Plan Review Notes
Plan Review Notes For Permit 05031435
Permit Number 05031435
Review Stop E
Sequence Number 4
Notes
Date Text
2006-06-16 00:00:00**** UNSAT ***
  
  
 1) NOTE: PLEASE SEE PLANS CAN BE
 REDLINED FOR MISSING LT FIXTURE REQUIRED
 FOR EGRESS. 210.70 LS 101 7.8.1.3
  
 2) NOTE: CALLED SUSI FROM STERLING COMM
 TO BRING IN 2ND SET OF SIGNED, AND
 SEALED PLANS.
  
 3) NOTE: PANEL SCHEDULE SHALL BE REVISED
 BEFORE FINAL AND SUBMITTED FOR REVIEW TO
 INDICATE ALL CIRCUITS AND ROOMS/AREAS IN
 WHICH THEY FEED. 408.4
  
  
 THESE NEED TO BE VERIFIED FOR THE SAME
 AS REV SUBMITTED AND REDLINED FOR NOTE
 #1 AND #3
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.