| 2005-04-23 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) SHT A1 TOILET ROOMS 109 & 110 SHOW |
| | CLEAR FLOOR SPACE FOR THE FIXTURES AND |
| | THE TURNING AREA REQUIRED BY SECTIONS |
| | 11-4.16.2, 11-4.19.3 AND 11-4.22.3. |
| | 2) SHT A1 DRINKING FOUNTAINS, SHOW THE |
| | CLEAR FLOOR SPACE FOR ACCESSIBLE |
| | DRINKING FOUNTAINS REQUIRED BY SECTION |
| | 11-4.15.5. |
| | 3) SHT A2 TOILET ROOMS 201 & 209 SHOW |
| | THE CLEAR FLOOR SPACE AND TURNING AREA |
| | REQUIRED BY SECTIONS 11-4.16.2, |
| | 11-4.19.3 AND 11-4.22.3. |
| | 4) SHT A2 SHOW THE CLEAR FLOOR SPACE FOR |
| | THE ACCESSIBLE DRINKING FOUNTAIN |
| | REQUIRED BY SECTION 11-4.15.5. |
| | 5) SHTS A12 & A13 TOILET ROOM DETAILS, |
| | SHOW THE FOLLOWING ACCESSIBLITY |
| | REQUIREMENTS ON DETAILS: |
| | A. TOILET HEIGHT 11-4.16.3 |
| | B. FLUSH CONTROLS 11-4.16.5. |
| | C. HEIGHT & CLEARANCES 11-4.19.2 |
| | D. FAUCETS 11-4.19.5 |
| | E. BOTTOM OF MIRROR TO BE 40" NOT 42" |
| | AS SHOWN. 11-4.19.6 |
| | 6) SHT A12 DETAILS FOR STAFF LOUNGE |
| | SHALL SHOW THE FOLLOWING: |
| | A. HEIGHT 11-4.24.2 |
| | B. KNEE CLEARANCE 11-4.24.3 |
| | C. SINK DEPTH 11-4.24.4 |
| | D. CLEAR FLOOR SPACE SHALL BE PROVIDED |
| | TO ALLOW FORWARD APPROACH AND SHALL |
| | EXTEND A MAXIMUM OF 19" UNDERNEATH THE |
| | SINK. 11-4.24.2 |
| | E. EXPOSED PIPES & SURFACES 11-4.24.6 |
| | F. FAUCETS 11-4.24.7 |
| | 7) DOORS SHALL NOT SWING INTO THE CLEAR |
| | FLOOR SPACE REQUIRED FOR ANY FIXTURE. |
| | SECTION 11-4.22.2 |
| | 8) SHTS P-1 & P-4 BACKFLOW PROTECTION |
| | SHALL BE REQUIRED ON THE SUPPLY LINES TO |
| | EACH WATER FEATURE. |
| | 9) SEPARATE PERMITS REQUIRED FOR THE |
| | WATER FEATURES AS INDICATED BY NOTE ON |
| | SHT A1. INFORMATION ON DRAINING |
| | FOUNTAINS WILL BE REQUIRED AT THAT TIME. |
| | SECTION 104.2.1. |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |