2005-06-29 00:00:00********UNSAT *******
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW.
  
 1)NOTE: NOTE #1, NO, PLEASE SEE
 GENERATOR IS NOTED AS BEING FUTURE,
 HOWEVER PLEASESEE ATS IS STILL BEING
 SHOWN AS BEING INSTALLED AND NO SPECS
 ETC WERE SUBMITTED FOR THIS.?215.5,
 225.36
  
 2)NOTE: NOTE #2, NO, PLEASE SEE RESPONSE
 LTR MENTIONS LIGHTNING PROTECTION SHALL
 BE SUBMITTED UDNER SEPARATE PERMIT,
 HOWEVER, LIGHTING DEVICES ETC ARE STILL
 BEING SHOWN ON PLANS??
 SEE PREVIOUS NOTE.
  
 3)NOTE:PLEASE SEE DOOR SWINGS ON E-1 ,AT
 GEN/ ELECTRICAL RM AREA.
 PLEASE CORRELATE WITH E-2 , AND A-1.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  