2005-07-26 00:00:00BUILDING REVIEW CHECKLIST:
  
 1- NEED RE-RECORDED NOTICE OF
 COMMENCEMENT. IT EXPIRES AFTER 90 DAYS
 IF WORK IS NOT STARTED.
  
 2- SHEET A3:A) ROOF LOADS CHARTWAS
 NOT REVISED. IT DOESN'T INCLUDE THE
 30PSF ATTIC LIVE LOAD FOR AREAS WITH
 STORAGE AND THE 10PSF ATTIC LIVE LOAD
 FOR NON-STORAGE AREAS. SOME NOTES
 PERTAINING TO THIS LOADS WERE ADDED ON
 SAME PAGE, BUT, THEY DON'T MATCH ROOF
 LOAD CHART.
  
 B) REVISE NOTE ABOVE BREAKFAST AREA.
 WINDOW USED IS NOT BUTT GLAZING.
  
 C) ROOF TILE ANCHORAGE IS BASED ON THE
 UPLIFT MOMENT. PROVIDE MOMENT CALCS TO
 VERIFY THAT ONLY ONE SCREW WILL RESIST
 THE UPLIFT MOMENT. SEC. 104.2.1.1AND
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 (ACCORDING TO THE FRSA MOMENT UPLIFT
 CHART ONE SCREW IS NOT ENOUGH).
  
 3- SHEET A1: REVISE NOTE ABOVE GARAGE
 AREA. IT IS ATTIC LIVE LOAD, NOT ATTIC
 DEAD LOAD OF 30PSF FOR STORAGE.
 SEE TABLE 1604.1 FBC 2001.
  
 4- SHEET A2: THERE IS NOT FOOTING SHOWN
 FOR CONCRETE COLUMN IN COVERED PORCH BY
 THE FAMILY ROOM AREA.
  
 5- REAR ELEVATION ON SHEET A6 SHOWS
 WINDOS AT MASTER BEDROOM, LIVING ROOM
 AND BREAKFAST AREA AS BUTT GLAZING
 SYSTEM. REVISE TO MATCH FLOOR PLAN.
  
 6- CLEARLY SPECIFY WINDOW MULLIONS TYPE,
 SIZE AND ANCHORS TO BE USED ON
 ASSEMBLIES AT MASTER BEDROOM,LIVING ROOM
 AND BREAKFAST AREA. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001. AND PROVIDE
 PERTAINING FLORIDA OR LOCAL PRODUCT
 APPROVAL.
  
 7- SHEET A7 BEARING WALL DETAIL: PROVIDE
 SPECIFIC TYPE OF HURRICANE CLIPS. SEC.
 104.2.1 FBC 2001.
  
 8- PROVIDE FLORIDA PRODUCT APPROVAL OR
 APPLY FOR LOCAL PRODUCT APPROVAL FOR:
 A) ENTRY DOORS (DADE COUNTY NOA ALONE IS
 NOT AUTOMATICALLY A FL. PROD. APPROVAL).
 B) POCKET SLIDING GLASS DOORS (DADE
 COUNTY NOA ALONE IS NOT A FLORIDA
 PRODUCT APPROVAL).
 C) WINDOW MULLIONS AS SHOWN ON PLANS.
 D) ALL TRUSS ANCHORS SPECIFIED ON PLANS.
 E) CASEMENT WINDOWS.
 F) BAY WINDOWS SHOWN ON MASTER BEDROOM,
 LIVING AND BREAKFAST AREA.
  
 9- OWES $4247.67. PERMIT FEES NOT PAID.
  
 10- ENERGY CALCULATIONS: A) WHEN
 PREPARED BY ARCHITECT MUST BE SIGNED,
 SEALED AND DATED AS REQ'D BY CHAPTER 481
 FL STATUTE
  
 B) OVERHANG LENGTH AND HEIGHT ARE NOT
 DONE CORRECTLY. SEE SEC. 601.2.A.3 OF
 CHAPTER 13 FBC 2001 FOR PROPER WAY OF
 CALCULATING THESE DIMENSIONS.
  
 *REMAINDER: OWNER/AGENT TO SIGN AND DATE
 FORM AS WELL.
  