| 2005-07-29 00:00:00 | BUILDING REVIEW PROVISO: |
| | 1- SHEET A-7: REVISE ROOF SHEATHING NAIL |
| | TYPE REQUIRED FOR ROOF WITH 25' MEAN |
| | ROOF HEIGHT ON ZONE 3 OF ROOF. SEE TABLE |
| | 2306.1 OF CITY AMENDMENTS TO FBC 2001. |
| | **NOTE:ZONE 3 INCLUDES CORNERS. SEE |
| | FIGURE 1606.2(C) FBC 2001. |
| | 2-SHEET A-8: A) REVISE ROOF SHEATHING |
| | NAIL FOR ZONE 3. SEE COMMENT #1 ABOVE. |
| | B) REVISE CONNECTOR G SPECIFIED FOR |
| | MASONRY WALL ON LEFT HAND SIDE BY |
| | BEDROOM #4. NEED MASONRY CONNECTOR. |
| | C) DETAIL 4/A12 BY BEDROOM #3 DOESN'T |
| | MATCH. SEE ORIENTATION OF FLOOR TRUSSES |
| | AND ROOF TRUSSES AT FIRST FLOOR. |
| | 3- STAIR SECTION ON SHEET A13: NOTE |
| | REGARDING 2X PICKETS AT 6"OC CONTRADICTS |
| | NOTE 4" SPHERENOT PASS THRU. REVISE. |
| | 4- DESIGNER OF RECORD TO SPECIFY ON |
| | PLANS ROOF TILE FASTENING AS REQ'D |
| | BY SEC. 104.2.1.1 CITY AMENDMENTS TO FBC |
| | 5- PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR: A) ALL MULLIONS INCLUDING |
| | ONE SPECIFIED FOR 12'-0" SLIDING DOORS. |
| | B) 8'-0" GARAGE DOORS THAT MEET THE |
| | DESIGN PRESSURES CALCULATED ON PLANS. |
| | C) TRUSS CONNECTORS SPECIFIED ON PLANS. |