| Plan Review Notes For Permit 05031469 |
| Permit Number |
05031469 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-04-28 00:00:00 | 1) ALL CONSTRUCTION, ALTERATION AND | | | DEMOLITION TO COMPLY WITH NFPA 241. | | | | | | 2) PLEASE NOTE THAT THE BUILDING IS | | | DESCRIBED AS A TWO STORY STRUCTURE THAT | | | IS 55' IN HEIGHT. SHEET #LS1. | | | | | | 3) THE DOOR SWING APPEARS TO OBSTRUCT | | | MORE THAN 1/2 THE WIDTH OF THE CORRIDOR. | | | SHEET #LS1.- 1ST FLOOR | | | | | | 4) EMERGENCY LIGHTING APPEARS TO BE | | | MISSING IN EGRESS AREAS ON BOTH FLOORS. | | | | | | 5) DRAWINGS DON'T SHOW LOCATIONS OF FIRE | | | HYDRANTS. | | | | | | 7) THE DOUBLE CHECK DETECTOR ASSEMBLY | | | SHALL BE SECURED WITH A CHAIN AND LOCK | | | IN ADDITION TO ELECTRONIC SUPERVISION. | | | | | | 8) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR FIRE SPRINKLER/FIRE | | | ALARM SYSTEMS. | | | | | | 9) NEW BUILDINGS ARE REQUIRED TO BE | | | MONITORED BY A UL LISTED CENTRAL STATION | | | SERVICE. | | | | | | 10) PLEASE PROVIDE THE LOCATION OF THE | | | FIRE DEPARTMENT CONNECTION. IT SHALL BE | | | LOCATED NOT MORE THAN 150' FROM THE | | | CLOSEST HYDRANT | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | WPBFR(561) 835-2910 OR 805-6722 |
|