Plan Review Notes
Plan Review Notes For Permit 05031504
Permit Number 05031504
Review Stop P
Sequence Number 1
Notes
Date Text
2005-05-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY WPB CODE
  
 1) PLUMBING PLANS ARE INCOMPLETE THIS
 SUBMITTAL AND MORE COMMENTS MAY BE
 FORTHCOMING ON THE NEXT REVIEW. SUBMIT
 THE FOLLOWING:
 A. EMERGENCY WATER HEATER PAN BUILDING
 ISOMETRIC AND RISER DIAGRAMS. SHOW
 MATERIAL TO BE USED. SHOW PIPE SIZE.
 SHOW TERMINATION POINT.
 B. P/T DISCHARGE VALVE RISERS AND BLDG
 DRAIN ISOMETRIC. SHOW MATERIAL TO BE
 USED. SHOW PIPE SIZE. SHOW TERMINATION
 POINT.
 C. CONDENSATE BUILDING DRAIN ISOMETRIC
 AND RISER DIAGRAMS. SHOW MATERIAL TO BE
 USED. SHOW PIPE SIZE. SHOW TERMINATION
 POINT AND VENT TERMINATION.
 (SECTIONS 104.2.1, 504.7.1, 504.7.2,
 504.8.1, 504.8.2, CITY CODE 90-125(5).
 2) SHT P3.02 WATER RISER DIAGRAMS. SHOWN
 ARE 6 FLOOR PLANS FOR THE WATER PIPING.
 IS THIS ALL THE FLOOR PLAN TYPES FOR THE
 WATER PIPING?
 A. WATER HAMMER ARRESTORS ARE REQUIRED
 AT THE DISH WASHER AND THE REFRIGERATOR.
 SECTION 604.9. THIS IS NOT SHOWN ON
 RISERS THAT DO NOT SHOW A SEPARATE LINE
 TO THE REF. NOR TO THE DISH WASHERS.
 B. HOSE BIBBS REQUIRE A SHUT OFF VALVE
 PER SECTION 606.2.(2).
 3) SHTS P3.03, P3.04, & P3.05.
 A. ALL RISERS ON ALL SHEETS. EVERY
 SANITARY DRAINAGE SYSTEM RECEIVING THE
 DISCHARGE OF A WATER CLOSET SHALL HAVE A
 MAIN VENT THAT IS EITHER A VENT STACK OR
 STACK VENT. SUCH VENT SHALL RUN
 UNDIMINISHED IN SIZE AND DIRECTLY AS
 POSSIBLE FROM THE BUILDING DRAIN THROUGH
 TO THE OPEN AIR ABOVE. SECTION 903.1.
 B. EVERY VENT STACK SHALL CONNECT TO THE
 BASE OF THE DRAINAGE STACK. THE VENT
 SHALL CONNECT AT OR BELOW THE LOWEST
 HORIZONTAL BRANCH. SECTION 903.4. -
 C. ALL RISERS SHALL SHOW ALL PIPE SIZES.
 TABLE 710.1(1).
 D. ALL RISERS WITH AIR ADMITTENCE VALVES
 SHALL HAVE A RELIEF VENT WHEN INSTALLED
 OVER 4 BRANCH INTERVALS BELOW THE TOP OF
 THE STACK. SECTION 917.3.2.
 E. RISER S/4-S/28 DOES NOT REFLECT THE
 FLOOR PLAN AT THE 4TH, 5TH, & 6TH
 FLOORS. SECTION 104.2.1.
 F. RISER S/15-S/18 DOES NOT REFLECT THE
 FLOOR PLAN AT THE 7TH FLOOR. SECTION
 104.2.1.
 G. RISERS S/13-S/37, & S/12-S/38 DO NOT
 REFLECT THE FLOOR PLAN. NO 9TH FLOOR
 SHOWN. PLEASE CLARIFY. SECTION 104.2.1.
 H. RISER S/10-S/35 DOES NOT REFLECT THE
 FLOOR PLAN ALL FLOORS, AND THE SHOWER IS
 NOT VENTED. SECTIONS 104.2.1. & 901.2.1.
 I. RISER S/9-S/34 DOES NOT REFLECT THE
 FLOOR PLAN AT THE 8TH FLOOR.
 - TUB ON ISOMETRIC NOT DRAWN CORRECTLY.
 (AS DRAWN IT INDICATES A DOWNWARD DROP
 OFF BRANCH LINE) SECTION 104.2.1.
 J. RISER S/25-2/40 SHOWER ON ISOMETRIC
 NOT DRAWN CORRECTLY. (SEE PREVIOUS
 COMMENT).
 K. RISER S/20-S/23 DOES NOT REFLECT THE
 FLOOR PLAN AT 7TH FLOOR. NO FIXTURES
 SHOWN ON THE FLOOR PLAN. - S/22 KITCHEN
 SINK PIPED OPPOSITE FROM OTHER RISERS.
 INDICATE ON RISER. SECTION 104.2.1.
 4) MORE INFORMATION REQUIRED. ARE THERE
 TOWNHOUSE UNITS ON SHT P2.001? PIPING
 SEEMS TO INDICATE THAT THERE ARE, BUT NO
 FLOOR PLAN SHOWN FOR THESE UNITS. IF NOT
 IS THE PIPING IN THE CEILING FOR THE
 NEXT FLOOR? SHEETS P2.01.1 & P2.01.2
 STATE "PARTIAL 1ST LEVEL PARKING, 1ST
 LEVEL TOWNHOUSE FLOOR PLAN. IS THE LOWER
 PARKING FLOOR PLAN AT GRADE LEVEL? IF SO
 IS THE 1ST LEVEL TOWNHOUSE ON THE 2ND
 FLOOR? PLEASE CLARIFY. - PIPING STILL
 INDICATES KITCHEN SINKS ARE ON THE
 GROUND FLOOR. PLEASE CLARIFY.
 5) SHTS P2.00.1 & P2.00.2 SHOW ALL PIPE
 SIZES, INDICATE RISER NUMBER ON ALL
 RISERS, SHOW FIXTURE UNITS AS THEY
 ACCUMULATE IN THE SYSTEM, SHOW SQUARE
 FOOTAGE AS IT ACCUMULATES IN THE SYSTEM.
 CONDENSATE DRAINING FROM THE EAST OF
 COL. LINE E1 IS NOT CONNECTED TO DRAIN.
 SECTION 104.2.1 AND TABLES 710.1(1),
 1106.2 & 1106.3.
 6) SHTS P2.01.1 & P2.01.2 SHOW ALL PIPE
 SIZES, RISER DESIGNATION NUMBERS. SANT.
 PIPING SHOWN ON FLOOR PLAN OF TOWNHOUSES
 DOES NOT SEEM TO CONNECT TO ANY
 FIXTURES. PLEASE CLARIFY. P&T VALVE
 DISCHARGE LINES MAY DRAIN INTO AN
 INDIRECT WASTE RECEPTOR. FLOOR DRAINS
 ARE NOT AN APPROVED I.W. RECEPTOR.
 EITHER A FLOOR SINK OR A HUB DRAIN IS
 REQUIRED. SECTIONS 104.2.1, 802.3 &
 802.3.2.
 7) SHTS P2.02.1 & P2.02.2 SHOW THE
 LOCATION OF ALL RISERS FOR ALL SYSTEMS.
 SECTION 104.2.1.
 8) SHTS P2.03.1 & P2.03.2 SHOW THE COL.
 LINES SO RISERS CAN BE TRACED FROM ONE
 FLOOR TO THE NEXT. SHOW ALL RISERS AND
 INDICATE LOCATION AND RISER NUMBER. SHOW
 ALL PIPE SIZES. MOST OF THESE FIXTURES
 ARE NOT SHOWN ON THE RISER DIAGRAMS.
 PLEASE CLARIFY. SECTION 104.2.1.
 9) SHTS P2.04.1 & P2.04.2THESE
 FIXTURES ARE NOT SHOWN ON THE RISER
 DIAGRAMS OR THE SANT. BUILDING DRAIN
 ISOMETRICS. SHTS P3.060 & P3.061. SUBMIT
 RISER DIAGRAMS SHOWING THESE FIXTURES.
 SHOW ALL PIPE SIZES. SECTIONS 104.2.1,
 AND 104.3.1.1.
 10) SHTS P2.05.1 & P2.05.2 RISERS 2/4,
 S/5, S/13, S/26, S/28, & S/37 DO NOT
 REFLECT THE FLOOR PLAN. RISERS S/13,
 S/25, & S/40 SHOW ALL PIPING. SECTION
 104.2.1. - SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS FOR
 THE 4TH FLOOR ELEVATION. SHOW SF OF EACH
 AREA AND SHOW 1/2 AREA OF ALL VERTICAL
 WALLS INCLUDING PARAPETS ADDED TO
 CALCULATIONS AS WELL AS AREA OF ANY ROOF
 THAT DRAINS ONTO THE AREAS FROM ABOVE.
 SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS. SHOW THE LOCATION OF ALL
 PRIMARY AND SECONDARY DRAINS.
 11) SUBMIT THE FOLLOWING: RISER DIAGRAMS
 FOR THE TOWNHOUSE UNITS. UNITS ON THE
 1ST, 2ND, AND THIRD FLOORS. THE
 FOLLOWING RISER DIAGRAMS WERE NOT
 LOCATED: S/3, S/27, ALL W/M RISERS.
 SECTIONS 104.2.1, & 104.3.1.1.
 12) SHTS P2.06.1 & P2,06.2 SHOW RISER
 S/25 NUMBER DESIGNATION. - SHOW PIPING
 FOR RISER S/25, S/13, S/37, & S/40 -
 RISERS S/4, S/5, S/13. S/26, S/28, &
 S/37 DO NOT REFLECT THE RISER DIAGRAM.
 SECTION 104.2.1.
 13) SHTS P2.07.1 & PS.07.2 RISERS DO NOT
 REFLECT THE RISER DIAGRAMS: S/4, S/13,
 S/28, & S/37. FOLLOWING RISERS SHALL
 SHOW DWV PIPING ON THE FLOOR PLAN: S/4,
 S/13, S/15, S/16, S/17, S/19, S/20,
 S/21, S/22, S/23, S/24, S/25, S/28,
 S/37, & S/40. RISER S/29 MISLABLED AS
 S/19. SECTION 104.2.1.
 14) SHTS P2.08.1 & P2.08.2 RISERS S/1,
 S/13, S/28, & S/37 DO NOT REFLECT THE
 RISER DIAGRAMS. SHOW THE DWV PIPING FOR
 THE FOLLOWING RISERS: S/4, S/9, S/12,
 S/13, S/29, S/34, S/37, & S/38. - SHOW
 THE LOCATIONS FOR THE FOLLOWING VTR'S AS
 SHOWN ON RISER DIAGRAMS: S/16, S/19,
 S/20, S/21, S/22, S/23, S/25, & S/40.
 SECTION 104.2.1.
 15) SHTS P2.09.1 & P2.09.2 RISERS S/11,
 S/38, & S/39 DO NOT REFLECT THE RISER
 DIAGRAMS. -RECHECK ALL RISERS FOR DWV
 PIPING ON THE FLOOR PLAN. - TWO #2
 RISERS SHOWN. SECTION 104.2.1.
 16) SHTS P2.10.1 & P2.10.2 SUBMIT
 CALCULATIONS FOR PRIMARY AND SECONDARY
 ROOF DRAINS. SHOW SQUARE FEET OF EACH
 AREA AND SHOW 1/2 AREA OF ALL VERTICAL
 WALLS AS WELL AS ALL ROOF AREA THAT
 DRAINS DOWN TO ROOF FROM ABOVE IN
 CALCULATIONS PER SECTIONS 1106 & 1107
 AND ALL SUBSECTIONS. SHOW THE LOCATION
 OF ALL SECONDARY DRAIN AND/OR SCUPPERS.
 SUBMIT A DETAIL FOR SCUPPERS SHOW HEIGHT
 AND WIDTH TO SHOW SQ.IN. AREA OF
 SCUPPER. - INDICATE LOCATION OF ALL VTR.
 17) SUBMIT MANUF. SPECIFICATION SHEET
 FOR DOMESTIC WATER BOOSTER PUMP. PUMP
 SHALL BE LISTED. SECTION 303.4.1.
 18) SHTS P3.07.0 &P3.07.1 ROOF DRAIN,
 OVERFLOW DRAINS, DECK DRAINS, OVERFLOW
 DECK DRAINS, PARKING DRAINS ECT WILL BE
 REVIEWED AFTER THE CALCULATIONS FOR THE
 DRAINS HAS BEEN CHECKED. ONE SET OF ROOF
 DRAINS/OVERFLOW DRAINS (5900 SF) HAS
 BEEN CROSSED BETWEEN THE OVERFLOW AND
 DRAIN. ONE SET OF RWL/OVERFLOW RWL ARE
 SO CLOSE THE SYSTEMS CAN NOT BE CHECKED
 FOR COMPLIANCE. PLANS SHALL HAVE
 SUFFICIENT CLARITY TO REVIEW. - SUMP
 PUMP FOR PARKING AREA DRAINS SHALL BE
 LISTED. SUBMIT MANUF. SPECIFICATIONS
 SHEETS. SECTIONS 303.4.1, & 104.2.1.
 19) SHTS A2.03, A2.09, & A4.91 THRU
 A4.95 SUBMIT CALCULATIONS FOR PRIMARY
 AND SECONDARY ROOF DRAINS. SHOW SQUARE
 FEET OF EACH AREA, AND SHOW 1/2 AREA OF
 ALL VERTICAL WALLS INCLUDING PARAPETS,
 AS WELL AS AREAS OF ROOFS THAT DRAIN
 ONTO THE ROOF AREAS FROM ABOVE ADDED IN
 CALCULATIONS. SECTIONS 1106, AND 1107
 AND ALL SUBSECTIONS.
 20) SHT A1.06 SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH FHA REQUIREMENTS 3 THRU
 7, PAGE 7.33 FOR TOWNHOUSE UNITS. POWDER
 ROOM SHALL BE COMPLIANT.
 21) SHT A1.06 PROVIDE A TYPICAL 2/3 BD
 UNIT. SECTION 104.2.1.
 22) SHT A1.06 DETAIL 06/A-1.06 INDICATE
 IF THIS IS SPECIFICATION "A" OR "B"
 23) SHT A1.06 ALL UNITS, MINIMUM
 OPENINGS FOR THE W/C IS 33". THE W/C
 SHALL BE 18" OFF THE WALL FROM
 CENTERLINE OF FIXTURE IF WALL IS
 AVAILABLE. PROVIDE INFORMATION ON
 TYPICAL UNITS SHEET.
 24) SHOW BACKING FOR UNITS PER
 SPECIFICATION 6 OF THE FHA DESIGN MANUAL
 25) SHTS A4.32 & A4.35 SECONDARY ROOF
 DRAINS, (OVERFLOW DRAINS) SHALL BE
 LOCATED 2" ABOVE THE PRIMARY ROOF DRAINS
 PER SECTION 1503.4.2. PLEASE INDICATE
 HOW THIS WILL BE ACCOMPLISHED. IN SOME
 AREAS THE OVERFLOW DRAIN IS IN CLOSE
 PROXIMITY TO THE PRIMARY ROOF DRAIN.
 SECTION 1503.4.2.
 26) SHTS A4.91 THRU A4.95 SHOW THE
 LOCATION OF ALL PRIMARY AND SECONDARY
 ROOF DRAINS. SECTION 104.2.1.
 27) SHT A7.05 INDICATE HEIGHT AND WIDTH
 OF SCUPPERS AT DETAIL 1/A7.05. SECTION
 104.2.1.
 28) SHT A9.08 PUBLIC TOILET ROOMS, NON
 ABSORBENT WALLS UP TO A HEIGHT OF 4 FT.
 REQUIRED PER SECTION 1204.2
 29) INFORMATIONAL: SEPARATE PERMIT
 REQUIRED FOR POOL AND IRRIGATION.
 SECTION 104.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS