Plan Review Notes
Plan Review Notes For Permit 05031469
Permit Number 05031469
Review Stop M
Sequence Number 1
Notes
Date Text
2005-05-11 00:00:00DENIED:
 1.PLAN SHEET A3 INDICATES THE
 FOLLOWING ROOMS AS HAVING A 1 HR
 FLOOR/CEILING ASSEMBLY; 111, 115, 123,
 121, 122, 126, 124, 120, 125, 119, 118,
 117 & 116.ALSO 2ND FLOOR 200.PLEASE
 PROVIDE DETAIL FOR THE PENETRATION OF
 THE DUCT/GRILLES.PLEASE NOTE, FIRE
 DAMPERS REQUIRED AT CEILING GRILLES.
  
 2.PLAN SHEET M-1 INDICATES FLEX DUCT
 PENETRATING RATED PARTITIONS WHICH IS
 NOT PERMITTED EPR 2001 FBC(M)603.5.5.
  
 3.PLAN M-1 INDICATES DRYER EXHAUST
 DUCT PENETRATING RATED PARTITION & FLOOR
 CEILING ASSEMBLY IN VIOLATION OF 2001
 FBC(M)504.2.
  
 4.PROVIDE ELEVATION FOR THE
 TERMINATION OF ALL EXHAUST TO THE
 EXTERIOR WALL UNDER/AT THE STAIRWELL.
 PER 2001 FBC(M)401.5.2, EXHAUST SHALL
 TERMIANTE AS TO NOT CREATE A NUISANCE
 AND SHALL NOT BE DIRECTED ONTO WALKWAYS.
  
 5.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS REQUIRED PER
 2001 FBC(M)606.2.1 & 606.4.1 #2.
  
 6.PLAN SHEET M-4, THE AHU DETAIL
 INDICATES THE AUXILIARY DRAIN LINE "SEE
 PLUMBING FOR CONTINUATION".THE
 AUXILIARY LINE IS NOT SHOWN ON THE
 PLUMBING PLANS.PLEASE NOTE, PER 2001
 FBC(M)307.2.3 & 307.2.4, THE AUXILAIRY
 DRAIN LINE SHALL TERMINATE AT A
 "CONSPICUOUS" POINT TO SERVE AS AN ALARM
 THAT THE PRIMARY DRAIN IS RESTRICTED.
 IN LIEU OF A SECONDARY DRAIN LINE AN
 APPROVED FLOAT DETECTOR MAY BY USED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  