Plan Review Notes
Plan Review Notes For Permit 05031319
Permit Number 05031319
Review Stop B
Sequence Number 1
Notes
Date Text
2005-04-26 00:00:00BUILDING REVIEW CHECKLIST:
 1- SHEET A-2: A) FOUNDATION NOTE #1.
 NEED 6 MIL, NOT 4 MIL VAPOR BARRIER.
 SEC. 1909.2 FBC 2001.
  
 B) REVISE FOUNDATION NOTE #2. SEE
 CHAPTER 19 FBC 2001 FOR PROPER ACI
 REFERENCE.
  
 C) THERE IS SOME OVERLAPPING INFORMATION
 THAT DOESN'T ALLOW NOTES TO BE LEGIBLE.
 REVISE AS REQUIRED.
  
 2- SHEET A-3: A) DESIGN PARAMETERS:
 WHERE IS THE BASIC VELOCITY PRESSURE
 TAKEN FROM? IT IS NOT SHOWN IN CHAPTER
 16 FBC 2001.
  
 B) REVISE HANDRAIL HEIGHT. SEE SECTION
 1007.5.1 FBC 2001 (EXEMPTION #3).
  
 C) PROVIDE ATTIC ACCESS AT MASTER SUITE
 WING AND AT BEDROOM #2 WING. AS REQUIRED
 BY SEC. 2309.6 FBC 2001.
  
 3- SHEET A-4: A) REVISE HANDRAIL HEIGHT.
 SEE SEC. 1007.5.1 (EXEMPTION #3) FBC.
  
 B) THERE IS SOME INFORMATION THAT IS
 OVERLAPPING. REVISE AS REQUIRED TO MAKE
 IT LEGIBLE.
  
 4- SHEET A-10: PROVIDE SMOKE DETECTOR ON
 FIRST FLOOR IN CLOSE PROXIMITY TO THE
 STAIRWAY LEADING TO THE 2ND FLOOR. SMOKE
 DETECTOR IS SHOWN ABOVE THE STAIRS. THIS
 IS A DOUBLE HEIGHT CEILING AND THERE IS
 ALREADY A SMOKE DETECTOR SHOWN ON SHEET
 A-11. REVISE AS REQUIRED TO COMPLY WITH
 SEC. 905.2.2 FBC 2001
  
 5- SHEET A-5: FRONT ELEVATION CALLS FOR
 FLAT CEMENT TILE. PRODUCT APPROVAL
 SUBMITTED IS FOR "S" TILE. REVISE.
  
 6- SHEET A-7: A) REVISE ROOF SHEATHING
 NAIL TYPE REQUIRED FOR ROOF WITH 25'
 MEAN ROOF HEIGHT ON ZONE 3 OF ROOF. SEE
 TABLE 2306.1 OF CITY AMENDMENTS TO FBC.
  
 B) REVISE/UPDATE TRUSS ANCHOR SCHEDULE.
 SEE LATEST CATALOGUE. PROVIDE COMPLETE
 ENGINEERING CALCULATIONS FOR NAIL TYPE
 AND NUMBER THAT DIFFERS FROM THOSE
 TESTED AND PUBLISHED BY MANUFACTURER.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 7- SHEET A-8: A) REVISE ROOF SHEATHING
 NAIL TYPE. SEE TABLE 2306.1 CITY
 AMENDMENTS TO FBC 2001 FOR ZONE 3 ON
 ROOF OVER 25'-0" MEAN ROOF HEIGHT.
  
 B) REVISE CONNECTOR G SPECIFIED FOR
 MASONRY WALL ON LEFT HAND SIDE. NEED
 WOOD TO MASONRY CONNECTOR.
  
 C) DETAIL 2/A-13 SHOWN ON RIGHT HAND
 SIDE DOESN'T APPLY. REVISE AS REQUIRED.
  
 8- STAIR SECTION ON SHEET A-13 DOESN'T
 MATCH STAIRS SHOWN ON PLANS. REVISE AS
 REQUIRED. AND PROVIDE COMPLETE
 INFORMATION INCLUDING FIREBLOCKING AS
 REQUIRED BY SEC. 2305.2 FBC 2001.
  
 9- GARAGE DOOR: PROVIDE PRODUCT APPROVAL
 FOR 8'-0" WIDE GARAGE DOOR THAT MEETS
 THE DESIGN PRESSURES SHOWN ON PLANS.
  
 10-SPECIFY ROOF TILE FASTENING. IT'S THE
 DESIGNER OF RECORD RESPONSIBILITY NOT HE
 CONTRACTOR.. SEE SEC. 104.2.1.1 OF CITY
 AMENDMENTS TO FBC 2001.
  
 11- PROVIDE COMPLETE DETAIL/SPECS FOR
 CEILING INSTALLATION AT ENTRY AND REAR
 PORCHES. SEE ASTM C926 AND ASTM C1063.
 SPECIFY ALL FASTENERS AND SPACING.
  
 12- OWES $934.91 FOR UPDATED VALUATION
 AND RADON FEES.
  
 13- SPECIFY MULLION SIZE AND ANCHORS TO
 BE USED BETWEEN 12'-0" WIDE SLIDING
 GLASS DOORS AND TRANSOM ABOVE TO VERIFY
 STRUCTURAL ADEQUACY OF MULLION SELECTED.
  
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 14- PROVIDE PRODUCT APPROVAL FOR SINGLE
 FRENCH DOORS AS SHOWN ON PLANS.
  
 15- PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOORS WITH IMPACT GLAZING AS SHOWN ON
 PLAN AND ELEVATIONS.
  
 PLEASE DON'T STAPLE PRODUCT APPROVALS TO
 PLANS AND IF YOU HAVE ANY QUESTIONS,
 PLEASE CALL JULIO GOMEZ AT (561)805-6712