| 2005-07-26 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | |
| | 1- NEED RE-RECORDED NOTICE OF |
| | COMMENCEMENT. IT EXPIRES AFTER 90 DAYS |
| | IF WORK IS NOT STARTED. |
| | |
| | 2- SHEET A3:A) ROOF LOADS CHARTWAS |
| | NOT REVISED. IT DOESN'T INCLUDE THE |
| | 30PSF ATTIC LIVE LOAD FOR AREAS WITH |
| | STORAGE AND THE 10PSF ATTIC LIVE LOAD |
| | FOR NON-STORAGE AREAS. SOME NOTES |
| | PERTAINING TO THIS LOADS WERE ADDED ON |
| | SAME PAGE, BUT, THEY DON'T MATCH ROOF |
| | LOAD CHART. |
| | |
| | B) REVISE NOTE ABOVE BREAKFAST AREA. |
| | WINDOW USED IS NOT BUTT GLAZING. |
| | |
| | C) ROOF TILE ANCHORAGE IS BASED ON THE |
| | UPLIFT MOMENT. PROVIDE MOMENT CALCS TO |
| | VERIFY THAT ONLY ONE SCREW WILL RESIST |
| | THE UPLIFT MOMENT. SEC. 104.2.1.1AND |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | (ACCORDING TO THE FRSA MOMENT UPLIFT |
| | CHART ONE SCREW IS NOT ENOUGH). |
| | |
| | 3- SHEET A1: REVISE NOTE ABOVE GARAGE |
| | AREA. IT IS ATTIC LIVE LOAD, NOT ATTIC |
| | DEAD LOAD OF 30PSF FOR STORAGE. |
| | SEE TABLE 1604.1 FBC 2001. |
| | |
| | 4- SHEET A2: THERE IS NOT FOOTING SHOWN |
| | FOR CONCRETE COLUMN IN COVERED PORCH BY |
| | THE FAMILY ROOM AREA. |
| | |
| | 5- REAR ELEVATION ON SHEET A6 SHOWS |
| | WINDOS AT MASTER BEDROOM, LIVING ROOM |
| | AND BREAKFAST AREA AS BUTT GLAZING |
| | SYSTEM. REVISE TO MATCH FLOOR PLAN. |
| | |
| | 6- CLEARLY SPECIFY WINDOW MULLIONS TYPE, |
| | SIZE AND ANCHORS TO BE USED ON |
| | ASSEMBLIES AT MASTER BEDROOM,LIVING ROOM |
| | AND BREAKFAST AREA. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. AND PROVIDE |
| | PERTAINING FLORIDA OR LOCAL PRODUCT |
| | APPROVAL. |
| | |
| | 7- SHEET A7 BEARING WALL DETAIL: PROVIDE |
| | SPECIFIC TYPE OF HURRICANE CLIPS. SEC. |
| | 104.2.1 FBC 2001. |
| | |
| | 8- PROVIDE FLORIDA PRODUCT APPROVAL OR |
| | APPLY FOR LOCAL PRODUCT APPROVAL FOR: |
| | A) ENTRY DOORS (DADE COUNTY NOA ALONE IS |
| | NOT AUTOMATICALLY A FL. PROD. APPROVAL). |
| | B) POCKET SLIDING GLASS DOORS (DADE |
| | COUNTY NOA ALONE IS NOT A FLORIDA |
| | PRODUCT APPROVAL). |
| | C) WINDOW MULLIONS AS SHOWN ON PLANS. |
| | D) ALL TRUSS ANCHORS SPECIFIED ON PLANS. |
| | E) CASEMENT WINDOWS. |
| | F) BAY WINDOWS SHOWN ON MASTER BEDROOM, |
| | LIVING AND BREAKFAST AREA. |
| | |
| | 9- OWES $4247.67. PERMIT FEES NOT PAID. |
| | |
| | 10- ENERGY CALCULATIONS: A) WHEN |
| | PREPARED BY ARCHITECT MUST BE SIGNED, |
| | SEALED AND DATED AS REQ'D BY CHAPTER 481 |
| | FL STATUTE |
| | |
| | B) OVERHANG LENGTH AND HEIGHT ARE NOT |
| | DONE CORRECTLY. SEE SEC. 601.2.A.3 OF |
| | CHAPTER 13 FBC 2001 FOR PROPER WAY OF |
| | CALCULATING THESE DIMENSIONS. |
| | |
| | *REMAINDER: OWNER/AGENT TO SIGN AND DATE |
| | FORM AS WELL. |
| | |