2005-06-29 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)PLEASE PROVIDE THE IMPACT FEE
 RECEIPT (ONLY THE BILL WAS IN THE
 PACKAGE).
  
 3.)SEE PREVIOUS LIST, ITEM #4,
 FBC3206.2, SIDEWALK OBSTRUCTION NOT
 ALLOWED.THE GATE WAS CHANGED ON A1 TO
 BE SLIDING BUT SP1 STILL SHOWS THE GATE
 OVER THE SIDEWALK.
  
 4.) THE HANDRAIL EXTENSIONS ARE SHOWN AT
 42IN AT THE STAIR LANDINGS ON A1.
 PLEASE SEE FBC11-4.9.4, CHAPTER 11
 FIGURE 19, FBC1007.5.5.EXTENSIONS NOT
 SHOWN ON 4-A8 OR A1.
  
 5.)THE STAIR RAIL SERVES AS A
 GUARDRAIL (FBC1015.1) AND IS TO BE NOT
 LESS THAN 42IN HIGH, FBC1015.2, A1.
  
 6.)SECTION 2-A8 SHOULD BE REVISED TO
 ELIMINATE THE LAUNDRY CHUTE (STILL SHOWS
 THE CHUTE OPENING INTO AN EXIT ACCESS
 CORRIDOR FBC705.2.4.3).IF THE LAUNDRY
 CHUTE IS TO REMAIN, PLEASE ADD IT TO THE
 FLOOR PLAN AND COMPLY WITH FBC705.2.4.3.
  
 7.)REGARDING THE ROOF PRODUCT APPROVAL
 SUBMITTED:
  
 A. PAGE 11 OF 107 OF THE BUTLER ROOF
 SYSTEM SUBMITTED STATES THAT THE SYSTEM
 HAS A 36 PSF MAXIMUM ALLOWABLE UPLIFT.
 THE WEBSITE WWW.FLORIDABUILDING.ORG HAS
 A DIFFERENT DOCUMENT (104 PAGES),
 DIFFERENT PRODUCT NAME.THE PAPERWORK
 SUBMITTED DOES NOT APPEAR CODE
 COMPLIANT.THE ENGINEER?S RESPONSE IN
 REGARDS TO ENHANCED FASTENING IN ZONES 2
 AND 3 IS ACKNOWLEDGED BUT I AM UNABLE TO
 LOCATE THE DESIGN PRESSURES OF 41 AND
 76.8.PLEASE HIGHLIGHT UPLIFTS IN THE
 PRODUCT APPROVAL, AND SUBMIT PAPERWORK
 CONSISTENT WITH THE STATE WEBSITE, SO
 THAT CODE COMPLIANCE CAN BE DETERMINED.
  
 B. THE PAPERWORK SUBMITTED DOES NOT
 MATCH THE FLORIDA STATE PRODUCT
 APPROVAL.
  
 C. IF A CODE COMPLIANT PRODUCT APPROVAL
 IS NOT SUBMITTED PRIOR TO PERMIT
 ISSUANCE, THE ROOF SUB PERMIT WILL BE
 VOIDED AND A SEPARATE PERMIT WILL BE
 REQUIRED.
  
 8.)THE DETAILS DATED 9/02/02 PROVIDED
 BY ALPINE FOR THE SIMPSON CONNECTORS
 SHOW A STRESS INCREASE FOR STEEL.THIS
 IS NOT ALLOWED FBC1609.4.3(2).SIMPSON
 AND USP HAVE REVISED THEIR CATALOG.
  
 9.)SEE PREVIOUS LIST, ITEM #8.
 FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED FOR STRUCTURAL COMPONENTS,
 FAC9B72.IF YOU ARE GOING TO INSTALL A
 TESTED/ENGINEERED PRODUCT REQUIRING
 PRODUCT APPROVAL NOT IN ACCORDANCE WITH
 MANUFACTURER?S SPECIFICATIONS ON THE
 WEBSITE, A LOCAL PRODUCT APPROVAL IS
 REQUIRED.ALSO, ALPINE CANNOT CHANGE
 THE SPECIFICATION FOR SIMPSON.I HAVE
 SPOKEN WITH JIM MAMOLA OF ONM&J AND HAVE
 EMAILED THE STATE TO CONFIRM MY
 UNDERSTANDING AND TO GET THIS RESOLVED
 WITH ONM&J.AS DISCUSSED WITH JIM
 MAMOLA, IF THIS ISSUE DOES NOT GET
 RESOLVED PRIOR TO PERMIT ISSUANCE THE
 PERMIT WILL BE ISSUED WITH A PROVISO
 THAT THE TRUSS TIE DOWN SCHEDULE BE
 REVISED.
  
 10.)SEE ATTACHED FS553.80(2)(B).