Plan Review Notes
Plan Review Notes For Permit 05031185
Permit Number 05031185
Review Stop P
Sequence Number 7
Notes
Date Text
2007-08-25 17:31:12REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 ****FROM PREVIOUS REVISION REVIEW:
  
  
 1. SHTS P-1, P-4, P-5, P-7, P-8, P-9 & P-10 REVISIONS
 ARE INDICATED AS REVISIONS 1 & 2. REVISIONS 1 & 2 ARE
 ALREADY SUBMITTED. THE NEW REVISIONS NUMBERS SHALL STAY
 IN SEQUENCE ALREADY ESTABLISHED ON THESE PLANS AND, FOR
 EXAMPLE, SHT P-1 HAS REVISIONS 1 THRU 5, SO THE NEXT
 REVISIONS SHALL BE 6 & 7. PLEASE INDICATE THE CORRECT
 REVISION NUMBERS ON EACH REVISED SHEET ACCORDING TO
 PREVIOUS REVISIONS. SECTION 106.1.3.
 ****RESPONSE NOTED, BUT P-1 STILL SHOWS A 2ND #2
 REVISION AND NEW REVISION #5 PREVIOUSLY DATED 03-07-05
 ON THE PLANS SIGNED, SEALED, AND DATED 3-11-05 HAS BEEN
 CHANGED TO 07-24-06. PLEASE CLARIFY. COMMENT HAS NOT
 BEEN ADDRESSED. ALSO PLEASE TURN OFF ALL PREVIOUSLY
 APPROVED REVISION CLOUDS AND REVISION NUMBERS ON THE
 PLAN. THIS WILL HELP EXPEDITE FUTURE REVISIONS AND
 ENABLE THE PLAN REVIEWERS TO REVIEW REVISIONS IN A
 TIMELY MANNER.--SHT P-4 REVISION #2 HAD AN ORIGINAL
 REVISION DATE 08-27-04, BUT THE NEW SHT P-4 SHOWS THE
 REVISION DATE 02-25-04 FOR THE SAME REVISION. PLEASE
 CLARIFY.
  
 2. OK
 3. OK
  
 4. SHT P-9 GAS SYSTEM SHOWS THE SERVICE SIZE TO BE
 2-1/2", BUT THE ISOMETRIC SHOWS 2" PIPE. TABLE 402.4(7)
 INDICATES 2-1/2" REQUIRED. ALSO 2" IS REQUIRED TO EACH
 WATER HEATER PER TABLE 402.4(7).PLEASE CORRECT THE
 PIPE SIZING ON THE ISOMETRIC. ALSO INDICATE THE CHANGE
 OF MATERIAL FROM SCHED. 40 TO SEMIRIGID COPPER.
 ****RESPONSE NOTED, BUT AS INDICATED, 2-1/2" PIPE IS
 REQUIRED. SEE TABLE 402.4(6).
  
 5. OK
  
 ************NEW COMMENTS************
  
 1B. SHTS P-2 & P-3 REVISION #4 HAS BEEN CHANGED, THE
 ORIGINAL REVISION IS DATED 07-06-05, BUT THE NEW SHTS
 SHOWS REVISION #4 DATED 07-24-06. ALSO REVISIONS
 INDICATED ON 07-24-06 HAS NOT BEEN FOUND OR APPROVED.
 SINCE THERE WAS ALREADY A REVISION #4 SHOWN ON THE
 SIGNED, SEALED SHEETS DATED 07-06-05, ALL REVISIONS
 AFTER THAT DATE SHALL HAVE THEIR OWN REVISION NUMBER.
 THE REVISIONS SHALL BE SEQUENTIAL TO TRACK ALL
 REVISIONS. SECTION 106.3.1. (NOTE: NO REVISION # 4
 REVISIONS ARE INDICATED ON THE SHEETS).
  
 2B. SHT P-5 INDICATES REVISION #3. REVISION #3 FOUND BY
 THE DIRECTIONAL COMPASS WITH NO CLOUD AND NO APPARENT
 CHANGE/REVISION. PLEASE CLARIFY. SECTION 106.1.1.
  
 3B. SHT P-6 REVISION #4 DATE HAS BEEN CHANGED FROM
 07-06-05 TO 07-24-06. ALSO REVISIONS INDICATED ON
 07-24-06 HAS NOT BEEN FOUND OR APPROVED.--REVISIONS
 5 & 6 FROM SET OF PLANS SIGNED, SEALED & DATED 09-23-05
 HAVE BEEN DELETED FROM THE REVISION INDEX. SINCE THERE
 ARE MANY REVISIONS ATTRIBUTED TO REVISION #6, WHY HAS
 REVISION #6 BEEN DELETED FROM THE REVISION INDEX?--
 NO NEW REVISION NUMBER #7 IS INDICATED ON THE NEW SHT
 P-6. PLEASE CLOUD AND NUMBER NEW REVISIONS AND TURN OFF
 ALL PREVIOUS CLOUDS OF REVISIONS APPROVED PRIOR TO THIS
 REVISION AS YOU HAVE FOR REVISIONS #5 & #6. (REVISIONS
 1, 2, 3 CLOUDS STILL SHOWN ON PLANS).
  
 4B. SHT P-7 RISER S/8 DOES NOT REFLECT THE FLOOR PLAN.
 SHT P-5 SHOWS AN ICE MAKER & A FLOOR SINK ON THE FLOOR
 PLAN, BUT THE RISER SHOWS NO FLOOR SINK. PLEASE
 CORRELATE RISER AND FLOOR PLAN INFORMATION. SECTION
 106.1.1.
  
 5B. P-7 RISER S/6 WASTE LINES FOR TUBS TO BE CONNECTED
 TO THE STACK BELOW THE FLOOR UNLESS THE TUBS ARE TO BE
 RAISED ABOVE THE FLOOR LEVEL. PLEASE CLARIFY. SECTION
 106.1.1.
  
 6B. SHT P-7 WATER RISER DIAGRAMS FOR MEN & WOMEN TOILET
 ROOMS: SHUT OFF VALVES ARE REQUIRED FOR THE W/H'S PER
 SECTION 606.2(2). PLEASE INDICATE ON RISER.
  
 7B. SHT P-7 WATER PIPING ISOMETRICS FOR UNITS 100, 101,
 102, 104, 105, 106 & 108 HAVE A REVISION #4. NO CHANGE
 IS NOTED. PLEASE CLARIFY. SECTION 106.1.1.
  
 8B. SHT P-8 REVISION #4 ON THE STAMPED PLANS SIGNED,
 SEALED & DATED 07-06-05 HAS BEEN CHANGED TO 07-24-06.
 SINCE THE REVISIONS #4 HAS ITS OWN REVISION, A NEW
 REVISION NUMBER IS REQUIRED FOR ALL NEW REVISIONS. ALSO
 REVISIONS INDICATED ON 07-24-06 HAS NOT BEEN FOUND OR
 APPROVED.
  
 9B. SHT P-9 REVISION #4 NOT FOUND OR APPROVED.
  
 10B. SHT P-9 GAS SYSTEM #1 PER TABLE 402.4(6) MINIMUM
 SIZE IS 2-1/2". 2" IS SHOWN.--SUBMIT MANUF
 SPECIFICATION SHEETS FOR THE WATER HEATERS TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA-54, NFPA-58 AND FBC-2004
 FUEL GAS SEC. 402.2.
  
 11B. SHT P-9 LOBBY REST-ROOMS WATER ISOMETRIC RISER
 DIAGRAM IS A REVISION & SHALL BE INDICATED AS SUCH WITH
 A CLOUD & A REVISION NUMBER ASSIGNED TO IT. SECTION
 106.1.3.
  
 12B. SHT P-10 REVISION #3 WAS DATED 07-06-05 AND HAS
 NOT BEEN CHANGED TO 07-24-06. THIS REVISION HAS NOT
 BEEN FOUND OR APPROVED. NEW REVISIONS SHALL HAVE NEW
 REVISION NUMBERS. EXISTING REVISIONS SHALL REMAIN AS
 APPROVED FOR CONFORMITY TO RECORD RETENTION.--
 REVISION #4 WAS DATED 09-16-05 AND NOW CHANGED TO DATE
 02-16-07. REVISION HAS NOT BEEN APPROVED. NEW REVISIONS
 SHALL HAVE NEW REVISION NUMBERS. TURN OFF ALL
 PREVIOUSLY APPROVED REVISION CLOUDS AND REVISION
 NUMBERS ON THE PLANS TO HELP EXPEDITE THE REVISION
 REVIEW. LEAVE REVISION INDEX NUMBER HISTORY CURRENT
 FROM FIRST REVISION THRU TO THE NEWEST REVISION.
  
 13B. SHT P-11 CONDENSATE DRAIN PIPING ISOMETRIC RISER
 DIAGRAM RISER C/1 SHOWS 2" RISER DRAINING INTO 1-1/2"
 BRANCH LINE. THIS IS NOT APPROVED PER SECTION 704.2.
 PLEASE CORRECT RISER DIAGRAM.
  
 14B. SHT P-12 GAS WATER HEATERS HAVE CHANGED. SUBMIT
 MANUF. SPECIFICATIONS FOR GAS APPROVAL. SECTION 402.2.
  
 15B. GENERAL NOTE: ALL SHEETS, TURN OFF ALL PREVIOUS
 REVISION CLOUDS & NUMBERED TRIANGLES THAT HAVE BEEN
 PREVIOUSLY APPROVED FROM THE FLOOR PLAN, ISOMETRICS
 ETC. LEAVING THESE ON CREATS CONFUSION AND ADDS TO THE
 PLAN REVIEW TIME AND TURN AROUND. LEAVE THE REVISION
 INDEX NUMBERS AND REVISION DATES AS APPROVED AND NEW
 REVISION NUMBERS SHALL BE ADDED FOR NEW REVISIONS
 WITHOUT DUPLICATING THE REVISIONS NUMBERS. SECTION
 106.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]