Plan Review Notes
Plan Review Notes For Permit 05031469
Permit Number 05031469
Review Stop P
Sequence Number 1
Notes
Date Text
2005-04-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHT A1 TOILET ROOMS 109 & 110 SHOW
 CLEAR FLOOR SPACE FOR THE FIXTURES AND
 THE TURNING AREA REQUIRED BY SECTIONS
 11-4.16.2, 11-4.19.3 AND 11-4.22.3.
 2) SHT A1 DRINKING FOUNTAINS, SHOW THE
 CLEAR FLOOR SPACE FOR ACCESSIBLE
 DRINKING FOUNTAINS REQUIRED BY SECTION
 11-4.15.5.
 3) SHT A2 TOILET ROOMS 201 & 209 SHOW
 THE CLEAR FLOOR SPACE AND TURNING AREA
 REQUIRED BY SECTIONS 11-4.16.2,
 11-4.19.3 AND 11-4.22.3.
 4) SHT A2 SHOW THE CLEAR FLOOR SPACE FOR
 THE ACCESSIBLE DRINKING FOUNTAIN
 REQUIRED BY SECTION 11-4.15.5.
 5) SHTS A12 & A13 TOILET ROOM DETAILS,
 SHOW THE FOLLOWING ACCESSIBLITY
 REQUIREMENTS ON DETAILS:
 A. TOILET HEIGHT 11-4.16.3
 B. FLUSH CONTROLS 11-4.16.5.
 C. HEIGHT & CLEARANCES 11-4.19.2
 D. FAUCETS 11-4.19.5
 E. BOTTOM OF MIRROR TO BE 40" NOT 42"
 AS SHOWN. 11-4.19.6
 6) SHT A12 DETAILS FOR STAFF LOUNGE
 SHALL SHOW THE FOLLOWING:
 A. HEIGHT 11-4.24.2
 B. KNEE CLEARANCE 11-4.24.3
 C. SINK DEPTH 11-4.24.4
 D. CLEAR FLOOR SPACE SHALL BE PROVIDED
 TO ALLOW FORWARD APPROACH AND SHALL
 EXTEND A MAXIMUM OF 19" UNDERNEATH THE
 SINK. 11-4.24.2
 E. EXPOSED PIPES & SURFACES 11-4.24.6
 F. FAUCETS 11-4.24.7
 7) DOORS SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE REQUIRED FOR ANY FIXTURE.
 SECTION 11-4.22.2
 8) SHTS P-1 & P-4 BACKFLOW PROTECTION
 SHALL BE REQUIRED ON THE SUPPLY LINES TO
 EACH WATER FEATURE.
 9) SEPARATE PERMITS REQUIRED FOR THE
 WATER FEATURES AS INDICATED BY NOTE ON
 SHT A1. INFORMATION ON DRAINING
 FOUNTAINS WILL BE REQUIRED AT THAT TIME.
 SECTION 104.2.1.
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]