| Plan Review Notes For Permit 05031469 |
| Permit Number |
05031469 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-06-30 00:00:00 | PLAN DENIED | | | 1) PLEASE REFER TO SECTION 307.2.3 | | | AUXILLIARY DRAIN PANS.MINIMUN DEPTH IS | | | 1 1/2IN.AND SHALL NOT BE LESS THAN 3IN. | | | LARGER THAN THE UNIOT. | | | 2) PLEASE REFER TO SECTION 601.3 DRYER | | | AND EXHAUST DUCT CAN NOT BE INSTALLED IN | | | RETURN AIR PLENUMS. | | | 3) PLEASE REFER TO SECTION 602.2.1 | | | MATERALS EXPOSED WITHIN PLENUMS.(ABOVE | | | CEILING RETURNAIR) | | | 4) PLESE REFER TO SECTION 606.4.1 | | | SUPERVISON.DUCT SMOKE DETECTORS. | | | 5)FIRE DAMPER FOR EF#5 ROOM 122 IS NOT | | | REQUIRED PER SECTION 607.1.3 EXECPTION | | | #3 | | | 6) PLESE HAVE THE INSPECTION ON | | | REFRIGERANT LINES BEFOR LINE CHASE IS | | | INSTALLED. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|