Plan Review Notes
Plan Review Notes For Permit 05031272
Permit Number 05031272
Review Stop E
Sequence Number 1
Notes
Date Text
2005-03-28 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE CORRELATE RISER WITH
 PLANS. PLANS INDICATE TWO POOL PANELS?
 ONE AT SERVICE LOCATION AND ONE AT POOL
 EQUIPMENT LOCATION. (MISPRINT).
  
 2)NOTE: PLEASE CORRELATE WIRING FOR
 SUB-PANEL "C", SHOWS 3-#6'S ON PANEL
 SCHEDULE"B" , YET RISER SHOWS 2-#6'S AND
 #8?
  
 3)NOTE: PLEASE SEE MISSING RECETP PER
 210.52 IN BEDRM #3.
  
 4)NOTE: PLEASE SEE COOKTOP SHOWS 6KW
 LOAD ON 1-POLE 20A BRKR.
 215.5,310.16,240.4 TEC.
  
 5)NOTE: PLEASE VERIFY LOAD/OCP AND AWG
 FOR BOTH A/C CU'S.
 4.5KW ON 40A OCP AND #10 AWG.
 240.4,310.16
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  