| Plan Review Notes For Permit 05031311 |
| Permit Number |
05031311 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-06-15 00:00:00 | ********** UNSAT 2ND REVIEW ******** | | | | | | PLEASE SEE NOTES FROM PREVIOUS REVIEW. | | | | | | 1)NOTE: PLEASE SEE PLANS AND PERMIT | | | APPLICATION INCLUDE A HEAT PUMP. THIS IS | | | ALSO SHOWN ON A SUBMITTED 8 1/2 X 11 | | | SUBMITTED AND ATTACHED TO ELECTRICAL | | | SHEET. PLEASE SEE THIS HEAT PUMP,WIRING | | | ETC IS NOT INDICATED ON ELECTRICAL PLANS | | | OR EQUIPMENT SCHEDULE?? | | | PLEASE SEE THIS IS NOT INCLUDED IN LOAD | | | CALCS FOR POOL PANEL OR FEED TO NEW POOL | | | PANEL. | | | | | | 2)NOTE: PLEASE INCLUDE MANUFACTURE | | | CUT/SPEC SHEETS FOR NEW HEAT PUMP | | | SHOWING LISTING FROM A NRTL. | | | | | | 3)NOTE: PLEASE REMOVE ANY AND ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW | | | REVISED SHEETS INTO COMPLETE SETS FOR | | | REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|