Plan Review Notes
Plan Review Notes For Permit 05031469
Permit Number 05031469
Review Stop P
Sequence Number 2
Notes
Date Text
2005-06-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 FROM PREVIOUS REVIEW:
 1. SHT A1 TOILET ROOMS 109 & 110 SHOW
 THE TURNING AREA REQUIRED BY SECTION
 11-4.22.3.
 3. SHT A2 TOILET ROOMS 201 & 209 SHOW
 THE TURNING AREA REQUIRED BY SECTION
 11-4.22.3.
 5. SHTS A12 & A13 TOILET ROOM DETAILS,
 SHOW THE FOLLOWING ACCESSIBLITY
 REQUIREMENTS ON DETAILS:
 D. FAUCETS 11-4.19.5 - NO RESPONSE FOR
 THE LAVS. NOTE ADDED ONLY REFERS TO THE
 W/C'S.
 6. SHT A12 DETAILS FOR STAFF LOUNGE
 SHALL SHOW THE FOLLOWING:
 C. SINK DEPTH 11-4.24.4 - NO RESPONSE
 NOTED.
 F. FAUCETS 11-4.24.7 - NO RESPONSE FOR
 THE SINK FAUCET. - NOTE ADDED ONLY
 REFERS TO THE W/C VALVE.
 ****************NEW COMMENT*************
 1B. SHT A13 TYPICAL FIXTURE MOUNTING
 HEIGHTS DETAIL:
 A. 11-4.16.6 DISPENSERS SHALL BE 19"
 MINIMUM TO CENTERLINE ABOVE THE FLOOR.
 DETAIL SHOWS 17". FIG 29.
  
 REVIEW BY KEN STEVENS