| Plan Review Notes For Permit 05031272 |
| Permit Number |
05031272 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-05-03 00:00:00 | ********** PROVISO/REVISION ********** | | | | | | PLEASE SEE NOTE'S #2 AND #5 FROM | | | PREVIOUS REVIEW. | | | | | | 1)NOTE: NOTE #2 , PLEASE SEE ORIGINAL | | | PLANS RISER SHOWED 2-#6'S, 1-#8 AND | | | 1-#10 FOR POOL SUB PANEL AND PANEL | | | SCHEDULE "B" SHOWED 3-#6'S? | | | PLEASE SEE NOW AN ADDITIONAL PHASE/HOT | | | CONDUCTOR HAS BEEN ADDED TO FEED | | | PANEL"C". PLEASE SEE RISER NOW SHOWS | | | 3-HOTS, 1-NEUTRAL AND 1-EQUIP GRND.??? | | | | | | PLEASE ADJUST TO ACTUAL INSTALLATION. | | | | | | 2)NOTE: NOTE #5, ORIG PLANS SHOWWS 4.5KW | | | FOR COND UNITS, WITH 40A OCP AND #10 | | | AWG. PLEASE SEE 4.5KW @240= 18.75A'S. | | | IT WAS REQUESTED TO VERIFY OCP FOR LOAD | | | AND AWG SHOWN, HOWEVER, 3-#6'S WERE | | | ADDED TO PANEL SCHEDULES INSTEAD.??? | | | | | | PLEASE ADJUST TO ACTUAL INSTALLATION. | | | | | | | | | | | | ***PLEASE MAKE THE ABOVE CORRECTIONS AND | | | SUBMIT WITH ANY OTHER POSSIBLE REVISIONS | | | BEFORE ROUGH ELECTRICAL INSPECTION IS | | | CALLED IN. | | | | | | IF THERE ARE ANY QUESTIONS, ONCE AGAIN, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|