| Plan Review Notes For Permit 05031319 |
| Permit Number |
05031319 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-08-02 00:00:00 | NEW SHEET A-10 SUBMITTED. | | | OLD SHEET A-10 NOT SUBMITTED TO SHOW | | | BEING VOIDED. | | | | | | PLEASE SEE MISSING RECEPTS IN LIVING | | | ROOM PER 210.52. | | | PLEASE SEE SERVICE IS REVISED TO SHOW A | | | NEW 400A SERVICE. PLEASE SEEE 250.66, | | | 310.15B6 FOR MIN SIZING OF GROUNDING | | | ELECTRODE CONDUCTOR. PLEASE SEE A 1/0MIN | | | IS REQUIRED. | | | PLEASE SEE WHAT APPEAR TO BE A SINGLE | | | CAR GARAGE IS SHOWN AS A THREE CAR | | | GARAGE? | | 2005-08-01 00:00:00 | IN ELEC FOR REVIEW, NEW ELECTRICAL | | | SHEETS. |
|