2005-05-12 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.
  
 3.)THE SQUARE FOOTAGE ON THE ENERGY
 CALC IS DIFFERENT FROM THE AREA
 CALCULATIONS.
  
 4.)FBC3206.2, SIDEWALK OBSTRUCTION NOT
 ALLOWED.THE GATE SWINGS OVER THE
 PUBLIC SIDEWALK, SP1.
  
 5.)FBC 304, GYMNASIUM IS ASSEMBLY
 OCCUPANCY.PLANS SHOW A GYM ON THE
 SECOND FLOOR.SHOW OCCUPANCY SEPARATION
 REQUIRED BY FBC TABLE 704.1 (2 HOUR);
 REVISE LS1.
  
 6.)ADDITIONAL FEES DUE, SEE ATTACHED
 (RADON).
  
 7.) A8 SHOWS A 1 HR TENANT SEPARATION
 BETWEEN THE GYM AND 1ST FLOOR.A 2 HR
 (OCCUPANCY) SEPARATION REQUIRED.
  
 8.)THE SIMPSON AND ALPINE CONNECTORS
 SPECIFIED ARE FOR WOOD TRUSSES.
 FAC9B72, IF YOU ARE GOING TO SPECIFY AND
 INSTALL A TESTED/ENGINEERED PRODUCT
 REQUIRING A PRODUCT APPROVAL NOT IN
 ACCORDANCE WITH THE MANUFACTURER?S
 SPECIFICATIONS, APPLY FOR A LOCAL
 PRODUCT APPROVAL AND ENGINEERING/TEST
 REPORTS.WWW.FLORIDABUILDING.ORG FOR
 MORE INFORMATION.
  
 9.)THE NOA FOR THE METAL ROOF REQUIRES
 ENGINEERED ENHANCED FASTENING IN THE
 PERIMETER AND CORNER ZONES.
  
 10.)THE NOA FOR THE METAL ROOF IS FOR
 WOOD DECKS.SUBMIT A LOCAL PRODUCT
 APPROVAL AND ENGINEERING IF YOU WISH TO
 USE THIS PRODUCT IN THIS APPLICATION, OR
 SUBMIT PAPERWORK IN ACCORDANCE WITH YOUR
 JOB CONDITIONS.
  
 11.)PROVIDE PRODUCT APPROVALS FOR THE
 FIXED GLASS WINDOWS.
  
 12.)OPENINGS WITHIN 10 FEET OF THE
 EXTERIOR STAIR ARE TO HAVE ? HOUR
 ASSEMBLIES.OPENINGS ON BOTH THE NORTH
 AND WEST ELEVATIONS APPEAR TO BE
 AFFECTED.NOTE ON PLAN (DOOR #27,
 AFFECTED WINDOWS) AND SUBMIT APPROPRIATE
 PRODUCT APPROVALS/FIRE RATING
 INFORMATION.
  
 13.)FBC 705.2.4.3, ACCESS OPENINGS TO
 LAUNDRY CHUTES SHALL NOT BE LOCATED IN
 EXIT ACCESS CORRIDORS (2ND FLOOR).
  
 14.)I WAS UNABLE TO LOCATE DOOR #24 ON
 THE PLAN.PLEASE PROVIDE DIRECTION AND
 PRODUCT APPROVAL IF THIS IS ON THE PLAN.
  
 15.)PROVIDE A DETAIL FOR THE STAFF
 LOUNGE SINK, FBC11-4.24.
  
 16.)HANDRAIL REQUIRED BOTH SIDES,
 EXTERIOR STAIR, FBC1007.5.2.
  
 17.)PROVIDE DESIGN CRITERIA FOR
 HANDRAILS AND GUARDRAILS, FBC1608.2.
  
 18.)THE STAIR HANDRAILS, A10, REQUIRE
 EXTENSIONS AT TOP AND BOTTOM
 FBC1007.5.5.
  
 19.)THE DOORS IN A SERIES, VESTIBULE
 (124), SHEET A1, ARE TO COMPLY WITH
 FBC11 FIGURE 26.
  
 20.)PROVIDE A DETAIL FOR THE GUARDRAIL
 AND HANDRAIL FOR THE EXTERIOR STAIRS.
  
 21.)IDENTIFY THE FIRE RATED WALL IN
 ACCORDANCE WITH FBC704.2.1.4.
  
  
  
  