Plan Review Notes
Plan Review Notes For Permit 05031311
Permit Number 05031311
Review Stop P
Sequence Number 2
Notes
Date Text
2005-06-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 424 SWIMMING POOLS
 FBC-2001 CHAPTER 1
  
 A. COMMENTS FROM PREVIOUS REVIEW NOT
 ADDRESSED:
 1) PLANS SHALL BE ROUTED TO THE PALM
 BEACH COUNTY HEALTH DEPT. FOR REVIEW AND
 STAMPING PRIOR TO RESUBMITTING FOR
 REVIEW BY CITY WPB. SECTION 101.4.7.
 2) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 3) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUF. CUT SHEETS SUBMITTAL).
 4) A SKETCH OF ANY PROPOSED HEATER
 INSTALLATION INCLUDING VALVES,
 THERMOMETER, PIPE SIZES, AND MATERIAL
 SPECIFICATIONS SHALL BE INCLUDED IN THE
 APPLICATION FOR PERMIT PRIOR TO
 INSTALLATION. SECTION 424.1.6.5.14
 5) OVERFLOW FROM THE POOL SHALL DRAIN TO
 STORM, AND WASTE FROM THE FILTER SHALL
 DRAIN TO SANITARY. (INDICATE ON PLANS).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]