| 2005-04-26 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- SHEET A-2: A)KEYED DETAILS DON'T |
| | MATCH. THERE IS NOT SHEET A-13. REVISE |
| | ALL KEYED DETAILS TO MATCH SPECIFIC |
| | DETAIL SHEET AND NUMBER/LETTER. |
| | |
| | B) DELETE BBQ TO MATCH FLOOR PLAN. |
| | |
| | C) FOUNDATION NOTE #2. SEE CHAPTER 19 |
| | FBC 2001 FOR PROPER CONCRETE REFERENCE. |
| | REVISE NOTE AS REQUIRED. |
| | |
| | 2- SHEET A-3: A) STAIR WINDERS TO HAVE |
| | 6" MIN. AT THE NARROWEST EDGE AS REQ'D |
| | BY SECTION 1007.8.1 FBC 2001. REVISE. |
| | |
| | B) KEYED DETAIL/SECTIONS DON'T MATCH. |
| | THERE IS NOT SHEET A-13. REVISE ALL |
| | DETAILS TO MATCH CORRECT SHEET & NUMBER. |
| | |
| | C) DESIGN PARAMETERS: WHERE IS THE BASIC |
| | VELOCITY PRESSURE TAKEN FROM?. THERE IS |
| | NOT MENTION OF THAT IN THE FBC 2001. |
| | |
| | 3- SHEET A-7: A) REVISE THE TRUSS ANCHOR |
| | SCHEDULE. SEE LATEST CATALOGUE OR |
| | PROVIDE COMPLETE ENGINEERING CALCS FOR |
| | TYPE AND NUMBER OF FASTENERS THAT DIFFER |
| | FROM THOSE TESTED AND PUBLISHED BY THE |
| | MANUFACTURER. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | B) KEYED DETAILS/SECTIONS DON'T MATCH |
| | THOSE SHOWN ON DETAIL SHEET. REVISE AS |
| | REQUIRED. |
| | |
| | 4- SHEET A-8: KEYED DETAILS DON'T MATCH |
| | THOSE SHOWN ON DETAIL SHEET. REVISE. |
| | |
| | 5- SPECIFY ROOF TILE FASTENING AS REQ'D |
| | BY SEC. 104.2.1.1 CITY AMENDMENTS TO FBC |
| | 2001. |
| | |
| | 6- PLANS CALL FOR FLAT ROOF TILE. |
| | PRODUCT APPROVAL SUBMITTED IS FOR "S". |
| | TILE. REVISE PLANS AS REQUIRED. |
| | |
| | 7- PROVIDE STRUCTURAL BUCK DETAIL FOR: |
| | A) WINDOWS. SEE SEC. 1707.4.4.2 FBC 2001 |
| | B) DOORS. SEE SEC. 1707.4.4.2 FBC 2001 |
| | FOR PROPER BUCK INSTALLATION. |
| | C) GARAGE DOOR. |
| | |
| | 8- CLEARLY SPECIFY SIZE OF MULLION AND |
| | ANCHORS TO BE USED FOR DOOR MULLION |
| | ABOVE 12'-0" WIDE SLIDING GLASS DOORS. |
| | SEE PRODUCT APPROVAL AND VERIFY THAT |
| | MULLION WILL MEET THE REQUIRED DESIGN |
| | PRESSURES. |
| | |
| | |
| | 9- CLARIFY IF USING THE STEEL DOORS FOR |
| | ENTRY DOORS. OTHERWISE, PROVIDE |
| | CORRESPONDING PRODUCT APPROVAL. |
| | |
| | 10 ENERGY CALCULATIONS ARE INCOMPLETE: |
| | THIS IS A 2 STORY HOUSE AND CALCULATIONS |
| | WERE DONE WITHOUT INCLUDING THE 2ND |
| | FLOOR. REVISE AS REQUIRED. |
| | |
| | 11- OWES $988.89 FOR UPDATED VALUATION |
| | AND RADON FEES. |
| | |
| | 12- PROVIDE STAIRS COMPLETE STAIR |
| | FRAMING DETAILS AND SPECS. |
| | **PROVIDE HANDRAIL SPECS. SEE SECTION |
| | 1007.5 FBC 2001. |
| | ***SPECIFY FIREBLOCKING. SEE SEC. |
| | 2305.1.4 FBC 2001 |
| | |
| | |