Plan Review Notes
Plan Review Notes For Permit 05031185
Permit Number 05031185
Review Stop B
Sequence Number 8
Notes
Date Text
2008-07-12 13:29:45"TEMPORARY FAIL" STATUS:FORMAL RESUBMITTAL IS NOT
 NECESSARY HOWEVER THE REVIEW WILL REMAIN IN TEMPORARY
 FAIL STATUS UNTIL COMMENT # 4 IS ADDRESSED AND THE
 ADDITIONAL PALM BEACH COUNTY IMPACT FEES ARE PAID FOR
 THE INCREASE IN FLOOR AREA.
  
  
 BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 5TH REVIEW OF REVISION FOR INCREASE IN NUMBER OF
 STORIES FROM 5 TO 8 STORIES.
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS ARE NUMBERED AS
 PER THE BUILDING PLAN REVIEW OF 5/24/08:
  
  
 3)IMPACT FEES. COMMENT RESPONSE, STATING THAT THE
 OWNER WILL PAY IMPACT FEES, IS NOTED AND THIS OFFICE
 WILL DROP THIS COMMENT ONCE THE FEES ARE PAID. PREVIOUS
 COMMENT (RE-STATED HERE FOR INFORMATION):THE PROPOSED
 INCREASE IN BUILDING AREA WILL INCREASE THE IMPACT FEES
 DUE.THE PLANS SHALL BE TAKEN TO PALM BEACH COUNTY
 BUILDING DEPARTMENT FOR CALCULATION OF THE ADDITIONAL
 IMPACT FEES. THEY SHALL BE STAMPED AT THAT OFFICE AND A
 COPY OF THE PAID RECEIPT SUBMITTED TO THE CITY OF WEST
 PALM BEACH DEPT OF CONSTRUCTION SERVICES BEFORE THE
 REVISED PLANS CAN BE STAMPED.
  
  
 THE FOLLOWING COMMENT CAN BE ADDRESSED WITHOUT FORMAL
 SUBMITTAL OF PLANS BUT IT MUST BE ADDRESSED BEFORE THE
 PLAN REVIEW CAN BE "PASSED":
  
 4) FBC 709.2.4COLUMN FIRE RESISTANCE RATING.SHEET
 S-9 HAS BEEN REVISED TO SHOW COLUMN TC-5 WITH ADEQUATE
 DIMENSIONS TO ACHIEVE THE REQUIRED 3 HOUR FIRE
 RESISTANCE RATING.HOWEVER THE SHEET WAS CORRECTED
 USING CORRECTION FLUID ("WITE-OUT").IT IS PERMISSIBLE
 FOR PLANS FOR PERMITTING PURPOSES TO BE REVISED BY THE
 DESIGNER OF RECORD USING HAND WRITTEN CHANGES PROVIDED
 THE DESIGNER OF RECORD SIGNS AND DATES NEXT TO EACH
 CHANGE, HOWEVER UNDER NO CIRCUMSTANCE CAN CORRECTION
 FLUID BE USED FOR PLAN REVISION PURPOSES.ONCE THE
 PLANS ARE STAMPED THERE WOULD BE NO WAY FOR THE
 INSPECTOR TO KNOW IF THE CORRECTION FLUID WAS APPLIED
 BEFORE OR AFTER STAMPING ("PASSING") OF THE PLANS.THE
 ENGINEER SHALL SUBMIT THREE COPIES OF SHEET S-9 WITH
 THE DIMENSIONS OF COLUMN TC-5 REVISED AS PROPOSED. THIS
 COMMENT MAY BE ADDRESSED WITHOUT FORMAL RESUBMITTAL OF
 PLANS.THE CONTRACTOR CAN SIMPLY BRING THE REVISED
 SHEETS TO THIS OFFICE AND INSERT THEM INTO THE SETS.
  
  
 --PROVISO--
 FBC 13-103.3EXTERIOR DOORS ON ENERGY CALCULATIONS.
 SUBMIT REVISED ENERGY CALCULATIONS AND INPUT DATA
 REPORT SHOWING THE INPUT FOR ALL EXTERIOR DOORS.SHEET
 10 OF THE INPUT DATA REPORT DOES NOT CURRENTLY REFLECT
 THE NUMBER AND TYPE OF EXTERIOR DOORS SHOWN ON THE
 PLANS.
  
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS