| 2005-06-09 00:00:00 | DENIED: |
| | 1.PLAN SHEET AC0.01 HEAT PUMP SCHEDULE |
| | HP-5, PER 2001 FBC(M)606.2.1 DUCT SMOKE |
| | DETECTORS ARE REQUIRED IN UNITS THAT |
| | HAVE THE DESIGN CAPACITY GREATER THAN |
| | 2,000 CFM. |
| | |
| | 2.PLAN SHEET AC0.02 FAN SCHEDULE, EF-2 |
| | DRYER BOOSTER FAN SHALL BE SUBMITTED |
| | UNDER ALTERNATE MATRERIALS & MEDTHODS TO |
| | THE BUILDING OFFICIAL, NEIL MELICK. |
| | PLEASE PROVIDE ALL SUBMITTAL DATA AND A |
| | LETTER FROM THE DRYER MANUFACTURER |
| | (ENGINEER) INDICATING THIS APPLICATION |
| | IS PERMITTED AND WILL NOT VOID THE |
| | WARRANTY. |
| | |
| | 3.PLAN SHEET AC0.04 GARAGE EXHAUST IS |
| | DESIGNED TO FUNCTION WITH THE CO |
| | SENSORS.PLEASE CLARIFY THE FOLLOWING: |
| | A) WILL THIS BE A PRIVATE OR PUBLIC |
| | GARAGE? |
| | B) PROVIDE CALCULATIONS IN ACCORDANE |
| | WITH 2001 FBC 411.5. |
| | |
| | 4.PLAN SHEET AC0.07 AHU DETAIL DOES |
| | NOT INDICATE AUXILIARY DRAIN PAN WITH |
| | OVERFLOW PROTECTION AS REQUIRED PER 2001 |
| | FBC(M)307.2.3. |
| | |
| | 5.PLAN SHEET AC2.01.1, EF-3 AND THE |
| | AIR MAKE-UP ARE INTO & FROM THE GARAGE. |
| | PER 2001 FBC(M)501.3, EVERY MECHANICAL |
| | EXHAUST SYSTEM SHALL BE DISCHARGED |
| | OUTDOORS. REFERENCE ALSO TABLE 403.3, |
| | EXHAUST AIR SHALL NOT BE RECIRCULATED. |
| | THIS APPLICATION IS DONE THROUHOUT THE |
| | GARAGE AREA. |
| | |
| | 6.PLAN SHEET AC2.01.2, SEF-8 & OUTSIDE |
| | AIR ARE WITHIN 10 FT OF EACH OTHER. |
| | EXHAUST SHALL NOT BE RECIRCULATED INTO |
| | FRESH AIR, NOXIOUS & TOXIC EXHAUST SHALL |
| | BE A MINIMUM OF 10 FT FROM FRESH AIR |
| | INTAKES PER 2001 FBC(M)401.5.1 |
| | |
| | 7.PLEASE NOTE, EXHAUST & INTAKE |
| | OPENINGS SHALL BE A MINIMUM OF 10 FT |
| | FROM LOT LINES OR BUILDINGS ON THE SAME |
| | LOT - 2001 FBC(M)401.5.PLANS DO NOT |
| | INDICATE REQUIRED DISTANCES. |
| | |
| | 8.PLAN SHEET AC2.01.2, PLEASE NOTE THE |
| | LOCATION OF CU-EV2 ON A STAND THAT |
| | APPREARS TO BE IN THE PATH OF TRAVEL TO |
| | A TOWN HOUSE.ALSO PROVIDE SUBMTITAL |
| | DATA FOR THE CU-EV2, DOES MANUFACTURER |
| | ALLOW THE OUTDOOR CU TO BE LOCATED IN AN |
| | ENCLOSED GARAGE? |
| | |
| | 9.PLAN SHEET AC2.08.2, PLEASE PROVIDE |
| | OUTSIDE AIR AND VENTILATION REQUIREMENTS |
| | FOR THE MECHANICAL ROOM. |
| | |
| | 10. PLEASE PROVIDE OUTSIDE AIR |
| | CALCULATIONS FOR ALL AREAS RESIDENTIAL |
| | AND COMMON, FITNESS ROOMS LOBBY AREAS, |
| | ETC. IN ACCORDANCE WITH 2001 FBC(M)TABLE |
| | 403.3. |
| | |
| | 11. PLEASE PROVIDE RISER FOR THE SMOKE |
| | EVAC AND OUTSIDE AIR DUCTS. |
| | |
| | 12. PROVIDE INFORMATION ON THE |
| | GENERATOR.INDICATE FUEL SOURCE. |
| | |
| | PLEASE NOTE, RESONSE TO COMMENTS MAY |
| | GENERATE NEW COMMENTS.PLEASE PROVIDE |
| | WRITTEN RESPONSE TO COMMENTS TO HELP |
| | EXPIDITE RESUBMITTAL. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |