Plan Review Notes For Permit 05031298
Permit Number 05031298
Review Stop B
Sequence Number 1
Notes
Date Text
2005-04-29 00:00:00DENIED
  
 1) THE CALCULATIONS ARE REQUIRED TO HAVE
 THE WET SIGNATURE, DATE AND EMBOSSED
 SEAL OF THE P.E. THE CALCS. THAT WERE
 SUBMITTED HAVE COPIED SIGNATURES.
  
 2) PLEASE CLARIFY THE 1-5/16" ON THE
 CALCULATIONS.
  
 3) SUBMIT CALCULATIONS FOR THE DESIGN
 LOADS OF THE SLOPED GLAZING AS REQUIRED
 BY FBC 2405.3.2.
  
 4) DRAWING 1 OF 4 INDICATES 3/8"
 POLYCARBONATE, 2 OF 4 HAS 9/16"
 H.S.LAMINATE. PLEASE SHOW 1-5/16"
 INSULATING GLASS IN ALL THE DRAWINGS FOR
 CLARITY.
  
 5) GENERAL NOTE #15 STATES THAT WOOD
 CURB AND ROOF STRUCTURE ARE TO BE
 REVIEWED BY THE STRUCTURAL PLANS
 EXAMINER. SUBMIT AN ANALYSIS OF THE
 SUPPORTING ROOF STRUCTURE BY A FLORIDA
 P.E. INDICATING THAT IT IS CAPABLE OF
 SUPPORTING THE ADDITIONAL DEAD LOADS AND
 LIVE LOADS IMPOSED BY THE REGLAZED
 SKYLIGHTS.
  