2005-04-18 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05031504
 ADD: 2323 N FLAGLER DR
 CONT:FIRST BLDG CORP OF FLORIDA
 TEL:(954)561-4900
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 NOTE IF A COMMENT IS MADE ON A
 PARTICULAR SHEET THIS COMMENT MAY NOT
 APPEAR ON OTHER SHEET.
  
 LOOK FOR COMMENTS BY OTHER PLAN REVIEW
 DISCIPLINES THAT MAY BE WRITTEN ON THE
 APPLICATION, PLANS, OR ATTACHED
 SEPARETLY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NESSARY.
 A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND,
 WILL HELP EXPEDITE YOUR PERMIT . THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 3) THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.A 'UNITY OF TITLE' SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE.
 SUBMIT A COPY OF THE RECORDED 'UNITY OF
 OF TITLE' DOCUMENT SO THAT FBC TABLE 600
 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
  
 4) FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 SRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPEC
 TION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGEN-
 CY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESH-
 OLD BUILDING. THE PURPOSE OF THE SRUCTUR
 AL INSPECTION PLAN IS TO PROVIDE SPECIF-
 IC INSPECTION PROCEDURES AND SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 5) W.P.B. AMENDMENT 105.13.4.4 ALL PLANS
 FOR THE BUILDING WHICH ARE REQUIRED TO
 BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CON- TAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR
 ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 6) SHEET A2.01, A2.02 REFERNCES THE TERM
 "TOWNHOUSE", THE LEGAL TERM (DEFINITION)
 IS A SINGLE FAMILY DWELLING CONSTRUCTED
 IN A SERIES OF ATTACHED UNITS WITH
 PROPERTY LINES SEPERATING EACH UNIT. SEE
 DEFINITIONS.
  
 7) SHEET A2.00 DOESN'T INDICATE THE
 STRUCTURAL WALL LINE ON THE WEST END OF
 THE LOWER PARKING PLAN, 104.2.1.2*
 ADDITIONAL INFORMATION REQUIRED.
  
 8) A2.01 DOESN'T INDICATE BARRIERS IN
 THE STAIRWELLS THAT LEAD TO BELOW GRADE.
 SEE 1005.6.6 A STAIRWAY IN A SMOKEPROOF
 ENCLOSURE SHALL NOT CONTINUE BELOW THE
 GRADE LEVEL UNLESSS AN APPROVED BARRIER
 IS PROVIDED AT THE GROUND LEVEL TO
 PREVENT PERSONS FROM ACCIDENTALLY
 CONTINUING INTO THE BASEMENT.
  
 9) THE PRIMARY ENTRY DOOR OF COVERED
 DWELLING UNITS IS PART OF PUBLIC AND
 COMMON USE SPACES, THEREFORE, IT MUST BE
 ON AN ACCESSIBLE ROUTE & BE ACCESSIBLE,
 I.E., MEET THE ANSI REQUIREMENTS OF
 4.13 DOORS. ANSI 4.13.9 LEVER OR OTHER
 EASY USE DOOR HARDWARE.
 THE UNITS 110-116 HAVE STAIRS ON THE
 ENTERNAL HALLWAYS MAKING THEM
 INACCESSIBLE TO THE HANDICAPPED.
  
 10) 1012.1.2 EGRESS DOORS SHALL BE SIDE
 SWINGING TYPE. DOORS SHALL SWING IN THE
 DIRECTION OF EGRESS FOR THE FOLLOWING:
 SHEETA2.01 CORRIDOR 133, THE DOOR
 LEADING INTO CORRIDOR 132 SHOULD HAVE A
 REVERSED SWING, DIRECTION OF TRAVEL IN A
 EXIT.
  
 11A) CORRIDOR 132 (SHEET A4.04)
 INDICATES THAT THERE IS A ENTRANCE INTO
 UNIT# 116, THIS CORRIDOR IS AN EXTENSION
 OF THE 2 HR RATED STAIRWAY, A EXIT
 PASSAGE SHALL HAVE THE SAME RATING AS
 THE STAIRWAY, 1005.6.5A SMOKEPROOF
 ENCLOSURE SHALL EXIT INTO A PUBLIC WAY
 OR INTO AN EXIT PASSAGE, YARD OPEN COURT
 OR OPEN SPACE HAVING DIRECT ACCESS TO A
 PUBLIC WAY. THE EXIT PASSAGE SHALL BE
 WITHOUT OTHER OPENINGS AND SHALL HAVE
 WALLS,FLOORS, AND CEILING OF 2-HR FIRE
 RATING.
  
 11B) THIS SAME CORRIDOR ALSO HAS A
 STORAGE ROOM DOOR THAT OPENS INTO THIS
 2HR EXIT PASSAGE, 1005.6.5.
  
 11C) A4.04, CORRIDOR# 132, THE DOOR
 SCHEDULE FOR THE FIRST FLOOR (A9.02)
 INDICATES DOORS 10,11) TO HAVE THE WRONG
 NUMBER IDENTIFYING THEM, AND RATING.
  
 11D) A9.02 DOOR SCHEDULE FOR THE
 TOWNHOUSE AND FIRST FLOOR LEVEL ARE
 NUMBERED THROUGH TO 30, THERE OTHER
 MISSING NUMBERED WITH AN IDENTIFYING
 NUMBER HIGHER THAN THIS.
  
 11E) THE TOWNHOUSE ENTRY DOORS ARE NOT
 IDENTIFIED & NOT INCLUDED IN THE DOOR
 SCHEDULE NOR RATING.
  
 12) SHEET A2.01 CORRIDOR# 138:
 1003.2.7.2 WHERE CHANGES IN ELEVATION OF
 12 IN.(305 MM) OR LESSOCCUR IN
 EXIT ACCESS CORRIDORS, EXITS AND EXIT
 DISCHARGE, RAMPS COMPLYING WITH ?1013
 SHALL BE PROVIDED.
  
 13) SHEET A4.01:
 A) ALL TOWNHOUSE ENTRY DOORS LEADING
 FROM THE GARAGE TO THE UNITS ARE NOT
 INCLUDED ON DOOR SCHEDULE NOR RATING.
  
 B) DOOR #21 IN DOOR SCHEDULE IS
 INDICATING BEING INSTALLED IN THE MECH
 ROOM, NO FIRE RATING TABLE 705.1.2
  
 C) TRASH ROOM DOORS #22 TO BE 3/4 HR
 RATING, T ABLE 705.1.2 SAME WITH #23
  
 D)STAIR TOWER DOOR #31 NOT LISTED IN
 DOOR SCHEDULE, NO RATING
  
 E) POWDER ROOM & CLOSET DOORS ARE NOT
 IDENTIFIED.
  
 F) BOTTOM LEFT CORNER "BARRIER CABLES"
 SEE DETAIL 7/A8.02 WRONG REFRENCE?
 SAME REFRENCE ON A4.02
  
 G) SEE 11-4.1.3(8)(D) ENTRANCES THAT ARE
 NOT ACCESSIBLE SHALL HAVE DIRECTIONAL
 SIGNAGE COMPLYING WITH 11-4.30.1,
 11-4.30.2, 11-4.30.3 & 11-4.30.5.
  
 H) A4.01 UNIT# 111, COMMON TO QUITE A
 FEW UNITS, ANSI 4.13.6. THERE IS TO BE
 18" CLEAR ON THE LATCH SIDE OF THE DOOR
 (PULL SIDE) FOR ACCESSIBLE DOORS.THIS IS
 FOR DOORS LOCATED IN COMMON AREAS ALSO.
 NOTE USABLE DOORS SHALL REQUIRE A CLEAR
 32 INCHES.USABLE DOORS ARE SECONARY
 ENTRANCE DOORS OR DOORS THAT ALLOW FOR
 PASSAGE WITHIN THE DWELLING UNIT.
  
  
 14) SHEET A4.03
 A) STAIRWELL NOT LABELED, MAYBE #5: THIS
 SHALL APPLY TO ALL STAIRS, AT THE BOTTOM
 OF LANDINGS UNDER THE STAIR CARRIAGE,
 11-4.4.2 HEAD ROOM, IF VERTICAL
 CLEARENCE OF AN AREA ADJOINING AN
 ACCESSIBLE ROUTE IS REDUCED TO LESS THAN
 80"INCHESA BARRIER TO WARN BLIND OR
 VISUALLY-IMPAIRED PERSONS SHALL BE
 PROVIDED.
  
 B) PROVIDE ADDITIONAL INFORMATION ON
 TECTUM FINALE PANELS, PROVIDE FIRE
 RATINGS,
  
 C) CORRIDOR 132 DOESN'T PROVIDE VERTICAL
 ACCESSIBILITY, NO RAMP. 11-4.1.2
 VERTICAL ACCESSIBILITY, NOTHING IN THIS
 CODE SHALL BE CONSTRUED TO RELIEVE THE
 OWNER OF ANY BUILDING, SSTRUCTURE OR
 FACILITY FROM THE DUTY TO PROVIDE
 VERTICAL ACCESSIBILITY TO ALL LEVELS
 ABOVE OR BELOW THE OCCUPIAABLE GRADE
 LEVEL.
  
 D) CORRIDOR #132 DOOR #02 MISSING THE
 1 1/2 HR RATING, TABLE 705.2.1.
  
 15) SHEET A4.05:
 A) INDICATES 2 UNITS THAT
 DO NOT MEET THE ACCESSIBILTY
 REQUIREMENTS FOR FAIR HOUSING.SEE 1.21
 BUILDINGS WITH ELEVATORS.
  
 B) SHEET A4.04/ A4.05 INDICATE STAIRS
 WITHIN THE 1ST FLOOR, NOT THE STAIRS TO
 THE SECOND FLOOR OF THE UNIT. THE FIRST
 FLOOR IS TO BE ACCESSIBLE.FAIR HOUSING
 INDICATES ON PAGE 1.22 THAT UNITS THAT
 ARE SERVICED BY AN ELEVATOR ARE TO BE
 ACCESSIBLE FOR THAT FLOOR.ELEVATORS MUST
 PROVIDE ACCESS TO PRIMARY ENTRY DOORS OF
 TWO-STORY DWELLING IN ELEVATOR BUILDINGS
 SEE FAIR HOUSING GUIDELINES ON PAGE 4.4
 CHANGES IN LEVEL. WITHIN SINGLE STORY
 DWELLING UNITS( AND ON THE PRIMARY ENTRY
 LEVEL OF A MULTISTORY DWELLING UNITS IN
 BUILDINGS WITH ELEVATORS) THE MAXIMUM
 VERTICAL FLOOR LEVEL CHANGE IS 1/4 INCH,
 EXCEPT WHEN A TAPERED THRESHOLD IS USED
 ,THE MAXIMUM HEIGHT IS 1/2 INCH.
  
 16)SHEET A4.06
 A) PLANS INDICATE A 1/2 INCH DIFFERENCE
 IN GRADE AT THE ENTRANCE TO EACH
 DWELLING UNIT, THE DETAILS ON A9.10
 STOREFRONT DETAIL "B" INDICATE A 3/4"
 CHANGE IN GRADE PLUS THE THRESHOLD.SEE
 FAIR HOUSING THRESHOLDS AT EXTERIOR
 DOORS FOR CORRECTION OF THRESHOLDS.
  
 B) PLANS FOR STAIRWELL RAILINGS/
 GAURDRAILS INDICATE DETAILS ON A8.01
 DETAIL# 1, THE BOTTOM RAIL ON THE STAIRS
 SHALL COMPLY WITH:
 1015.3(1) A 6 INCH SPHERE SHALL NOT PASS
 THROUGH THE TRIANGLE OPENING FORMED BY A
 TREAD , RISER AND THE BOTTOM OF A
 GUARDRAIL.
  
 17) SHEET A4.07
 A) DISCREPANCY BETWEEN A2.01.1 & A4.07
 SHEET A2.01.1 EAST OF STAIRWELL# 4
 INDICATES A STORAGE AREA, A4.07 DOESN'T
 INDICATE STORAGE AREA, THE SECOND ISSUE
 IS ON A4.07 THE AREA EAST OF THIS HAS A
 DOORWAY WITH NO ROOM IDENTIFICATION,
 PLANS INDICATE THE USE OF TECTUM FINALE
 PANELS PROVIDE FIRE AND SMOKE
 DEVELOPMENT INFORMATION.
  
 B) THIS SAME AREA INDICATES SOME TYPE OF
  
 OPENINGS IN THE INTERIOR AS WELL AS
 EXTERIOR WALLS BUT NO INFO? CHECKING
 ELEVATIONS IS THIS AREA FOR VENTILATION
 IN BOTH WALLS?
  
 18) A4.11 VS A9.02 STAIRWELL AND
 ELEVATOR LOBBY DOOR FIRE RATINGS AND
 STYLE ARE REVERSED IN THE DOOR SCHEDULE.
  
 19) A4.13 VS A9.02 STAIRWELL #1 DOOR IS
 LABELED 3/4 HR IN DOOR SCHEDULE.
  
 20) A4.14 INDICATES A 1/2 INCH CHANGE IN
 GRADE, FAIR HOUSING MAX 1/4".
  
 21) A4.16 INDICATES A DOOR # 20 TO A
 MECHANICAL ROOM MISSING ON A9.02 DOOR
 SCHEDULE.
  
 22) A4.21/ A4.23 HAVE ELEVATOR LOBBIES,
 THE WINDOW IN THE LOBBY DOESN'T INDICATE
  
 ANY FIRE RATING, SEE 412.6(1)1HR WALLS
 REQUIRE 20-MINUTE OPENING PROTECTIVES.
  
 23) A4.31 THERE ARE RATED WALLS 1 & 2 HR
 THAT DO NOT INDICATE WHICH SYSTEM SHOULD
 BE USED?
  
 24) A4.34:
 A) THE COMMUNITY ROOM, FAIR HOUSING
 INDICATES THAT THE ACCESSIBLE
 ROUTE TO THE SUN DECK IS DISCREMINTORY
 BECAUSE OF THE TRAVEL DISTANCE REQUIRED
 IF YOU ARE HANDICAPPED.
  
 25) A4.35:
 A) PLANS INDICATE THAT THE SECONARY
 ENTRY DOOR ( TERRACE) FROM UNITS ONTO
 THE PATIO BUT NOT ACCESSIBILE BECAUSE OF
 THE STEPSONTO THE SUN DECK.THIS IS
 DISCRIMINATING AGAINST THE HANDICAPPED
 BECAUSE THE HANDICAPPED HAVE TO USE
 ANOTHER ROUTE.
 CONTACTED BARBRA CHANDLIER/ FAIR HOUSING
  
 B) THE SECOND ISSUE WITH THIS ROUTE IS
 THE GATE HAS TO BE A MINIMUM OF 32"
 CLEAR FOR A SECONARY EXTERIOR DOORWAY.
 PAGE 3.10
  
 C) HANDRAILS WILL BE REQUIRED FOR A
 CHANGE IN GRADE OVER 6".
  
 26) A4.36 THE PLANS APPEAR TO HAVE (2)
 COLUMNS IN THE ROOM ,1 IN THE MIDDLE OF
 A DOORWAY UNIT 303?
  
 27) A4.43 UNIT 405 IT APPEARSTHAT 2
 COLUMNS APPEAR AS COMMENT ABOVE.
  
 28) A4.46 THE KEY PLAN DOES NOT MATCH
 THE CONFIGURATION OF THE BUILDING, THIS
 IS THE SOUTHWEST CORNER OF THE BUILDING
  
 29) A4.53 SAME COMMENT AS 26 ROOM 505.
  
 30) A4.63 SAME COMMENT AS 26 ROOM 605.
  
 31) A4.65 SAME COMMENT AS 26 ROOM 603.
  
 32 A4.72 SAME COMMENT AS 26 ROOM 705.
  
 33) A4.74 SAME COMMENT AS 26 ROOM 703.
  
 34) A4.71/ A4.72/ A2.07:
 A) 1004.1.4 WHERE 2 OR MORE EXITS OR
 EXIT ACCESS DOORS ARE REQUIED, AT LEAST
 2 OF THE EXIT OR EXIT ACCESS DOORS SHALL
 BE PLACED A DISTANCE APART EQUAL TO NOT
 LESS THAN 1/2 OF THE LENGTH OF THE MAX-
 IMUM OVERALL DIAGONAL DIMENSION OF THE
 BUILDING OR AREA TO BE SERVED, REDUCED
 TO 1/3 THE DIAGONAL FOR FIRE SPRINKLERED
 SPRINKLERS.
  
 35)A8.01/DETAILS 7&8,A8.03 /12
 ARCHITECTURAL TRIM
 TYPE I, II CONSTRUCTION OR MORE THAN
 40', SHALL BE SECURED TO THE WALL WITH
 METAL OR APPROVED FASTENERS.WHEN TRIM IS
 LOCATED ALONG THE TOP OF EXTERIOR WALLS,
 IT SHALL BE COMPLETELY BACKED BY THE
 EXTERIOR WALL AND SHALL NOT EXTEND OVER
 THE TOP OF EXTERIOR WALLS. 1404.1.
  
 A36) THIS BUILDING HAS BEEN TRATED AS A
 BIG SQUARE AS FAR AS WIND ZONES!
 1606.2.2.1/1606.2.2.2 MEMBERES THAT ARE
 BOTH PART OF THE MAIN FORCE RESISTING
 SYSTEM AND AS COMPONENTS AND CLADDING
 SHALL BE DESIGNED FOR EACH SEPERATE LOAD
 CASE. LOOKING AT A3.03 THE SOUTH
 ELEVATION THE INTERNAL ZONE HAS BEEN
 TAKEN FOR THE COMPLETE SOUTH SIDE WITH
 THE EXCEPTION OF THE EXTREME END ZONES
 TAKEN AS 16'-0". THERE IS NO
 CONSIDERATION FOR THE SOCALLED INTERIOR
 END ZONES SEE UNITS 601 & 624 FOR
 EXAMPLE. THE WIND ALSO WILL PRESSURIZE
 ONTO THE NORTH WALL AT THE POOL DECK.
 REVISIT PRESSURE ZONES. NO MENTION OF A
 PRESSURE DIFFERENCE AT THE ROOF TOP
 CABANAS CONSIDERED WHICH ZONE?
  
 37)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 38)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EXTERIOR DOORS GLAZED OR NOT
 B) WINDOWS FIXED OR MOVABLE, STOREFRONT
 C) LOUVERS
 D)STORM SHUTTERS
 E) EXTERIOR RAILINGS
 F) EFIS SYSTEMS
 G) SKYLIGHTS IF USED
 H) ROOFING ASSEMBLIES
  
 39) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 40) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 41) 1707.4.3 EACH EXTERIOR DOOR ASSEMBLY
 NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
 42) PLANS DO NOT INDICATE WHERE FAIR
 HOUSING INFORMATION CAN BE FOUND, CLEAR
 FLOOR SPACE FOR KITCHEN APPLIANCES
 BATHROOMS, NOR WHCICH UNITS ARE "A" OR
 "B" UNITS. ALSO MISSING IS INFORMATION
 FOR BACKING FOR BATHROOMS AND LOCATIONS.
  
 43) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026