Plan Review Notes
Plan Review Notes For Permit 05031435
Permit Number 05031435
Review Stop E
Sequence Number 3
Notes
Date Text
2006-06-09 00:00:00****** UNSAT ******
  
  
 ** PLEASE SEE THE FOLLOWING COMMENTS AS
 THE RISER AND SERVICE DIAGRAM HAS
 COMPLETELY CHANGED FROM THE ORIGINAL
 PLANS SUBMITTED AND REVIEW.
  
  
 1) NOTE: PLEASE CORRELATE IDENTIFICATION
 OF PANELS AND CORRELATE WITH RISER.
 PLEASE SEE RISER SHOWS PANELS, A1, A2,
 B, C, AND POOL PANEL, YET THE TWO 200A
 PANEL SCHEDULES SUBMITTED ARE SHOWN AS
 "A" AND "B"?
 215.5
  
 2) NOTE: PLEASE SEE PANEL "A" INDICATES
 "FEED THRU LUGS" TO PANEL "B", YET RISER
 SHOWS PANEL "B" COMING FROM THE
 METER/MAIN PANEL.?
 215.5
  
 3) NOTE: PLEASE SEE NO PANEL SCHEDULE
 FOR THE METER/MAIN 8 CIRCUIT SECTION WAS
 SUBMITTED, YET THERE ARE ITEMS BEING FED
 FROM THIS PANEL?
 215.5,408
  
 4) NOTE: PLEASE SEE SERVICE IS NOW
 400A'S AND THE SEC'S ARE STILL BEING
 SHOWN FOR THE ORIGINAL 200A SERVICE??
 PLEASE INDICATE OF THE SEC'S ARE
 INSTALLED BY FPL, OR IF THESE ARE SEC'S
 INSTALLED TO A HAND HOLE WHICH WOULD
 FALL UNDER 310.16,240.4,310.15B6
 IN THIS CASE, PLEASE SEE THE FOLLOWING
 NOTE.
 215.5
  
 5) NOTE: PLEASE SEE THE GROUNDING
 ELECTRODE CONDUCTOR WAS NOT INCREASED
 FOR THE 400A SERVICE.
 PLEASE SEE 310.15B6, 250.66
 MIN SIZE SHALL BE 1/0.
  
 6) NOTE: PLEASE CORRELATE PANELS WITH
 RISER AS RISER SHOWS THESE AS 32CIR AND
 PANELS ARE SHOWN AS 42 CIRCUIT??
 215.5
  
 7) NOTE: PLEASE SEE SD IN BEDRMS WITH
 SLOPED CEILINGS SHALL MEET NFPA-72 BEING
 INSTALLED WITHIN 3' OF THE PEAK ON A
 SLOPED CEILING.
 CHAPTER 8-1 INNFPA-72 99 OR CHAPTER 11
 IN NFPA-72 2002.
 PLEASE SEE LOCATIONS ON PLANS WHICH NEED
 TO BE ADJUSTED.
  
 8) NOTE: PLEASE SEE KITCHEN COUNTER
 SPACE MISSING GFI RECEPTS AS REQUIRED
 PER 210.52C1-5, 210.8A6
  
 9) NOTE: PLEASE SEE RISER SHOWS A POOL
 PANEL , YET PLANS DO NOT??
 PLEASE SHOW LOCATION.
 215.5
  
 10) NOTE: PLEASE SEE REAR EGRESS WHERE A
 MIN OF ONE LT FIXTURE OF SOME TYPE WILL
 BE REQUIRED FOR EGRESS.
 210.70, NFPA-101 7.8
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  