| 2005-04-01 00:00:00 | *********** UNSAT ************* |
| | |
| | 1)NOTE: PLEASE CORRELATE AHU'S ON |
| | ELECTRICAL PLANS WITH MECH PLANS. |
| | PLEASE SEE TWO #3 A/C SYSTEMS. PLEASE |
| | SEE THESE ARE NOT ON MECH PLANS. |
| | |
| | 2)NOTE: PLEASE SEE WHIRLPOOL TUB IS |
| | SHOWN ON PANEL SCHEDULE BUT NOT SHOWN ON |
| | PLANS. |
| | PLEASE ALSO SHOW GFI PROTECTION PER |
| | 680.71. |
| | PLEASE ALSO SEE THIS IS SHOWN AS 2-POLE |
| | 20A. ONLY A NOTE: |
| | |
| | 3)NOTE: PLEASE SEE MEANS OF EGRESS |
| | LIGHTING CONTROL AT BOTTOM OF STAIRS AT |
| | FOYER LOCATION. SWITCH IS SHOWN AS |
| | SINGLE POLE, IS THIS THE 3-WAY FOR |
| | STAIRWAY? PLEASE ALSO SEE MEANS OF |
| | EGRESS CONTROL REQUIRED FOR OUTER |
| | STAIR/PORCH AREA BY BEDRM #4. 210.70, LS |
| | 101 5-8. |
| | |
| | 4)NOTE: PLEASE SEE MISSING RECEPTS |
| | REQUIRED PER 210.52 ALONG WALL/RAIL |
| | AREAS IN STUDY AND MEZZ. PLEASE SEE RAIL |
| | AREAS ARE CONSIDERED WALL SPACE. |
| | |
| | 5)NOTE: PLEASE SEE SD FOR INSIDE MASTER |
| | BEDRM MUST BE WITHIN 3' OF PEAK OF |
| | CEILING. IF CEILING HAS A LESSTHAN 3' |
| | PEAK. SD IS STILL REQUIRED TO BE WITHIN |
| | BEDRM. |
| | NFPA-72 8-1.4, ETC. |
| | |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO TWO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF OLD SHEETS SHOULD BE |
| | SUBMITTED FOR REFERENCE ONLY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |