2005-12-30 00:00:00DENIED:
 PLEASE PROVIDE ADDITIONAL CLARIFICATION
 TO THE RESPONSES GIVEN TO COMMENTS FROM
 REVIEW DATED 6-9-05.
  
 COMMENT #3 PLAN SHEET AC0.02 GENERAL FAN
 NOTE #16, PLEASE REVISE NOTE TO INDICATE
 THE CARBON MONOXIDE SENSOR SHALL
 ACTIVATE GARAGE FAN AT A MAXIMUM OF 25
 PPM IN ACCORDANCE WITH 2001 FMC 403.4.
 PLEASE INDICATE THIS ON REFERENCES TO CO
 SENSORS.TESTING WILL BE REQUIRED AT
 FINAL INSPECTION.
  
 COMMENT #5 RESPONSE STATES EXHAUST &
 MAKEUP AIR CANNONT BE TAKES TO THE
 OUTDOORS.PLEASE PROVIDE CO SENSORS
 INSIDE THESE VARIOUS ROOMS.
  
 COMMENT #6 NOXIOUS EXHAUST TERMINATING
 WITHIN 10 FT OFF FRESH AIR INTAKES.
 RESPONSE ONLY ADDRESSED SOME OF THE
 ISSUES.PLAN SHEET AC2.01.2 SEF-9 IS
 TERMINATING OVER AN EXIT DOOR AS IS
 GEF-6 WHICH AS 12,500 CFM OF
 NOXIOUS/TOXIC EXHAUST TERMINATING ABOVE
 A DOOR.EXHAUST SHALL NOT TERMINATE
 ONTO WALKWAYS - 2001 FMC 401.5.1.
  
 COMMENT #10PLAN SHEET AC0.003 &
 RESPONSE TO COMMENT #10, INDICATE O.A.
 FOR THE RESIDENCE BY INFILTRATION BY THE
 'CRACK METHOD'.SHOULD THIS REFER TO
 THE MAXIMUM INFILTRATION RATES GIVEN IN
 CHAPTER 13 OF THE FBC, THE INFILTRATION
 RATE MAY NOT ALLOW THE MAXIMUM THEREFORE
 IS SPECULATIVE AS IS THE 50 CFM FROM THE
 CORRIDOR.
  
 COMMENT #12 INFORMATION ON THE
 GENERATOR.RESPONSE STATES SUB-BASE
 FUEL TANK.PLEASE CLARIFY DIESEL FUEL.
 PLEASE PROVIDE MANUFACTURER SUBMITTAL
 DATA.PLEASE NOTE WINDOW IN THE UNIT
 #118 & 119 ARE WITHIN 10 FT OF THE
 EXHAUST TERMINATION.
  