| 2005-08-10 00:00:00 | BUILDING REVIEW THIRD CHECKLIST: |
| | 1- ENERGY CALCULATIONS ARE STILL WRONG. |
| | (SEE COPY OF FLORIDA STATUTE |
| | 553.80(2)(B)REGARDING DESIGN |
| | PROFESSIONAL DOCUMENTS).OVERHANG LENGTH |
| | AND HEIGHT ARE STILL WRONG. SEE SEC. |
| | 601.2 OF CHAPTER 13 FBC. |
| | **NOTE: ARCHITECT ALSO NEEDS TO IMPRESS |
| | HIS SEAL IN ALL DOCUMENTS THAT ARE |
| | SUBMITTTED FOR PUBLIC RECORDS AS REQ'D |
| | BY CHAPTER 481 FLORIDA STATUTES. |
| | |
| | 2- PROVIDE FLORIDA OR APPLY FOR LOCAL |
| | PRODUCT APPROVAL FOR: |
| | A) POCKET SLIDING GLASS DOORS AS SHOWN |
| | ON PLANS. |
| | |
| | B) BAY WINDOW FOR BREAKFAST AREA. |
| | PRODUCT APPROVAL SUBMITTED DOESN'T COVER |
| | SIZE SPECIFIED ON PLANS FOR BREAKFAST |
| | AREA. |
| | |
| | C) EYEBROW WINDOW ASSEMBLY AS SHOWN ON |
| | LIVING ROOM. |
| | |
| | D) CASEMENT WINDOWS. NEED DADE COUNTY |
| | NOA REPORT THAT MATCHES ONE SUBMITTED |
| | FOR FLORIDA PRODUCT APPROVAL. |
| | |
| | E) ALL TRUSS CONNECTORS SPECIFIED ON |
| | PLANS. |
| | |
| | 3- SIZE OF LIVING ROOM WINDOW SPECIFIED |
| | ON SHEET A1 DOESN'T MATCH SIZE SHOWN ON |
| | THE REAR ELEVATION. REVISE/CLARIFYAS |
| | REQUIRED TO VERIFY PRODUCT APPROVAL |
| | COMPLIANCE. |
| | |
| | 4- SHEET A1: A) NOTE ON GARAGE ATTIC |
| | STORAGE IS WRONG. IT SHOULD BE 30PSF |
| | ATTIC LIVE LOAD NOT 30PSF DEAD LOAD. |
| | REVISE AS REQ'D. TABLE 1604.1 FBC 2001. |
| | |
| | B) WINDOW GLAZING NOTE: REFERENCED SEC. |
| | #3513 DOESN'T APPLY. REVISE AS REQUIRED. |
| | |
| | 5- SLIDING GLASS DOOR POCKET DETAIL. |
| | PREVIOUS CHECKLIST REQUIRED TO SPECIFY |
| | 7/8" MIN. STUCCO THICKNESS AS REQUIRED |
| | BY ASTM C-926. DETAIL WAS REVISED TO |
| | HAVE 7/8" CDX PLYWOOD INSTEAD. REVISE AS |
| | REQUIRED. |
| | |