Plan Review Notes
Plan Review Notes For Permit 05031469
Permit Number 05031469
Review Stop M
Sequence Number 2
Notes
Date Text
2005-06-30 00:00:00PLAN DENIED
 1) PLEASE REFER TO SECTION 307.2.3
 AUXILLIARY DRAIN PANS.MINIMUN DEPTH IS
 1 1/2IN.AND SHALL NOT BE LESS THAN 3IN.
 LARGER THAN THE UNIOT.
 2) PLEASE REFER TO SECTION 601.3 DRYER
 AND EXHAUST DUCT CAN NOT BE INSTALLED IN
 RETURN AIR PLENUMS.
 3) PLEASE REFER TO SECTION 602.2.1
 MATERALS EXPOSED WITHIN PLENUMS.(ABOVE
 CEILING RETURNAIR)
 4) PLESE REFER TO SECTION 606.4.1
 SUPERVISON.DUCT SMOKE DETECTORS.
 5)FIRE DAMPER FOR EF#5 ROOM 122 IS NOT
 REQUIRED PER SECTION 607.1.3 EXECPTION
 #3
 6) PLESE HAVE THE INSPECTION ON
 REFRIGERANT LINES BEFOR LINE CHASE IS
 INSTALLED.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732