2005-07-29 00:00:00BUILDING REVIEW PROVISO:
 1- SHEET A-7: REVISE ROOF SHEATHING NAIL
 TYPE REQUIRED FOR ROOF WITH 25' MEAN
 ROOF HEIGHT ON ZONE 3 OF ROOF. SEE TABLE
 2306.1 OF CITY AMENDMENTS TO FBC 2001.
 **NOTE:ZONE 3 INCLUDES CORNERS. SEE
 FIGURE 1606.2(C) FBC 2001.
 2-SHEET A-8: A) REVISE ROOF SHEATHING
 NAIL FOR ZONE 3. SEE COMMENT #1 ABOVE.
 B) REVISE CONNECTOR G SPECIFIED FOR
 MASONRY WALL ON LEFT HAND SIDE BY
 BEDROOM #4. NEED MASONRY CONNECTOR.
 C) DETAIL 4/A12 BY BEDROOM #3 DOESN'T
 MATCH. SEE ORIENTATION OF FLOOR TRUSSES
 AND ROOF TRUSSES AT FIRST FLOOR.
 3- STAIR SECTION ON SHEET A13: NOTE
 REGARDING 2X PICKETS AT 6"OC CONTRADICTS
 NOTE 4" SPHERENOT PASS THRU. REVISE.
 4- DESIGNER OF RECORD TO SPECIFY ON
 PLANS ROOF TILE FASTENING AS REQ'D
 BY SEC. 104.2.1.1 CITY AMENDMENTS TO FBC
 5- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR: A) ALL MULLIONS INCLUDING
 ONE SPECIFIED FOR 12'-0" SLIDING DOORS.
 B) 8'-0" GARAGE DOORS THAT MEET THE
 DESIGN PRESSURES CALCULATED ON PLANS.
 C) TRUSS CONNECTORS SPECIFIED ON PLANS.