Plan Review Notes
Plan Review Notes For Permit 05031185
Permit Number 05031185
Review Stop P
Sequence Number 8
Notes
Date Text
2008-02-06 19:02:46REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 ****FROM PREVIOUS REVISION REVIEW:
  
 ******FROM PREVIOUS REVISION REVIEW:
  
 NOTE: MOST OF THESE SHEETS SUBMITTED ARE THE EXACT SAME
 SHEETS SUBMITTED AND DENIED ON THE LAST REVISION
 SUBMITTAL. NO CHANGES.
  
  
 1. SHTS P-1, P-4, P-5, P-7, P-8, P-9 & P-10 REVISIONS
 ARE INDICATED AS REVISIONS 1 & 2. REVISIONS 1 & 2 ARE
 ALREADY SUBMITTED. THE NEW REVISIONS NUMBERS SHALL STAY
 IN SEQUENCE ALREADY ESTABLISHED ON THESE PLANS AND, FOR
 EXAMPLE, SHT P-1 HAS REVISIONS 1 THRU 5, SO THE NEXT
 REVISIONS SHALL BE 6 & 7. PLEASE INDICATE THE CORRECT
 REVISION NUMBERS ON EACH REVISED SHEET ACCORDING TO
 PREVIOUS REVISIONS. SECTION 106.1.3.
 ****RESPONSE NOTED, BUT P-1 STILL SHOWS A 2ND #2
 REVISION AND NEW REVISION #5 PREVIOUSLY DATED 03-07-05
 ON THE PLANS SIGNED, SEALED, AND DATED 3-11-05 HAS BEEN
 CHANGED TO 07-24-06. PLEASE CLARIFY. COMMENT HAS NOT
 BEEN ADDRESSED. ALSO PLEASE TURN OFF ALL PREVIOUSLY
 APPROVED REVISION CLOUDS AND REVISION NUMBERS ON THE
 PLAN. THIS WILL HELP EXPEDITE FUTURE REVISIONS AND
 ENABLE THE PLAN REVIEWERS TO REVIEW REVISIONS IN A
 TIMELY MANNER.--SHT P-4 REVISION #2 HAD AN ORIGINAL
 REVISION DATE 08-27-04, BUT THE NEW SHT P-4 SHOWS THE
 REVISION DATE 02-25-04 FOR THE SAME REVISION. PLEASE
 CLARIFY.
 ******RESPONSE NOTED, BUT THIS IS THE SAME SHEETS WITH
 THE SAME MARKINGS FROM THE PREVIOUS REVISION SUBMITTAL.
 NO CHANGES COMMENTS NOT ADDRESSED.
  
 2. OK
 ******SAME SHEET PREVIOUSLY APPROVED. NOT REQUIRED.
 3. OK
 ******SAME SHEET PREVIOUSLY APPROVED. NOT REQUIRED.
  
 4. OK
 5. OK
  
 ************NEW COMMENTS************
  
 1B. SHTS P-2 & P-3 REVISION #4 HAS BEEN CHANGED, THE
 ORIGINAL REVISION IS DATED 07-06-05, BUT THE NEW SHTS
 SHOWS REVISION #4 DATED 07-24-06. ALSO REVISIONS
 INDICATED ON 07-24-06 HAS NOT BEEN FOUND OR APPROVED.
 SINCE THERE WAS ALREADY A REVISION #4 SHOWN ON THE
 SIGNED, SEALED SHEETS DATED 07-06-05, ALL REVISIONS
 AFTER THAT DATE SHALL HAVE THEIR OWN REVISION NUMBER.
 THE REVISIONS SHALL BE SEQUENTIAL TO TRACK ALL
 REVISIONS. SECTION 106.3.1. (NOTE: NO REVISION # 4
 REVISIONS ARE INDICATED ON THE SHEETS).
 ******NO RESPONSE, NOT ADDRESSED.
  
 2B. SHT P-5 INDICATES REVISION #3. REVISION #3 FOUND BY
 THE DIRECTIONAL COMPASS WITH NO CLOUD AND NO APPARENT
 CHANGE/REVISION. PLEASE CLARIFY. SECTION 106.1.1.
 ******NO RESPONSE, NOT ADDRESSED.
  
 3B. SHT P-6 REVISION #4 DATE HAS BEEN CHANGED FROM
 07-06-05 TO 07-24-06. ALSO REVISIONS INDICATED ON
 07-24-06 HAS NOT BEEN FOUND OR APPROVED.--REVISIONS
 5 & 6 FROM SET OF PLANS SIGNED, SEALED & DATED 09-23-05
 HAVE BEEN DELETED FROM THE REVISION INDEX. SINCE THERE
 ARE MANY REVISIONS ATTRIBUTED TO REVISION #6, WHY HAS
 REVISION #6 BEEN DELETED FROM THE REVISION INDEX?--
 NO NEW REVISION NUMBER #7 IS INDICATED ON THE NEW SHT
 P-6. PLEASE CLOUD AND NUMBER NEW REVISIONS AND TURN OFF
 ALL PREVIOUS CLOUDS OF REVISIONS APPROVED PRIOR TO THIS
 REVISION AS YOU HAVE FOR REVISIONS #5 & #6. (REVISIONS
 1, 2, 3 CLOUDS STILL SHOWN ON PLANS).
 ******NO RESPONSE, NOT ADDRESSED.
  
 4B. OK
 5B. OK
 6B. OK
 7B. OK
  
 8B. SHT P-8 REVISION #4 ON THE STAMPED PLANS SIGNED,
 SEALED & DATED 07-06-05 HAS BEEN CHANGED TO 07-24-06.
 SINCE THE REVISIONS #4 HAS ITS OWN REVISION, A NEW
 REVISION NUMBER IS REQUIRED FOR ALL NEW REVISIONS. ALSO
 REVISIONS INDICATED ON 07-24-06 HAS NOT BEEN FOUND OR
 APPROVED.
 ******NO RESPONSE, NOT ADDRESSED.
  
 9B. OK
  
 10B. SHT P-9 GAS SYSTEM #1 PER TABLE 402.4(6) MINIMUM
 SIZE IS 2-1/2". 2" IS SHOWN.--SUBMIT MANUF
 SPECIFICATION SHEETS FOR THE WATER HEATERS TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA-54, NFPA-58 AND FBC-2004
 FUEL GAS SEC. 402.2.
 ******PIPE SIZES ADDRESSED, BUT MANUF. SPECIFICATION
 SHEETS NOT SUBMITTED.
  
 11B. OK
  
 12B. SHT P-10 REVISION #3 WAS DATED 07-06-05 AND HAS
 NOT BEEN CHANGED TO 07-24-06. THIS REVISION HAS NOT
 BEEN FOUND OR APPROVED. NEW REVISIONS SHALL HAVE NEW
 REVISION NUMBERS. EXISTING REVISIONS SHALL REMAIN AS
 APPROVED FOR CONFORMITY TO RECORD RETENTION.--
 REVISION #4 WAS DATED 09-16-05 AND NOW CHANGED TO DATE
 02-16-07. REVISION HAS NOT BEEN APPROVED. NEW REVISIONS
 SHALL HAVE NEW REVISION NUMBERS. TURN OFF ALL
 PREVIOUSLY APPROVED REVISION CLOUDS AND REVISION
 NUMBERS ON THE PLANS TO HELP EXPEDITE THE REVISION
 REVIEW. LEAVE REVISION INDEX NUMBER HISTORY CURRENT
 FROM FIRST REVISION THRU TO THE NEWEST REVISION.
 ******NO RESPONSE, NOT ADDRESSED.
  
 13B. OK
  
 14B. SHT P-12 GAS WATER HEATERS HAVE CHANGED. SUBMIT
 MANUF. SPECIFICATIONS FOR GAS APPROVAL. SECTION 402.2.
 ******NO RESPONSE, NOT ADDRESSED.
  
 15B. OK
  
 **********NEW COMMENTS**********
  
 1C. SHT P-7 SANT. RISERS S/1A, S/3 & S/7 VENT STACKS
 SHALL CONNECT TO THE BASE OF THE SANT. STACK. SECTION
 903.4.
  
 2C. SHT P-12 SHOWS FRESH AIR VENTS DELETED FOR THE
 WATER HEATERS. PLEASE SUBMIT CALCULATIONS FOR
 COMBUSTION AIR. ( SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  