| 2005-04-18 00:00:00 | ********** UNSAT ************** |
| | |
| | 1)NOTE" PLEASE SEE IF GENERATOR IS GOING |
| | TO BE INCLUDED UNDER BASE BLDG PERMIT, |
| | PLEASE SUBMIT ALL MANUFACTURE SPEC |
| | SHEETS FOR GENERATOR, ATS, SUB BASE FUEL |
| | TANK. |
| | IF NOT UNDER BASE BLDG, THIS WILL BE |
| | REQUIRED TO BE UNDER A SEPARATE PERMIT. |
| | |
| | 2)NOTE: PLEASE KNOW, IF "LIGHTING |
| | PROTECTION" IS ALSO GOING TO BE UNDER |
| | THE BASE BLDG ELECTRICAL PERMIT, PLEASE |
| | SHOW DETAILS FOR RODS, CONNECTIONS, ETC. |
| | IF SYSTEM IS GOING TO BE INSTALLED BY A |
| | LIGHTING PROTECTION SUB-CONTRACTOR, THEN |
| | SYSTEM CAN BE SHOWN ON PLANS, HOWEVER IT |
| | WILL REQUIRED A SEPARATE PERMIT. |
| | PLEASE BE SURE TO SEE NFPA-780 FOR |
| | SYSTEMS WHICH APPROVED AND RECOGNIZED |
| | AND APPROVED BY NFPA. |
| | |
| | 3)NOTE: PLEASE SEE 600.5 FOR REQUIRED |
| | SIGN CIRCUIT. |
| | |
| | 4)NOTE: PLEASE SEE AWG FOR AHU SHOWN AS |
| | #12, ON 50A OCP. |
| | 424.3,240.4,310.16 |
| | |
| | 5)NOTE: PLEASE CLARIFY LOCATION OF GFI |
| | PER 210.63 |
| | |
| | 6)NOTE: PLEASE CLARIFY SIZE OF AWG FOR |
| | INSTA-HOT ON PANEL "G". 8.3KW, W/ 30A |
| | OCP AND #12? |
| | 240.4,310.16 |
| | |
| | 7)NOTE: PLEASE CLARIFY, TOP LEFT CORNER |
| | OF EACH PANEL, "PANEL TYPE" ALL SHOWN AS |
| | ITE ETC, HOWEVER, PANEL "L: MENTIONS |
| | VERIFY W/ TEKTRON??? |
| | |
| | PLEASE SEE OTHER POSSIBLE COMMENTS FROM |
| | OTHER REVIEWERS WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |