Plan Review Notes
Plan Review Notes For Permit 05031469
Permit Number 05031469
Review Stop B
Sequence Number 3
Notes
Date Text
2005-07-23 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)THE NOC IS EXPIRED, OVER 90 DAYS
 WITHOUT COMMENCING WORK, FS713.13(2).
 PLEASE RERECORD TO GET A NEW RECORDING
 DATE.
  
 THE FOLLOWING COMMENTS ARE FROM THE
 PREVIOUS REVIEW (KEEPING THE SAME
 COMMENT NUMBERS):
  
 7.)REGARDING THE ROOF PRODUCT APPROVAL
 SUBMITTED:
  
 A. PAGE 11 OF 107 OF THE BUTLER ROOF
 SYSTEM SUBMITTED STATES THAT THE SYSTEM
 HAS A 36 PSF MAXIMUM ALLOWABLE UPLIFT.
 THE WEBSITE WWW.FLORIDABUILDING.ORG HAS
 A DIFFERENT DOCUMENT (104 PAGES),
 DIFFERENT PRODUCT NAME.THE PAPERWORK
 SUBMITTED DOES NOT APPEAR CODE
 COMPLIANT.THE ENGINEER?S RESPONSE IN
 REGARDS TO ENHANCED FASTENING IN ZONES 2
 AND 3 IS ACKNOWLEDGED BUT I AM UNABLE TO
 LOCATE THE DESIGN PRESSURES OF 41 AND
 76.8.PLEASE HIGHLIGHT UPLIFTS IN THE
 PRODUCT APPROVAL, AND SUBMIT PAPERWORK
 CONSISTENT WITH THE STATE WEBSITE, SO
 THAT CODE COMPLIANCE CAN BE DETERMINED.
  
 B. THE PAPERWORK SUBMITTED DOES NOT
 MATCH THE FLORIDA STATE PRODUCT
 APPROVAL.
  
 C. IF A CODE COMPLIANT PRODUCT APPROVAL
 IS NOT SUBMITTED PRIOR TO PERMIT
 ISSUANCE, THE ROOF SUB PERMIT WILL BE
 VOIDED AND A SEPARATE PERMIT WILL BE
 REQUIRED.
  
 ENGINEER PROVIDED SHEET 9 OF 107 WHICH
 SHOWS -41 FOR A 4' SPAN.HOWEVER, THE
 PAPERWORK SUBMITTED IS STILL NOT THE
 SAME AS ON THE STATE WEBSITE FOR THIS
 APPROVAL.
  
 ENGINEERING FOR THE ENHANCED FASTENING
 FOR ZONES 2 AND 3 ARE REQUIRED TO BE
 SIGNED & SEALED ORIGINALS.THE TITLE
 BLOCK IS TO INCLUDE ALL INFORMATION
 REQUIRED BY FAC61G15-23.002.
  
 9.)SEE PREVIOUS LIST, ITEM #8.
 FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED FOR STRUCTURAL COMPONENTS,
 FAC9B72.IF YOU ARE GOING TO INSTALL A
 TESTED/ENGINEERED PRODUCT REQUIRING
 PRODUCT APPROVAL NOT IN ACCORDANCE WITH
 MANUFACTURER'S SPECIFICATIONS ON THE
 WEBSITE, A LOCAL PRODUCT APPROVAL IS
 REQUIRED.ALSO, ALPINE CANNOT CHANGE
 THE SPECIFICATION FOR SIMPSON.I HAVE
 SPOKEN WITH JIM MAMOLA OF ONM&J AND HAVE
 EMAILED THE STATE TO CONFIRM MY
 UNDERSTANDING AND TO GET THIS RESOLVED
 WITH ONM&J.AS DISCUSSED WITH JIM
 MAMOLA, IF THIS ISSUE DOES NOT GET
 RESOLVED PRIOR TO PERMIT ISSUANCE THE
 PERMIT WILL BE ISSUED WITH A PROVISO
 THAT THE TRUSS TIE DOWN SCHEDULE BE
 REVISED.
  
 THE SIMPSON CONNECTORS DO NOT HAVE
 FLORIDA STATE APPROVAL FOR THIS
 APPLICATION.THEY ARE ALSO NOT INCLUDED
 IN THE SIMPSON CATALOG FOR LIGHT GAGE
 METAL TRUSSES, SEE ATTACHED (OR SEE
 CATALOG ONLINE AT STRONG-TIE.COM).IT
 WAS MY UNDERSTANDING WITH JIM MAMOLA
 THAT THIS WOULD BE A PROVISO ITEM, BUT
 SHEET S3 HAS BEEN REVISED AND THE
 TRANSMITTAL LETTER STATES THAT THIS HAS
 BEEN ADDRESSED.ALL CONNECTORS REQUIRE
 FLORIDA STATE OR LOCAL PRODUCT APPROVAL.
  
  
 10.)A 4X FEE IS REQUIRED TO BE CHARGED
 FS553.80(2)(B).