| 2005-12-30 00:00:00 | DENIED: |
| | PLEASE PROVIDE ADDITIONAL CLARIFICATION |
| | TO THE RESPONSES GIVEN TO COMMENTS FROM |
| | REVIEW DATED 6-9-05. |
| | |
| | COMMENT #3 PLAN SHEET AC0.02 GENERAL FAN |
| | NOTE #16, PLEASE REVISE NOTE TO INDICATE |
| | THE CARBON MONOXIDE SENSOR SHALL |
| | ACTIVATE GARAGE FAN AT A MAXIMUM OF 25 |
| | PPM IN ACCORDANCE WITH 2001 FMC 403.4. |
| | PLEASE INDICATE THIS ON REFERENCES TO CO |
| | SENSORS.TESTING WILL BE REQUIRED AT |
| | FINAL INSPECTION. |
| | |
| | COMMENT #5 RESPONSE STATES EXHAUST & |
| | MAKEUP AIR CANNONT BE TAKES TO THE |
| | OUTDOORS.PLEASE PROVIDE CO SENSORS |
| | INSIDE THESE VARIOUS ROOMS. |
| | |
| | COMMENT #6 NOXIOUS EXHAUST TERMINATING |
| | WITHIN 10 FT OFF FRESH AIR INTAKES. |
| | RESPONSE ONLY ADDRESSED SOME OF THE |
| | ISSUES.PLAN SHEET AC2.01.2 SEF-9 IS |
| | TERMINATING OVER AN EXIT DOOR AS IS |
| | GEF-6 WHICH AS 12,500 CFM OF |
| | NOXIOUS/TOXIC EXHAUST TERMINATING ABOVE |
| | A DOOR.EXHAUST SHALL NOT TERMINATE |
| | ONTO WALKWAYS - 2001 FMC 401.5.1. |
| | |
| | COMMENT #10PLAN SHEET AC0.003 & |
| | RESPONSE TO COMMENT #10, INDICATE O.A. |
| | FOR THE RESIDENCE BY INFILTRATION BY THE |
| | 'CRACK METHOD'.SHOULD THIS REFER TO |
| | THE MAXIMUM INFILTRATION RATES GIVEN IN |
| | CHAPTER 13 OF THE FBC, THE INFILTRATION |
| | RATE MAY NOT ALLOW THE MAXIMUM THEREFORE |
| | IS SPECULATIVE AS IS THE 50 CFM FROM THE |
| | CORRIDOR. |
| | |
| | COMMENT #12 INFORMATION ON THE |
| | GENERATOR.RESPONSE STATES SUB-BASE |
| | FUEL TANK.PLEASE CLARIFY DIESEL FUEL. |
| | PLEASE PROVIDE MANUFACTURER SUBMITTAL |
| | DATA.PLEASE NOTE WINDOW IN THE UNIT |
| | #118 & 119 ARE WITHIN 10 FT OF THE |
| | EXHAUST TERMINATION. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |
| | |
| | |
| | |