Text |
| 2005-05-21 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FBC-2001 BUILDING |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | CITY WPB CODE |
| | |
| | 1) PLUMBING PLANS ARE INCOMPLETE THIS |
| | SUBMITTAL AND MORE COMMENTS MAY BE |
| | FORTHCOMING ON THE NEXT REVIEW. SUBMIT |
| | THE FOLLOWING: |
| | A. EMERGENCY WATER HEATER PAN BUILDING |
| | ISOMETRIC AND RISER DIAGRAMS. SHOW |
| | MATERIAL TO BE USED. SHOW PIPE SIZE. |
| | SHOW TERMINATION POINT. |
| | B. P/T DISCHARGE VALVE RISERS AND BLDG |
| | DRAIN ISOMETRIC. SHOW MATERIAL TO BE |
| | USED. SHOW PIPE SIZE. SHOW TERMINATION |
| | POINT. |
| | C. CONDENSATE BUILDING DRAIN ISOMETRIC |
| | AND RISER DIAGRAMS. SHOW MATERIAL TO BE |
| | USED. SHOW PIPE SIZE. SHOW TERMINATION |
| | POINT AND VENT TERMINATION. |
| | (SECTIONS 104.2.1, 504.7.1, 504.7.2, |
| | 504.8.1, 504.8.2, CITY CODE 90-125(5). |
| | 2) SHT P3.02 WATER RISER DIAGRAMS. SHOWN |
| | ARE 6 FLOOR PLANS FOR THE WATER PIPING. |
| | IS THIS ALL THE FLOOR PLAN TYPES FOR THE |
| | WATER PIPING? |
| | A. WATER HAMMER ARRESTORS ARE REQUIRED |
| | AT THE DISH WASHER AND THE REFRIGERATOR. |
| | SECTION 604.9. THIS IS NOT SHOWN ON |
| | RISERS THAT DO NOT SHOW A SEPARATE LINE |
| | TO THE REF. NOR TO THE DISH WASHERS. |
| | B. HOSE BIBBS REQUIRE A SHUT OFF VALVE |
| | PER SECTION 606.2.(2). |
| | 3) SHTS P3.03, P3.04, & P3.05. |
| | A. ALL RISERS ON ALL SHEETS. EVERY |
| | SANITARY DRAINAGE SYSTEM RECEIVING THE |
| | DISCHARGE OF A WATER CLOSET SHALL HAVE A |
| | MAIN VENT THAT IS EITHER A VENT STACK OR |
| | STACK VENT. SUCH VENT SHALL RUN |
| | UNDIMINISHED IN SIZE AND DIRECTLY AS |
| | POSSIBLE FROM THE BUILDING DRAIN THROUGH |
| | TO THE OPEN AIR ABOVE. SECTION 903.1. |
| | B. EVERY VENT STACK SHALL CONNECT TO THE |
| | BASE OF THE DRAINAGE STACK. THE VENT |
| | SHALL CONNECT AT OR BELOW THE LOWEST |
| | HORIZONTAL BRANCH. SECTION 903.4. - |
| | C. ALL RISERS SHALL SHOW ALL PIPE SIZES. |
| | TABLE 710.1(1). |
| | D. ALL RISERS WITH AIR ADMITTENCE VALVES |
| | SHALL HAVE A RELIEF VENT WHEN INSTALLED |
| | OVER 4 BRANCH INTERVALS BELOW THE TOP OF |
| | THE STACK. SECTION 917.3.2. |
| | E. RISER S/4-S/28 DOES NOT REFLECT THE |
| | FLOOR PLAN AT THE 4TH, 5TH, & 6TH |
| | FLOORS. SECTION 104.2.1. |
| | F. RISER S/15-S/18 DOES NOT REFLECT THE |
| | FLOOR PLAN AT THE 7TH FLOOR. SECTION |
| | 104.2.1. |
| | G. RISERS S/13-S/37, & S/12-S/38 DO NOT |
| | REFLECT THE FLOOR PLAN. NO 9TH FLOOR |
| | SHOWN. PLEASE CLARIFY. SECTION 104.2.1. |
| | H. RISER S/10-S/35 DOES NOT REFLECT THE |
| | FLOOR PLAN ALL FLOORS, AND THE SHOWER IS |
| | NOT VENTED. SECTIONS 104.2.1. & 901.2.1. |
| | I. RISER S/9-S/34 DOES NOT REFLECT THE |
| | FLOOR PLAN AT THE 8TH FLOOR. |
| | - TUB ON ISOMETRIC NOT DRAWN CORRECTLY. |
| | (AS DRAWN IT INDICATES A DOWNWARD DROP |
| | OFF BRANCH LINE) SECTION 104.2.1. |
| | J. RISER S/25-2/40 SHOWER ON ISOMETRIC |
| | NOT DRAWN CORRECTLY. (SEE PREVIOUS |
| | COMMENT). |
| | K. RISER S/20-S/23 DOES NOT REFLECT THE |
| | FLOOR PLAN AT 7TH FLOOR. NO FIXTURES |
| | SHOWN ON THE FLOOR PLAN. - S/22 KITCHEN |
| | SINK PIPED OPPOSITE FROM OTHER RISERS. |
| | INDICATE ON RISER. SECTION 104.2.1. |
| | 4) MORE INFORMATION REQUIRED. ARE THERE |
| | TOWNHOUSE UNITS ON SHT P2.001? PIPING |
| | SEEMS TO INDICATE THAT THERE ARE, BUT NO |
| | FLOOR PLAN SHOWN FOR THESE UNITS. IF NOT |
| | IS THE PIPING IN THE CEILING FOR THE |
| | NEXT FLOOR? SHEETS P2.01.1 & P2.01.2 |
| | STATE "PARTIAL 1ST LEVEL PARKING, 1ST |
| | LEVEL TOWNHOUSE FLOOR PLAN. IS THE LOWER |
| | PARKING FLOOR PLAN AT GRADE LEVEL? IF SO |
| | IS THE 1ST LEVEL TOWNHOUSE ON THE 2ND |
| | FLOOR? PLEASE CLARIFY. - PIPING STILL |
| | INDICATES KITCHEN SINKS ARE ON THE |
| | GROUND FLOOR. PLEASE CLARIFY. |
| | 5) SHTS P2.00.1 & P2.00.2 SHOW ALL PIPE |
| | SIZES, INDICATE RISER NUMBER ON ALL |
| | RISERS, SHOW FIXTURE UNITS AS THEY |
| | ACCUMULATE IN THE SYSTEM, SHOW SQUARE |
| | FOOTAGE AS IT ACCUMULATES IN THE SYSTEM. |
| | CONDENSATE DRAINING FROM THE EAST OF |
| | COL. LINE E1 IS NOT CONNECTED TO DRAIN. |
| | SECTION 104.2.1 AND TABLES 710.1(1), |
| | 1106.2 & 1106.3. |
| | 6) SHTS P2.01.1 & P2.01.2 SHOW ALL PIPE |
| | SIZES, RISER DESIGNATION NUMBERS. SANT. |
| | PIPING SHOWN ON FLOOR PLAN OF TOWNHOUSES |
| | DOES NOT SEEM TO CONNECT TO ANY |
| | FIXTURES. PLEASE CLARIFY. P&T VALVE |
| | DISCHARGE LINES MAY DRAIN INTO AN |
| | INDIRECT WASTE RECEPTOR. FLOOR DRAINS |
| | ARE NOT AN APPROVED I.W. RECEPTOR. |
| | EITHER A FLOOR SINK OR A HUB DRAIN IS |
| | REQUIRED. SECTIONS 104.2.1, 802.3 & |
| | 802.3.2. |
| | 7) SHTS P2.02.1 & P2.02.2 SHOW THE |
| | LOCATION OF ALL RISERS FOR ALL SYSTEMS. |
| | SECTION 104.2.1. |
| | 8) SHTS P2.03.1 & P2.03.2 SHOW THE COL. |
| | LINES SO RISERS CAN BE TRACED FROM ONE |
| | FLOOR TO THE NEXT. SHOW ALL RISERS AND |
| | INDICATE LOCATION AND RISER NUMBER. SHOW |
| | ALL PIPE SIZES. MOST OF THESE FIXTURES |
| | ARE NOT SHOWN ON THE RISER DIAGRAMS. |
| | PLEASE CLARIFY. SECTION 104.2.1. |
| | 9) SHTS P2.04.1 & P2.04.2THESE |
| | FIXTURES ARE NOT SHOWN ON THE RISER |
| | DIAGRAMS OR THE SANT. BUILDING DRAIN |
| | ISOMETRICS. SHTS P3.060 & P3.061. SUBMIT |
| | RISER DIAGRAMS SHOWING THESE FIXTURES. |
| | SHOW ALL PIPE SIZES. SECTIONS 104.2.1, |
| | AND 104.3.1.1. |
| | 10) SHTS P2.05.1 & P2.05.2 RISERS 2/4, |
| | S/5, S/13, S/26, S/28, & S/37 DO NOT |
| | REFLECT THE FLOOR PLAN. RISERS S/13, |
| | S/25, & S/40 SHOW ALL PIPING. SECTION |
| | 104.2.1. - SUBMIT CALCULATIONS FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS FOR |
| | THE 4TH FLOOR ELEVATION. SHOW SF OF EACH |
| | AREA AND SHOW 1/2 AREA OF ALL VERTICAL |
| | WALLS INCLUDING PARAPETS ADDED TO |
| | CALCULATIONS AS WELL AS AREA OF ANY ROOF |
| | THAT DRAINS ONTO THE AREAS FROM ABOVE. |
| | SECTIONS 1106 & 1107 AND ALL |
| | SUBSECTIONS. SHOW THE LOCATION OF ALL |
| | PRIMARY AND SECONDARY DRAINS. |
| | 11) SUBMIT THE FOLLOWING: RISER DIAGRAMS |
| | FOR THE TOWNHOUSE UNITS. UNITS ON THE |
| | 1ST, 2ND, AND THIRD FLOORS. THE |
| | FOLLOWING RISER DIAGRAMS WERE NOT |
| | LOCATED: S/3, S/27, ALL W/M RISERS. |
| | SECTIONS 104.2.1, & 104.3.1.1. |
| | 12) SHTS P2.06.1 & P2,06.2 SHOW RISER |
| | S/25 NUMBER DESIGNATION. - SHOW PIPING |
| | FOR RISER S/25, S/13, S/37, & S/40 - |
| | RISERS S/4, S/5, S/13. S/26, S/28, & |
| | S/37 DO NOT REFLECT THE RISER DIAGRAM. |
| | SECTION 104.2.1. |
| | 13) SHTS P2.07.1 & PS.07.2 RISERS DO NOT |
| | REFLECT THE RISER DIAGRAMS: S/4, S/13, |
| | S/28, & S/37. FOLLOWING RISERS SHALL |
| | SHOW DWV PIPING ON THE FLOOR PLAN: S/4, |
| | S/13, S/15, S/16, S/17, S/19, S/20, |
| | S/21, S/22, S/23, S/24, S/25, S/28, |
| | S/37, & S/40. RISER S/29 MISLABLED AS |
| | S/19. SECTION 104.2.1. |
| | 14) SHTS P2.08.1 & P2.08.2 RISERS S/1, |
| | S/13, S/28, & S/37 DO NOT REFLECT THE |
| | RISER DIAGRAMS. SHOW THE DWV PIPING FOR |
| | THE FOLLOWING RISERS: S/4, S/9, S/12, |
| | S/13, S/29, S/34, S/37, & S/38. - SHOW |
| | THE LOCATIONS FOR THE FOLLOWING VTR'S AS |
| | SHOWN ON RISER DIAGRAMS: S/16, S/19, |
| | S/20, S/21, S/22, S/23, S/25, & S/40. |
| | SECTION 104.2.1. |
| | 15) SHTS P2.09.1 & P2.09.2 RISERS S/11, |
| | S/38, & S/39 DO NOT REFLECT THE RISER |
| | DIAGRAMS. -RECHECK ALL RISERS FOR DWV |
| | PIPING ON THE FLOOR PLAN. - TWO #2 |
| | RISERS SHOWN. SECTION 104.2.1. |
| | 16) SHTS P2.10.1 & P2.10.2 SUBMIT |
| | CALCULATIONS FOR PRIMARY AND SECONDARY |
| | ROOF DRAINS. SHOW SQUARE FEET OF EACH |
| | AREA AND SHOW 1/2 AREA OF ALL VERTICAL |
| | WALLS AS WELL AS ALL ROOF AREA THAT |
| | DRAINS DOWN TO ROOF FROM ABOVE IN |
| | CALCULATIONS PER SECTIONS 1106 & 1107 |
| | AND ALL SUBSECTIONS. SHOW THE LOCATION |
| | OF ALL SECONDARY DRAIN AND/OR SCUPPERS. |
| | SUBMIT A DETAIL FOR SCUPPERS SHOW HEIGHT |
| | AND WIDTH TO SHOW SQ.IN. AREA OF |
| | SCUPPER. - INDICATE LOCATION OF ALL VTR. |
| | 17) SUBMIT MANUF. SPECIFICATION SHEET |
| | FOR DOMESTIC WATER BOOSTER PUMP. PUMP |
| | SHALL BE LISTED. SECTION 303.4.1. |
| | 18) SHTS P3.07.0 &P3.07.1 ROOF DRAIN, |
| | OVERFLOW DRAINS, DECK DRAINS, OVERFLOW |
| | DECK DRAINS, PARKING DRAINS ECT WILL BE |
| | REVIEWED AFTER THE CALCULATIONS FOR THE |
| | DRAINS HAS BEEN CHECKED. ONE SET OF ROOF |
| | DRAINS/OVERFLOW DRAINS (5900 SF) HAS |
| | BEEN CROSSED BETWEEN THE OVERFLOW AND |
| | DRAIN. ONE SET OF RWL/OVERFLOW RWL ARE |
| | SO CLOSE THE SYSTEMS CAN NOT BE CHECKED |
| | FOR COMPLIANCE. PLANS SHALL HAVE |
| | SUFFICIENT CLARITY TO REVIEW. - SUMP |
| | PUMP FOR PARKING AREA DRAINS SHALL BE |
| | LISTED. SUBMIT MANUF. SPECIFICATIONS |
| | SHEETS. SECTIONS 303.4.1, & 104.2.1. |
| | 19) SHTS A2.03, A2.09, & A4.91 THRU |
| | A4.95 SUBMIT CALCULATIONS FOR PRIMARY |
| | AND SECONDARY ROOF DRAINS. SHOW SQUARE |
| | FEET OF EACH AREA, AND SHOW 1/2 AREA OF |
| | ALL VERTICAL WALLS INCLUDING PARAPETS, |
| | AS WELL AS AREAS OF ROOFS THAT DRAIN |
| | ONTO THE ROOF AREAS FROM ABOVE ADDED IN |
| | CALCULATIONS. SECTIONS 1106, AND 1107 |
| | AND ALL SUBSECTIONS. |
| | 20) SHT A1.06 SUBMIT A DETAIL SHOWING |
| | COMPLIANCE WITH FHA REQUIREMENTS 3 THRU |
| | 7, PAGE 7.33 FOR TOWNHOUSE UNITS. POWDER |
| | ROOM SHALL BE COMPLIANT. |
| | 21) SHT A1.06 PROVIDE A TYPICAL 2/3 BD |
| | UNIT. SECTION 104.2.1. |
| | 22) SHT A1.06 DETAIL 06/A-1.06 INDICATE |
| | IF THIS IS SPECIFICATION "A" OR "B" |
| | 23) SHT A1.06 ALL UNITS, MINIMUM |
| | OPENINGS FOR THE W/C IS 33". THE W/C |
| | SHALL BE 18" OFF THE WALL FROM |
| | CENTERLINE OF FIXTURE IF WALL IS |
| | AVAILABLE. PROVIDE INFORMATION ON |
| | TYPICAL UNITS SHEET. |
| | 24) SHOW BACKING FOR UNITS PER |
| | SPECIFICATION 6 OF THE FHA DESIGN MANUAL |
| | 25) SHTS A4.32 & A4.35 SECONDARY ROOF |
| | DRAINS, (OVERFLOW DRAINS) SHALL BE |
| | LOCATED 2" ABOVE THE PRIMARY ROOF DRAINS |
| | PER SECTION 1503.4.2. PLEASE INDICATE |
| | HOW THIS WILL BE ACCOMPLISHED. IN SOME |
| | AREAS THE OVERFLOW DRAIN IS IN CLOSE |
| | PROXIMITY TO THE PRIMARY ROOF DRAIN. |
| | SECTION 1503.4.2. |
| | 26) SHTS A4.91 THRU A4.95 SHOW THE |
| | LOCATION OF ALL PRIMARY AND SECONDARY |
| | ROOF DRAINS. SECTION 104.2.1. |
| | 27) SHT A7.05 INDICATE HEIGHT AND WIDTH |
| | OF SCUPPERS AT DETAIL 1/A7.05. SECTION |
| | 104.2.1. |
| | 28) SHT A9.08 PUBLIC TOILET ROOMS, NON |
| | ABSORBENT WALLS UP TO A HEIGHT OF 4 FT. |
| | REQUIRED PER SECTION 1204.2 |
| | 29) INFORMATIONAL: SEPARATE PERMIT |
| | REQUIRED FOR POOL AND IRRIGATION. |
| | SECTION 104.1.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |