Plan Review Notes
Plan Review Notes For Permit 05031504
Permit Number 05031504
Review Stop E
Sequence Number 1
Notes
Date Text
2005-05-03 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SEE THAT THE ADDRESS ON THE
 APPLICATION IS NOT THE ADDRESS OF RECORD
 FOR THE PCN ON CITY RECORDS.
  
 2} PLEASE SEE NO REFERENCE WAS MADE
 REGARDING THE FAIR HOUSING ACT. NOTE
 COMPLIANCE WITH SAME.
  
 3} THE PANEL SCHEDULE SHOWS "MSBHE" AS
 HAVING A 1000 AMP MAIN BREAKER. THE
 RISER DIAGRAM SHOWS A 1000 AMP MAIN
 AHEAD OF THE ATS. ARE THESE THREE PIECES
 OF EQUIPMENT AN INTEGRAL PART OF THE
 MAIN GEAR, OR ALL SEPARATE PIECES OF
 EQUIPMENT? PLEASE PROVIDE SPECS ON THE
 GEAR.
  
 4} IF "MSBHE" IS FED THROUGH THE ATS
 FROM THE 1000 AMP EMERGENCY MAIN, AND
 DOES NOT HAVE A GFI PROTECTED MAIN
 BREAKER INTERNALLY, THE BREAKER ON THE
 GENERATOR WOULD BE REQUIRED TO BE GFI
 PER 240.13 NEC.
  
 5} IF THE EMERGENCY MAIN SHOWN ON THE
 RISER IS A SEPERATE PIECE OF EQUIPMENT
 AS MENTIONED, GIVE AIC RATING.
  
 6} INDICATE THE AIC RATING OF THE
 DWELLING UNIT MAINS AN METER CENTER
 EQUIPMENT PER 110.9.
  
 7} INDICATE THE CONDUIT AND CONDUCTOR
 SIZE AND TYPE FROM THE GENERATOR TO THE
 ATS.
  
 8} THE DOMESTIC BOOSTER PUMP CONTROLLER
 ON THE RISER IS SHOWN FED FROM "WL1E",
 BUT LISTED ON "EH1E" SCEDULE, CIRCUITS
 14,16&18. PLEASE CORRELATE.
  
 9} THE JOCKEY PUMP IS ALSO SHOWN AS FED
 FROM "WL1E", BUT APPEARS ON "EH1E"
 SCHEDULE, PLEASE CORRELATE.
  
 10} PLEASE REMOVE REFERENCES TO THE 1999
 NEC FROM NOTES (SEE APARTMENT KEY NOTES)
 AND REFERENCE THE 2002 NEC CURRENTLY
 BEING USED.
  
 11} ELECTRICAL ROOMS MEANS OF EGRESS
 MUST COMPLY WITH 110.26(C)(2). SEE
 DOORSWING SHEET E4.00(INCORRECTLY MARKED
 AS E3.0.1 ON SHEET E2.01.3 NOTES).
  
 THE FOLLOWING COMMENTS REGARD THE PANEL
 SCHEDULES BEGINNING ON SHEET E6.01.
  
 1} PANEL "WL1" CIRCUITS 31,35 EWH-2 OCP
 DOES NOT CORRELATE WITH E0.01 EQ
 SCHEDULE.
  
 2} "WH8E" SHEET E6.02,CIRCUITS 14,16,18
 OCP DOES NOT CORRELATE WITH EQUIPMENT
 SCHEDULE.
  
 3} ALL DWELLING UNIT EWH CIRCUITS IN ALL
 DWELLING PANELS ARE IN VOILATION OF
 422.11(E). THE OCP IS TOO LARGE FOR THE
 INDICATED LOADS.
  
 4} THE HEAT PUMP CIRCUITS IN ALL
 DWELLING PANELS WITH THE EXCEPTION OF
 "A4", DO NOT CORRELATE WITH THE
 EQUIPMENT SCHEDULE MAX OCP.
  
 THE FOLLOWING COMMENTS REGARD THE FLOOR
 PLANS BEGINNING ON SHEET E3.01.
  
 1} THE RECEPTACLES SHOWN OUTSIDE THE
 UNIT(S)ON CIRCUIT "T1-6" ARE ON THE
 SMALL APPLIANCE CIRCUIT IN VIOLATION OF
 210.52(B)(2).
  
 2} ALL UNITS RECEPTACLE PLACEMENT
 (CIRCUIT #8) FOR THE MICROWAVE, THOUGH
 PLACED WITHIN 2' OF THE SINK, DO NOT
 COUNT FOR SPACING PER 210.52(C)(1) SMALL
 APPLIANCE REQUIREMENT FOR SPACING AS
 CIRCUIT #8 IS NOT A SMALL APPLIANCE
 CIRCUIT. A SMALL APPLIANCE RECEPTACLE
 MUST BE ADDED TO COMPLY, ALL UNITS.
  
 3} ALL BALCONY RECEPTACLES, ALL UNITS
 ARE ON A SMALL APPLIANCE CIRCUIT IN
 VIOLATION OF 210.52(B)(2) EXCEPT CIRCUIT
 T1-7 SHEET E3.05 WHICH IS ON THE BATH
 RECEPTACLE CIRCUIT IN VIOLATION OF
 210.11(C)(3).
  
 4} REFERENCE SHEET E3.02. DWG 2&3 E3.02.
 2 BEDROOM @ STAIR.A RECEPTACLE MUST BE
 ADDED TO THE PENINSULAR TO COMPLY WITH
 210.52(C)(4).
  
 5} 4 E3.02 2 BEDROOM 8TH FLOOR PLAN.
 210.52(C)(4) AND BEDROOM NEEDS
 RECEPTACLE PER 210.52(A)(2).
  
 6} SHEET E3.03 CUT1,3 BEDROOM UNIT RCP
 PLAN. ADD RECEPTACLE IN THE MASTER
 BEDROOM PER 210.52(A)(1).
 2/3 BEDROOM UNIT W/SKYLOFT RCP PLAN. ADD
 A SMOKE DETECTOR @ STAIRWELL PER 905.2.2
 FBC.
  
 7} TOWNHOUSE UNIT 4 NEEDS A RECEPTACLE
 BETWEEN THE STOVE AND FRIDGE,
 210.11(C)(1) COUNTERTOP SPACING,4 E3.04.
 ALSO NOTE THAT AN ISLAND RECEPTACLES
 MUST BE ADDED IF THERE IS COUNTERTOP
 SEPARATION (SINK), SEE 210.52(C)(4) AND
 EXCEPTION. CALL ME WITH QUESTIONS.
  
 8} A RECEPTACLE MUST BE ADDED FOR
 SPACING REQUIREMENTS 210.52(A), MASTER
 BEDROOM, 2' REQ.
  
 9} REFERENCE SHEET E3.04. SEC.3. TWO
 BEDROOM@ LOBBY. MASTER BEDROOM
 RECEPTACLES, ADD 1 AND ADD OR RELOCATE
 ONE, SEE REVIEWED PLAN.210.52(A).
  
 10} CIRCUIT #T1-28 E3.05, SEC'S 1&2, IS
 INDICATED AS A CIRCUIT # ON TWO
 RECEPTACLES. THIS IS LISTED AS A
 LIGHTING CIRCUIT ON THE SCHEDULE. PLEASE
 CORRELATE.
  
 11} AGAIN REGARDING THE ISLAND IN THESE
 TWO UNITS, SEE 210.52(A)(4) REGARDING
 RECEPTACLE SPACING, ONE MUST BE ADDED.
 ALSO SEE EXCEPTION 210.52(C)(5)(B) FOR
 OVERHANG.
  
 12} SHEET E3.06 SEC.2, 2ND LEVEL FLOOR
 PLAN, ADD A RECEPTACLE IN BEDROOM #2,
 210.52(A)(2), SEE PLAN. ISLAND
 RECEPTACLE COMMENTS APPLY AS WELL.
 CIRCUIT T-28 HAS RECEPTALES IN LIVING
 ROOM(S).
  
 13} SHEET E3.07 CENTER FLOOR PLAN MASTER
 BEDROOM NEEDS A RECEPTACLE TO COMPLY
 210.52(A)(2).
  
 14} SEE FIRE REVIEW FOR COMMENTS ON
 EMERGENCY EGRESS LIGHTING IN CORREDORS
 AND COMMON AREAS. SEE A.7.9.2.2 NFPA
 101.
  
 15} PLEASE SEE REQUIREMENTS FOR CURBS @
 FLOOR PENETRATIONS RE: BUSWAYS. ARTICLE
 368.6 NEC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  