| Plan Review Notes For Permit 05031272 |
| Permit Number |
05031272 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-03-28 00:00:00 | *** UNSAT *** | | | | | | 1)NOTE: PLEASE CORRELATE RISER WITH | | | PLANS. PLANS INDICATE TWO POOL PANELS? | | | ONE AT SERVICE LOCATION AND ONE AT POOL | | | EQUIPMENT LOCATION. (MISPRINT). | | | | | | 2)NOTE: PLEASE CORRELATE WIRING FOR | | | SUB-PANEL "C", SHOWS 3-#6'S ON PANEL | | | SCHEDULE"B" , YET RISER SHOWS 2-#6'S AND | | | #8? | | | | | | 3)NOTE: PLEASE SEE MISSING RECETP PER | | | 210.52 IN BEDRM #3. | | | | | | 4)NOTE: PLEASE SEE COOKTOP SHOWS 6KW | | | LOAD ON 1-POLE 20A BRKR. | | | 215.5,310.16,240.4 TEC. | | | | | | 5)NOTE: PLEASE VERIFY LOAD/OCP AND AWG | | | FOR BOTH A/C CU'S. | | | 4.5KW ON 40A OCP AND #10 AWG. | | | 240.4,310.16 | | | | | | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO TWO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|