| 2006-02-16 00:00:00 | ****CORRECTIONS**** |
| | ****TRUSS ENGINEERING**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | 1.)PROVIDE A SIGNED AND SEALED TRUSS |
| | PLACEMENT PLAN. |
| | |
| | THIS WAS PROVIDED BUT THE INFORMATION |
| | REQUIRED BY FAC61G15-23.002 (TITLE |
| | BLOCK) IS NOT ON THE PLAN. |
| | |
| | 2.)SOME OF THE TRUSS ENGINEERING |
| | SHEETS ARE NOT SEALED.THE SHEETS |
| | APPEAR TO BE PHOTOCOPIES.ORIGINAL |
| | SIGNED, SEALED AND DATED ENGINEERING |
| | REQUIRED. |
| | |
| | NOT ADDRESSED PROPERLY.SIGNATURE STILL |
| | APPEARS TO BE A PHOTOCOPY.SOME SHEETS |
| | NOT SEALED.THE COVER PAGE WAS SIGNED |
| | AND SEALED.IF THIS IS TO SERVE AS AN |
| | INDEX SHEET, IT IS TO COMPLY WITH |
| | FAC61G15-31.003. |
| | |
| | NEW COMMENT: |
| | |
| | 3.)THE SEAL IS TO STATE "LICENSE", NOT |
| | "CERTIFICATE".THIS IS REQUIRED |
| | EFFECTIVE JANUARY 1, 2006, |
| | FAC61G15-23.001(1).SEE THE INFORMATION |
| | ON THE FBPE WEBSITE, WWW.FBPE.ORG. |
| | |
| | 4.)ALL SUBMITTALS ARE TO BE REVIEWED |
| | BY DESIGNER OF RECORD.TRUSS |
| | ENGINEERING IS REQUIRED TO BE REVIEWED |
| | BY STRUCTURAL ENGINEER OF RECORD |
| | FAC61G15-31.003(2). |