.IN. AREA OF |
| | SCUPPER. - INDICATE LOCATION OF ALL VTR. |
| | - RESPONSE NOTED, BUT CALCULATIONS WERE |
| | NOT SUBMITTED OR LOCATED. RISER S/20 VTR |
| | NOT LOCATED. |
| | 18) SHTS P3.07.0 &P3.07.1 ROOF DRAIN, |
| | OVERFLOW DRAINS, DECK DRAINS, OVERFLOW |
| | DECK DRAINS, PARKING DRAINS ECT WILL BE |
| | REVIEWED AFTER THE CALCULATIONS FOR THE |
| | DRAINS HAS BEEN CHECKED. ONE SET OF ROOF |
| | DRAINS/OVERFLOW DRAINS (5900 SF) HAS |
| | BEEN CROSSED BETWEEN THE OVERFLOW AND |
| | DRAIN. ONE SET OF RWL/OVERFLOW RWL ARE |
| | SO CLOSE THE SYSTEMS CAN NOT BE CHECKED |
| | FOR COMPLIANCE. PLANS SHALL HAVE |
| | SUFFICIENT CLARITY TO REVIEW. - SUMP |
| | PUMP FOR PARKING AREA DRAINS SHALL BE |
| | LISTED. SUBMIT MANUF. SPECIFICATIONS |
| | SHEETS. SECTIONS 303.4.1, & 104.2.1. - |
| | RESPONSE NOTED, BUT CALCULATIONS WERE |
| | NOT SUBMITTED OR LOCATED. |
| | 19) SHTS A2.03, A2.09, & A4.91 THRU |
| | A4.95 SUBMIT CALCULATIONS FOR PRIMARY |
| | AND SECONDARY ROOF DRAINS. SHOW SQUARE |
| | FEET OF EACH AREA, AND SHOW 1/2 AREA OF |
| | ALL VERTICAL WALLS INCLUDING PARAPETS, |
| | AS WELL AS AREAS OF ROOFS THAT DRAIN |
| | ONTO THE ROOF AREAS FROM ABOVE ADDED IN |
| | CALCULATIONS. SECTIONS 1106, AND 1107 |
| | AND ALL SUBSECTIONS. - NO RESPONSE NO |
| | CALCULATIONS SUBMITTED. |
| | 20) SHT A1.06 SUBMIT A DETAIL SHOWING |
| | COMPLIANCE WITH FHA REQUIREMENTS 3 THRU |
| | 7, PAGE 7.33 FOR TOWNHOUSE UNITS. POWDER |
| | ROOM SHALL BE COMPLIANT. |
| | 24) SHOW BACKING FOR UNITS PER |
| | SPECIFICATION 6 OF THE FHA DESIGN MANUAL |
| | - RESPONSE NOTED, BUT THE BACKING DETAIL |
| | SHALL REFLECT THE DESIGN MANUAL AND SHOW |
| | DIMENSIONS OFF THE FLOOR, LENGTH AND |
| | WIDTH OF THE BACKING. |
| | 25) SHTS A4.32 & A4.35 SECONDARY ROOF |
| | DRAINS, (OVERFLOW DRAINS) SHALL BE |
| | LOCATED 2" ABOVE THE PRIMARY ROOF DRAINS |
| | PER SECTION 1503.4.2. PLEASE INDICATE |
| | HOW THIS WILL BE ACCOMPLISHED. IN SOME |
| | AREAS THE OVERFLOW DRAIN IS IN CLOSE |
| | PROXIMITY TO THE PRIMARY ROOF DRAIN. |
| | SECTION 1503.4.2. - RESPONSE NOTED, BUT |
| | AFTER SPEAKING TO THE BUILDING OFFICIAL, |
| | HE QUESTIONS THE DESIGN AND INDICATES |
| | THE POOLING EFFECT IN A HEAVY RAIN WILL |
| | HAVE WATER IN THE UNIT. SUBMIT |
| | CALCULATIONS SHOWING THE DRAINS FOR THE |
| | TERRACHS WILL MEET THE POOLING EFFECT |
| | FOR THE 4.5" RAINFALL SHOWN ON FIGURE |
| | 1106.1 SHTS A4.32 & A4.35 INDICATE THE |
| | FLOOR ELEVATION TO BE 128'9" AND THE |
| | PATIO SLAB TO BE 128'3". PLEASE CLARIFY |
| | HOW THAT WILL BE ONLY 3/4" FROM DRAIN TO |
| | THRESHOLD. |
| | **************NEW COMMENTS************** |
| | 1B. ALL PIPING FOR EACH FLOOR SHALL BE |
| | SHOWN ON THE FLOOR PLAN WITH THE |
| | FIXTURES SHOWN. SHOW ALL PIPE SIZES ON |
| | EACH FLOOR PLAN. SHOWING THE PIPING |
| | LAYOUT ON PREVIOUS SHEET IS CONFUSING |
| | AND ADDS MANY HOURS TO THE PLAN REVIEW. |
| | SOME SHEETS SHOW SOME OF THE PIPING ON |
| | THE SHEET WITH THE FIXTURES AND ALSO |
| | SHOW SOME PIPING ON PREVIOUS SHEETS. |
| | 2B. CPVC IN THE PLENUMS IS NOT APPROVED |
| | UNLESS IT IS FILLED WITH WATER. PER |
| | MANUF. SPECIFICATIONS THE CPVC FOR THE |
| | P/T, PAN DRAIN AND CONDENSATE IS NOT |
| | APPROVED. PLEASE INDICATE AN ALTERNATIVE |
| | MATERIAL. |
| | 3B. SHT P2.08.2 SHOW THE LOCATION OF THE |
| | FLOOR DRAIN SHOWN ON RISER 2/22 7TH |
| | FLOOR. FLOOR DRAIN SHALL NOT DRAIN STORM |
| | WATER. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |