Plan Review Notes
Plan Review Notes For Permit 05031461
Permit Number 05031461
Review Stop E
Sequence Number 1
Notes
Date Text
2005-03-31 00:00:00**** UNSAT ****
  
 1)NOTE: PLEASE SEE PLANS INDICATE A
 DRYER, HOWEVER PANEL SCHEDULE AND LOAD
 CALCULATIONS DO NOT SHOW.
  
 2)NOTE: PLEASE SEE PANEL SCHEDULE
 INDICATES DISHWASHER ON A 2P20A BRKR FOR
 OCP.?
 IS THIS PART OF DISPOSAL/DISHWASHER?
  
 3)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING TO CONDENSING UNITS.
 PLEASE ALSO SEE 3-#6'S TO COND UNIT. IS
 THIS 2-#6'S AND ONE #10?
 PLEASE SEE CONDUIT FILL FOR SCHEDULE 80
 PVC. PLEASE SEE EUIPMENT GROUNDING PER
 250.122
  
 4)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 5)NOTE: PLEASE SEE NUMEROUS BRANCH
 CIRCUITS WITH 15A OCP ON #12 AWG. THIS
 IS OK AND DOES MEET CODE, HOWEVER PLEASE
 VERIFY. IF SHOWN, THEN THIS MUST BE
 DONE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  