| Notes |
| Date |
Text |
| 2005-11-16 00:00:00 | | | | PROVISO | | | | | | ALL DWELLING UNIT EWH CIRCUITS IN ALL | | | DWELLING PANELS ARE IN VOILATION OF | | | 422.11(E). THE OCP IS TOO LARGE FOR THE | | | INDICATED LOADS. | | | | | | ALTHOUGH THIS WAS DISCUSSED, AFTER DOING | | | THE MATH AGAIN ON THIS REVIEW I STILL | | | CONTEND THE OCP'S ARE INCORRECT.IG: | | | PANEL A1 EWH LISTED @ 3000VA/208V(SINGLE | | | PHASE)=14.42AMPS X 150%(422.11(E))=21.6 | | | OR 22AMPS. PER 422.11(E)(3)25AMP BREAKER | | | WOULD BE PERMITTED. THE PANEL SCHEDULE | | | INDICATES A 40 AMP BREAKER. | | | | | | PLEASE CORRECT THE PANEL SCHEDULES ON | | | THE NEXT REVISION. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|