| 2006-01-04 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05031504 |
| | ADD: 2323 N FLAGLER DR BLDG. "E" |
| | BARCELONA SQUARE I |
| | |
| | CONT:FIRST BLDG CORP OF FLORIDA |
| | TEL:(954)561-4900 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | NOTE IF A COMMENT IS MADE ON A |
| | PARTICULAR SHEET THIS COMMENT MAY NOT |
| | APPEAR ON OTHER SHEET.LOOK FOR COMMENTS |
| | BY OTHER PLAN REVIEW DISCIPLINES THAT |
| | MAY BE WRITTEN ON THE APPLICATION, |
| | PLANS, OR ATTACHED SEPARETLY. WHEN |
| | RESUBMITTING PLANS PLEASE CLEARLY |
| | INDICATE THE REVISION & REMOVE & REPLACE |
| | ANY PAGES AS NESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET |
| | OR SPECIFICATION PAGE WHERE THE CHANGES |
| | CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT . THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2)COMMENT# 6 FROM THE PEVIOUS REVIEW, |
| | SHEET A2.01, A2.02 REFERNCES THE TERM |
| | "TOWNHOUSE", THE LEGAL TERM (DEFINITION) |
| | IS A SINGLE FAMILY DWELLING CONSTRUCTED |
| | IN A SERIES OF ATTACHED UNITS WITH |
| | PROPERTY LINES SEPERATING EACH UNIT. SEE |
| | DEFINITIONS. THE TRM HAS BEEN REMOVED |
| | FROM THE ARCHITECTURAL SHEETS BUT NOT |
| | THE LIFE SAFETY NOR THE M-E-P SHEETS. |
| | |
| | 3) COMMENT# 9 FROM THE PREVIOUS REVIEW, |
| | THE PRIMARY ENTRY DOOR OF COVERED |
| | DWELLING UNITS IS PART OF PUBLIC AND |
| | COMMON USE SPACES, THEREFORE, IT MUST BE |
| | ON AN ACCESSIBLE ROUTE & BE ACCESSIBLE, |
| | I.E., MEET THE ANSI REQUIREMENTS OF |
| | 4.13 DOORS. ANSI 4.13.9 LEVER OR OTHER |
| | EASY USE DOOR HARDWARE. |
| | THE UNITS LOCATED ON THE S.W. CORNER |
| | DO NOT HAVE AN ACCESSIBLE ROUTE TO THE |
| | WEST LOBBY SINCE THERE ARE STAIRS AND NO |
| | ACCESSIBLE RAMP. |
| | |
| | 4) COMMENT# 37 & 38 FROM THE PREVIOUS |
| | REVIEW, DEAL WITH PRODUCT APPROVALS, |
| | 4A) EXTERIOR LOUVERED DOORS NO REPORTS |
| | WERE SUBMITTED. |
| | 4B) GLAZED DOORS, ARCH FRENCH DOORS, |
| | THE PRODUCT APPROVALS SUBMITTED HAVE |
| | DESIGN PRESSURES OF +62.6/ -64.0. THE |
| | REPORT DOES NOT INDICATE SIDELIGHTS. |
| | WHEN LOOKING AT THE ELEVATIONS THE |
| | SIDELIGHT IS CLEARLY LOCATED IN THE END |
| | ZONES REQUIRING THE HIGHER PRESSURES. |
| | A STRUCTURAL MULLION WITH THE REQUIRED |
| | VALUES FOR THE END ZONE COULD SEPERATE |
| | THE SIDELIGHT AND DOOR FRAME. THE |
| | DESIGNER WILL NEED TO INDICATE HOW THEY |
| | WILL TRANSFER THE LOADS OR THE |
| | CONTRACTOR WILL NEED TO PROVIDE PRODUCT |
| | TESTING REPORTS FOR THE PATIO DOORS WITH |
| | THE HIGHER ASSOCIATED PRESSURES. |
| | 4C) THE REPORT SUBMITTED ARCH FRENCH |
| | DOORS IS FOR SMALL MISSLE HOW WILL YOU |
| | DEAL WITH THE DOORS LOCATED IN THE END |
| | ZONE REQUIRING SHUTTERS 30' TO GRADE. |
| | 4D) PGT FIXED WINDOWS, THE WINDOWS |
| | LOCATED IN THE END ZONES WILL NEED TO |
| | MEET THE REQUIRED -122.4 SEE BOTTOM OF |
| | THE TYPE "C" WINDOWS AND THE WINDOWS |
| | NEXT TO GLASS DOORS LOCATED IN THE END |
| | ZONE. |
| | 4E) SUNSHINE WINDOWS SINGLE HUNG LOCATED |
| | |
| | IN THE END ZONES WILL REQUIRE DESIGN |
| | PRESSURES OF +98/ -168.3. |
| | |
| | 5) COMMENT# 43 FROM THE PREVIOUS REVIEW, |
| | BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 6)PLEASE PROVIDE A SQ FTBREAKDOWN OF |
| | THE FLOOR AREAS PER FLOOR TO PARKING, |
| | A/C AND POOL DECK. THE CALCULATED AREA |
| | THAT I CAME UP WITH IS 338,379 SQ FT. |
| | THIS WILL TRANSLATE INTO A CALCULATED |
| | VALUE OF $26,289,000.00 WHICH WILL |
| | EFFECT PERMIT FEES AND RADON FEES. |
| | |
| | 7) SEE MECHANICAL COMMENT# 6 AS TO |
| | NOXIOUS EXHAUST TERMINATING OVER THE |
| | EXIT AND WITHIN 10' OF WINDOWS. |
| | |
| | 8) NOTE: A SEPERATE PERMIT WILL BE |
| | REQUIRED FOR AWNINGS. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |
| | |
| | |
| | |