| Date |
Text |
| 2006-06-09 00:00:00 | ****** UNSAT ****** |
| | |
| | |
| | ** PLEASE SEE THE FOLLOWING COMMENTS AS |
| | THE RISER AND SERVICE DIAGRAM HAS |
| | COMPLETELY CHANGED FROM THE ORIGINAL |
| | PLANS SUBMITTED AND REVIEW. |
| | |
| | |
| | 1) NOTE: PLEASE CORRELATE IDENTIFICATION |
| | OF PANELS AND CORRELATE WITH RISER. |
| | PLEASE SEE RISER SHOWS PANELS, A1, A2, |
| | B, C, AND POOL PANEL, YET THE TWO 200A |
| | PANEL SCHEDULES SUBMITTED ARE SHOWN AS |
| | "A" AND "B"? |
| | 215.5 |
| | |
| | 2) NOTE: PLEASE SEE PANEL "A" INDICATES |
| | "FEED THRU LUGS" TO PANEL "B", YET RISER |
| | SHOWS PANEL "B" COMING FROM THE |
| | METER/MAIN PANEL.? |
| | 215.5 |
| | |
| | 3) NOTE: PLEASE SEE NO PANEL SCHEDULE |
| | FOR THE METER/MAIN 8 CIRCUIT SECTION WAS |
| | SUBMITTED, YET THERE ARE ITEMS BEING FED |
| | FROM THIS PANEL? |
| | 215.5,408 |
| | |
| | 4) NOTE: PLEASE SEE SERVICE IS NOW |
| | 400A'S AND THE SEC'S ARE STILL BEING |
| | SHOWN FOR THE ORIGINAL 200A SERVICE?? |
| | PLEASE INDICATE OF THE SEC'S ARE |
| | INSTALLED BY FPL, OR IF THESE ARE SEC'S |
| | INSTALLED TO A HAND HOLE WHICH WOULD |
| | FALL UNDER 310.16,240.4,310.15B6 |
| | IN THIS CASE, PLEASE SEE THE FOLLOWING |
| | NOTE. |
| | 215.5 |
| | |
| | 5) NOTE: PLEASE SEE THE GROUNDING |
| | ELECTRODE CONDUCTOR WAS NOT INCREASED |
| | FOR THE 400A SERVICE. |
| | PLEASE SEE 310.15B6, 250.66 |
| | MIN SIZE SHALL BE 1/0. |
| | |
| | 6) NOTE: PLEASE CORRELATE PANELS WITH |
| | RISER AS RISER SHOWS THESE AS 32CIR AND |
| | PANELS ARE SHOWN AS 42 CIRCUIT?? |
| | 215.5 |
| | |
| | 7) NOTE: PLEASE SEE SD IN BEDRMS WITH |
| | SLOPED CEILINGS SHALL MEET NFPA-72 BEING |
| | INSTALLED WITHIN 3' OF THE PEAK ON A |
| | SLOPED CEILING. |
| | CHAPTER 8-1 INNFPA-72 99 OR CHAPTER 11 |
| | IN NFPA-72 2002. |
| | PLEASE SEE LOCATIONS ON PLANS WHICH NEED |
| | TO BE ADJUSTED. |
| | |
| | 8) NOTE: PLEASE SEE KITCHEN COUNTER |
| | SPACE MISSING GFI RECEPTS AS REQUIRED |
| | PER 210.52C1-5, 210.8A6 |
| | |
| | 9) NOTE: PLEASE SEE RISER SHOWS A POOL |
| | PANEL , YET PLANS DO NOT?? |
| | PLEASE SHOW LOCATION. |
| | 215.5 |
| | |
| | 10) NOTE: PLEASE SEE REAR EGRESS WHERE A |
| | MIN OF ONE LT FIXTURE OF SOME TYPE WILL |
| | BE REQUIRED FOR EGRESS. |
| | 210.70, NFPA-101 7.8 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |