| Plan Review Notes For Permit 05031469 |
| Permit Number |
05031469 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-06-25 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | FROM PREVIOUS REVIEW: | | | 1. SHT A1 TOILET ROOMS 109 & 110 SHOW | | | THE TURNING AREA REQUIRED BY SECTION | | | 11-4.22.3. | | | 3. SHT A2 TOILET ROOMS 201 & 209 SHOW | | | THE TURNING AREA REQUIRED BY SECTION | | | 11-4.22.3. | | | 5. SHTS A12 & A13 TOILET ROOM DETAILS, | | | SHOW THE FOLLOWING ACCESSIBLITY | | | REQUIREMENTS ON DETAILS: | | | D. FAUCETS 11-4.19.5 - NO RESPONSE FOR | | | THE LAVS. NOTE ADDED ONLY REFERS TO THE | | | W/C'S. | | | 6. SHT A12 DETAILS FOR STAFF LOUNGE | | | SHALL SHOW THE FOLLOWING: | | | C. SINK DEPTH 11-4.24.4 - NO RESPONSE | | | NOTED. | | | F. FAUCETS 11-4.24.7 - NO RESPONSE FOR | | | THE SINK FAUCET. - NOTE ADDED ONLY | | | REFERS TO THE W/C VALVE. | | | ****************NEW COMMENT************* | | | 1B. SHT A13 TYPICAL FIXTURE MOUNTING | | | HEIGHTS DETAIL: | | | A. 11-4.16.6 DISPENSERS SHALL BE 19" | | | MINIMUM TO CENTERLINE ABOVE THE FLOOR. | | | DETAIL SHOWS 17". FIG 29. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|