Plan Review Notes
Plan Review Notes For Permit 05031504
Permit Number 05031504
Review Stop M
Sequence Number 1
Notes
Date Text
2005-06-09 00:00:00DENIED:
 1.PLAN SHEET AC0.01 HEAT PUMP SCHEDULE
 HP-5, PER 2001 FBC(M)606.2.1 DUCT SMOKE
 DETECTORS ARE REQUIRED IN UNITS THAT
 HAVE THE DESIGN CAPACITY GREATER THAN
 2,000 CFM.
  
 2.PLAN SHEET AC0.02 FAN SCHEDULE, EF-2
 DRYER BOOSTER FAN SHALL BE SUBMITTED
 UNDER ALTERNATE MATRERIALS & MEDTHODS TO
 THE BUILDING OFFICIAL, NEIL MELICK.
 PLEASE PROVIDE ALL SUBMITTAL DATA AND A
 LETTER FROM THE DRYER MANUFACTURER
 (ENGINEER) INDICATING THIS APPLICATION
 IS PERMITTED AND WILL NOT VOID THE
 WARRANTY.
  
 3.PLAN SHEET AC0.04 GARAGE EXHAUST IS
 DESIGNED TO FUNCTION WITH THE CO
 SENSORS.PLEASE CLARIFY THE FOLLOWING:
 A) WILL THIS BE A PRIVATE OR PUBLIC
 GARAGE?
 B) PROVIDE CALCULATIONS IN ACCORDANE
 WITH 2001 FBC 411.5.
  
 4.PLAN SHEET AC0.07 AHU DETAIL DOES
 NOT INDICATE AUXILIARY DRAIN PAN WITH
 OVERFLOW PROTECTION AS REQUIRED PER 2001
 FBC(M)307.2.3.
  
 5.PLAN SHEET AC2.01.1, EF-3 AND THE
 AIR MAKE-UP ARE INTO & FROM THE GARAGE.
 PER 2001 FBC(M)501.3, EVERY MECHANICAL
 EXHAUST SYSTEM SHALL BE DISCHARGED
 OUTDOORS. REFERENCE ALSO TABLE 403.3,
 EXHAUST AIR SHALL NOT BE RECIRCULATED.
 THIS APPLICATION IS DONE THROUHOUT THE
 GARAGE AREA.
  
 6.PLAN SHEET AC2.01.2, SEF-8 & OUTSIDE
 AIR ARE WITHIN 10 FT OF EACH OTHER.
 EXHAUST SHALL NOT BE RECIRCULATED INTO
 FRESH AIR, NOXIOUS & TOXIC EXHAUST SHALL
 BE A MINIMUM OF 10 FT FROM FRESH AIR
 INTAKES PER 2001 FBC(M)401.5.1
  
 7.PLEASE NOTE, EXHAUST & INTAKE
 OPENINGS SHALL BE A MINIMUM OF 10 FT
 FROM LOT LINES OR BUILDINGS ON THE SAME
 LOT - 2001 FBC(M)401.5.PLANS DO NOT
 INDICATE REQUIRED DISTANCES.
  
 8.PLAN SHEET AC2.01.2, PLEASE NOTE THE
 LOCATION OF CU-EV2 ON A STAND THAT
 APPREARS TO BE IN THE PATH OF TRAVEL TO
 A TOWN HOUSE.ALSO PROVIDE SUBMTITAL
 DATA FOR THE CU-EV2, DOES MANUFACTURER
 ALLOW THE OUTDOOR CU TO BE LOCATED IN AN
 ENCLOSED GARAGE?
  
 9.PLAN SHEET AC2.08.2, PLEASE PROVIDE
 OUTSIDE AIR AND VENTILATION REQUIREMENTS
 FOR THE MECHANICAL ROOM.
  
 10. PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS FOR ALL AREAS RESIDENTIAL
 AND COMMON, FITNESS ROOMS LOBBY AREAS,
 ETC. IN ACCORDANCE WITH 2001 FBC(M)TABLE
 403.3.
  
 11. PLEASE PROVIDE RISER FOR THE SMOKE
 EVAC AND OUTSIDE AIR DUCTS.
  
 12. PROVIDE INFORMATION ON THE
 GENERATOR.INDICATE FUEL SOURCE.
  
 PLEASE NOTE, RESONSE TO COMMENTS MAY
 GENERATE NEW COMMENTS.PLEASE PROVIDE
 WRITTEN RESPONSE TO COMMENTS TO HELP
 EXPIDITE RESUBMITTAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.