| 2005-05-11 00:00:00 | DENIED: |
| | 1.PLAN SHEET A3 INDICATES THE |
| | FOLLOWING ROOMS AS HAVING A 1 HR |
| | FLOOR/CEILING ASSEMBLY; 111, 115, 123, |
| | 121, 122, 126, 124, 120, 125, 119, 118, |
| | 117 & 116.ALSO 2ND FLOOR 200.PLEASE |
| | PROVIDE DETAIL FOR THE PENETRATION OF |
| | THE DUCT/GRILLES.PLEASE NOTE, FIRE |
| | DAMPERS REQUIRED AT CEILING GRILLES. |
| | |
| | 2.PLAN SHEET M-1 INDICATES FLEX DUCT |
| | PENETRATING RATED PARTITIONS WHICH IS |
| | NOT PERMITTED EPR 2001 FBC(M)603.5.5. |
| | |
| | 3.PLAN M-1 INDICATES DRYER EXHAUST |
| | DUCT PENETRATING RATED PARTITION & FLOOR |
| | CEILING ASSEMBLY IN VIOLATION OF 2001 |
| | FBC(M)504.2. |
| | |
| | 4.PROVIDE ELEVATION FOR THE |
| | TERMINATION OF ALL EXHAUST TO THE |
| | EXTERIOR WALL UNDER/AT THE STAIRWELL. |
| | PER 2001 FBC(M)401.5.2, EXHAUST SHALL |
| | TERMIANTE AS TO NOT CREATE A NUISANCE |
| | AND SHALL NOT BE DIRECTED ONTO WALKWAYS. |
| | |
| | 5.FAN SHUTDOWN BY DUCT SMOKE DETECTOR |
| | WITH NOTIFICATION TO ALARM/STROBE IN |
| | NORMALLY OCCUPIED AREAS REQUIRED PER |
| | 2001 FBC(M)606.2.1 & 606.4.1 #2. |
| | |
| | 6.PLAN SHEET M-4, THE AHU DETAIL |
| | INDICATES THE AUXILIARY DRAIN LINE "SEE |
| | PLUMBING FOR CONTINUATION".THE |
| | AUXILIARY LINE IS NOT SHOWN ON THE |
| | PLUMBING PLANS.PLEASE NOTE, PER 2001 |
| | FBC(M)307.2.3 & 307.2.4, THE AUXILAIRY |
| | DRAIN LINE SHALL TERMINATE AT A |
| | "CONSPICUOUS" POINT TO SERVE AS AN ALARM |
| | THAT THE PRIMARY DRAIN IS RESTRICTED. |
| | IN LIEU OF A SECONDARY DRAIN LINE AN |
| | APPROVED FLOAT DETECTOR MAY BY USED. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |