2005-06-22 00:00:00************ UNSAT *************
  
 1)NOTE: PLEASE SEE NEW RISER DIAGRAM NOW
 SUBMITTED. PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR TO POOL SUB PANEL,
 250.110,250.24,680.6
  
 2)NOTE: PLEASE SEE ELECTRICAL SHEET HAS
 NOW COME BACK WITH A DIFFERENT SIGNATURE
 FOR ARCH OF RECORD THAN SIGNATURE ON
 FILE FOR ARCH AND DIFERENT FROM
 SIGNATURE ON OTHER SHEETS. THIS
 SIGNATURE AS SHOWN IS NOT ACCEPTABLE TO
 THIS OFFICE. THIS HAS BEEN NOTED ON
 NUMEROUS PREVIOUS REVIEWS OF OTHER
 PROJECTS. PLEASE SEE FS 481.221 WHICH
 REQUIRES THE ARCH TO SIGN,SEAL AND DATE
 PLANS. THIS MAY ONLY BE DONE BY THE
 ARCHITECT HOLDING LICENSE AND SAID SEAL.
 ONE COPY OFELECTRICAL PLANS ARE BEING
 RETAINED AND SHALL BE PLACED WITH PLANS
 ALREADY IN RETENTION. THIS WAS SUBMITTED
 TO THE BLDG OFFICAL AND ALL PLANS SHALL
 BE TURNED OVER TO THE STATE LEGAL
 COUNSEL FOR STATE BOARD OF ARCHITECT'S
 FOR REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  