| 2005-05-03 00:00:00 | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PLEASE SEE THAT THE ADDRESS ON THE |
| | APPLICATION IS NOT THE ADDRESS OF RECORD |
| | FOR THE PCN ON CITY RECORDS. |
| | |
| | 2} PLEASE SEE NO REFERENCE WAS MADE |
| | REGARDING THE FAIR HOUSING ACT. NOTE |
| | COMPLIANCE WITH SAME. |
| | |
| | 3} THE PANEL SCHEDULE SHOWS "MSBHE" AS |
| | HAVING A 1000 AMP MAIN BREAKER. THE |
| | RISER DIAGRAM SHOWS A 1000 AMP MAIN |
| | AHEAD OF THE ATS. ARE THESE THREE PIECES |
| | OF EQUIPMENT AN INTEGRAL PART OF THE |
| | MAIN GEAR, OR ALL SEPARATE PIECES OF |
| | EQUIPMENT? PLEASE PROVIDE SPECS ON THE |
| | GEAR. |
| | |
| | 4} IF "MSBHE" IS FED THROUGH THE ATS |
| | FROM THE 1000 AMP EMERGENCY MAIN, AND |
| | DOES NOT HAVE A GFI PROTECTED MAIN |
| | BREAKER INTERNALLY, THE BREAKER ON THE |
| | GENERATOR WOULD BE REQUIRED TO BE GFI |
| | PER 240.13 NEC. |
| | |
| | 5} IF THE EMERGENCY MAIN SHOWN ON THE |
| | RISER IS A SEPERATE PIECE OF EQUIPMENT |
| | AS MENTIONED, GIVE AIC RATING. |
| | |
| | 6} INDICATE THE AIC RATING OF THE |
| | DWELLING UNIT MAINS AN METER CENTER |
| | EQUIPMENT PER 110.9. |
| | |
| | 7} INDICATE THE CONDUIT AND CONDUCTOR |
| | SIZE AND TYPE FROM THE GENERATOR TO THE |
| | ATS. |
| | |
| | 8} THE DOMESTIC BOOSTER PUMP CONTROLLER |
| | ON THE RISER IS SHOWN FED FROM "WL1E", |
| | BUT LISTED ON "EH1E" SCEDULE, CIRCUITS |
| | 14,16&18. PLEASE CORRELATE. |
| | |
| | 9} THE JOCKEY PUMP IS ALSO SHOWN AS FED |
| | FROM "WL1E", BUT APPEARS ON "EH1E" |
| | SCHEDULE, PLEASE CORRELATE. |
| | |
| | 10} PLEASE REMOVE REFERENCES TO THE 1999 |
| | NEC FROM NOTES (SEE APARTMENT KEY NOTES) |
| | AND REFERENCE THE 2002 NEC CURRENTLY |
| | BEING USED. |
| | |
| | 11} ELECTRICAL ROOMS MEANS OF EGRESS |
| | MUST COMPLY WITH 110.26(C)(2). SEE |
| | DOORSWING SHEET E4.00(INCORRECTLY MARKED |
| | AS E3.0.1 ON SHEET E2.01.3 NOTES). |
| | |
| | THE FOLLOWING COMMENTS REGARD THE PANEL |
| | SCHEDULES BEGINNING ON SHEET E6.01. |
| | |
| | 1} PANEL "WL1" CIRCUITS 31,35 EWH-2 OCP |
| | DOES NOT CORRELATE WITH E0.01 EQ |
| | SCHEDULE. |
| | |
| | 2} "WH8E" SHEET E6.02,CIRCUITS 14,16,18 |
| | OCP DOES NOT CORRELATE WITH EQUIPMENT |
| | SCHEDULE. |
| | |
| | 3} ALL DWELLING UNIT EWH CIRCUITS IN ALL |
| | DWELLING PANELS ARE IN VOILATION OF |
| | 422.11(E). THE OCP IS TOO LARGE FOR THE |
| | INDICATED LOADS. |
| | |
| | 4} THE HEAT PUMP CIRCUITS IN ALL |
| | DWELLING PANELS WITH THE EXCEPTION OF |
| | "A4", DO NOT CORRELATE WITH THE |
| | EQUIPMENT SCHEDULE MAX OCP. |
| | |
| | THE FOLLOWING COMMENTS REGARD THE FLOOR |
| | PLANS BEGINNING ON SHEET E3.01. |
| | |
| | 1} THE RECEPTACLES SHOWN OUTSIDE THE |
| | UNIT(S)ON CIRCUIT "T1-6" ARE ON THE |
| | SMALL APPLIANCE CIRCUIT IN VIOLATION OF |
| | 210.52(B)(2). |
| | |
| | 2} ALL UNITS RECEPTACLE PLACEMENT |
| | (CIRCUIT #8) FOR THE MICROWAVE, THOUGH |
| | PLACED WITHIN 2' OF THE SINK, DO NOT |
| | COUNT FOR SPACING PER 210.52(C)(1) SMALL |
| | APPLIANCE REQUIREMENT FOR SPACING AS |
| | CIRCUIT #8 IS NOT A SMALL APPLIANCE |
| | CIRCUIT. A SMALL APPLIANCE RECEPTACLE |
| | MUST BE ADDED TO COMPLY, ALL UNITS. |
| | |
| | 3} ALL BALCONY RECEPTACLES, ALL UNITS |
| | ARE ON A SMALL APPLIANCE CIRCUIT IN |
| | VIOLATION OF 210.52(B)(2) EXCEPT CIRCUIT |
| | T1-7 SHEET E3.05 WHICH IS ON THE BATH |
| | RECEPTACLE CIRCUIT IN VIOLATION OF |
| | 210.11(C)(3). |
| | |
| | 4} REFERENCE SHEET E3.02. DWG 2&3 E3.02. |
| | 2 BEDROOM @ STAIR.A RECEPTACLE MUST BE |
| | ADDED TO THE PENINSULAR TO COMPLY WITH |
| | 210.52(C)(4). |
| | |
| | 5} 4 E3.02 2 BEDROOM 8TH FLOOR PLAN. |
| | 210.52(C)(4) AND BEDROOM NEEDS |
| | RECEPTACLE PER 210.52(A)(2). |
| | |
| | 6} SHEET E3.03 CUT1,3 BEDROOM UNIT RCP |
| | PLAN. ADD RECEPTACLE IN THE MASTER |
| | BEDROOM PER 210.52(A)(1). |
| | 2/3 BEDROOM UNIT W/SKYLOFT RCP PLAN. ADD |
| | A SMOKE DETECTOR @ STAIRWELL PER 905.2.2 |
| | FBC. |
| | |
| | 7} TOWNHOUSE UNIT 4 NEEDS A RECEPTACLE |
| | BETWEEN THE STOVE AND FRIDGE, |
| | 210.11(C)(1) COUNTERTOP SPACING,4 E3.04. |
| | ALSO NOTE THAT AN ISLAND RECEPTACLES |
| | MUST BE ADDED IF THERE IS COUNTERTOP |
| | SEPARATION (SINK), SEE 210.52(C)(4) AND |
| | EXCEPTION. CALL ME WITH QUESTIONS. |
| | |
| | 8} A RECEPTACLE MUST BE ADDED FOR |
| | SPACING REQUIREMENTS 210.52(A), MASTER |
| | BEDROOM, 2' REQ. |
| | |
| | 9} REFERENCE SHEET E3.04. SEC.3. TWO |
| | BEDROOM@ LOBBY. MASTER BEDROOM |
| | RECEPTACLES, ADD 1 AND ADD OR RELOCATE |
| | ONE, SEE REVIEWED PLAN.210.52(A). |
| | |
| | 10} CIRCUIT #T1-28 E3.05, SEC'S 1&2, IS |
| | INDICATED AS A CIRCUIT # ON TWO |
| | RECEPTACLES. THIS IS LISTED AS A |
| | LIGHTING CIRCUIT ON THE SCHEDULE. PLEASE |
| | CORRELATE. |
| | |
| | 11} AGAIN REGARDING THE ISLAND IN THESE |
| | TWO UNITS, SEE 210.52(A)(4) REGARDING |
| | RECEPTACLE SPACING, ONE MUST BE ADDED. |
| | ALSO SEE EXCEPTION 210.52(C)(5)(B) FOR |
| | OVERHANG. |
| | |
| | 12} SHEET E3.06 SEC.2, 2ND LEVEL FLOOR |
| | PLAN, ADD A RECEPTACLE IN BEDROOM #2, |
| | 210.52(A)(2), SEE PLAN. ISLAND |
| | RECEPTACLE COMMENTS APPLY AS WELL. |
| | CIRCUIT T-28 HAS RECEPTALES IN LIVING |
| | ROOM(S). |
| | |
| | 13} SHEET E3.07 CENTER FLOOR PLAN MASTER |
| | BEDROOM NEEDS A RECEPTACLE TO COMPLY |
| | 210.52(A)(2). |
| | |
| | 14} SEE FIRE REVIEW FOR COMMENTS ON |
| | EMERGENCY EGRESS LIGHTING IN CORREDORS |
| | AND COMMON AREAS. SEE A.7.9.2.2 NFPA |
| | 101. |
| | |
| | 15} PLEASE SEE REQUIREMENTS FOR CURBS @ |
| | FLOOR PENETRATIONS RE: BUSWAYS. ARTICLE |
| | 368.6 NEC. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |