| 2007-08-25 17:31:12 | REVISION DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | |
| | ****FROM PREVIOUS REVISION REVIEW: |
| | |
| | |
| | 1. SHTS P-1, P-4, P-5, P-7, P-8, P-9 & P-10 REVISIONS |
| | ARE INDICATED AS REVISIONS 1 & 2. REVISIONS 1 & 2 ARE |
| | ALREADY SUBMITTED. THE NEW REVISIONS NUMBERS SHALL STAY |
| | IN SEQUENCE ALREADY ESTABLISHED ON THESE PLANS AND, FOR |
| | EXAMPLE, SHT P-1 HAS REVISIONS 1 THRU 5, SO THE NEXT |
| | REVISIONS SHALL BE 6 & 7. PLEASE INDICATE THE CORRECT |
| | REVISION NUMBERS ON EACH REVISED SHEET ACCORDING TO |
| | PREVIOUS REVISIONS. SECTION 106.1.3. |
| | ****RESPONSE NOTED, BUT P-1 STILL SHOWS A 2ND #2 |
| | REVISION AND NEW REVISION #5 PREVIOUSLY DATED 03-07-05 |
| | ON THE PLANS SIGNED, SEALED, AND DATED 3-11-05 HAS BEEN |
| | CHANGED TO 07-24-06. PLEASE CLARIFY. COMMENT HAS NOT |
| | BEEN ADDRESSED. ALSO PLEASE TURN OFF ALL PREVIOUSLY |
| | APPROVED REVISION CLOUDS AND REVISION NUMBERS ON THE |
| | PLAN. THIS WILL HELP EXPEDITE FUTURE REVISIONS AND |
| | ENABLE THE PLAN REVIEWERS TO REVIEW REVISIONS IN A |
| | TIMELY MANNER.--SHT P-4 REVISION #2 HAD AN ORIGINAL |
| | REVISION DATE 08-27-04, BUT THE NEW SHT P-4 SHOWS THE |
| | REVISION DATE 02-25-04 FOR THE SAME REVISION. PLEASE |
| | CLARIFY. |
| | |
| | 2. OK |
| | 3. OK |
| | |
| | 4. SHT P-9 GAS SYSTEM SHOWS THE SERVICE SIZE TO BE |
| | 2-1/2", BUT THE ISOMETRIC SHOWS 2" PIPE. TABLE 402.4(7) |
| | INDICATES 2-1/2" REQUIRED. ALSO 2" IS REQUIRED TO EACH |
| | WATER HEATER PER TABLE 402.4(7).PLEASE CORRECT THE |
| | PIPE SIZING ON THE ISOMETRIC. ALSO INDICATE THE CHANGE |
| | OF MATERIAL FROM SCHED. 40 TO SEMIRIGID COPPER. |
| | ****RESPONSE NOTED, BUT AS INDICATED, 2-1/2" PIPE IS |
| | REQUIRED. SEE TABLE 402.4(6). |
| | |
| | 5. OK |
| | |
| | ************NEW COMMENTS************ |
| | |
| | 1B. SHTS P-2 & P-3 REVISION #4 HAS BEEN CHANGED, THE |
| | ORIGINAL REVISION IS DATED 07-06-05, BUT THE NEW SHTS |
| | SHOWS REVISION #4 DATED 07-24-06. ALSO REVISIONS |
| | INDICATED ON 07-24-06 HAS NOT BEEN FOUND OR APPROVED. |
| | SINCE THERE WAS ALREADY A REVISION #4 SHOWN ON THE |
| | SIGNED, SEALED SHEETS DATED 07-06-05, ALL REVISIONS |
| | AFTER THAT DATE SHALL HAVE THEIR OWN REVISION NUMBER. |
| | THE REVISIONS SHALL BE SEQUENTIAL TO TRACK ALL |
| | REVISIONS. SECTION 106.3.1. (NOTE: NO REVISION # 4 |
| | REVISIONS ARE INDICATED ON THE SHEETS). |
| | |
| | 2B. SHT P-5 INDICATES REVISION #3. REVISION #3 FOUND BY |
| | THE DIRECTIONAL COMPASS WITH NO CLOUD AND NO APPARENT |
| | CHANGE/REVISION. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 3B. SHT P-6 REVISION #4 DATE HAS BEEN CHANGED FROM |
| | 07-06-05 TO 07-24-06. ALSO REVISIONS INDICATED ON |
| | 07-24-06 HAS NOT BEEN FOUND OR APPROVED.--REVISIONS |
| | 5 & 6 FROM SET OF PLANS SIGNED, SEALED & DATED 09-23-05 |
| | HAVE BEEN DELETED FROM THE REVISION INDEX. SINCE THERE |
| | ARE MANY REVISIONS ATTRIBUTED TO REVISION #6, WHY HAS |
| | REVISION #6 BEEN DELETED FROM THE REVISION INDEX?-- |
| | NO NEW REVISION NUMBER #7 IS INDICATED ON THE NEW SHT |
| | P-6. PLEASE CLOUD AND NUMBER NEW REVISIONS AND TURN OFF |
| | ALL PREVIOUS CLOUDS OF REVISIONS APPROVED PRIOR TO THIS |
| | REVISION AS YOU HAVE FOR REVISIONS #5 & #6. (REVISIONS |
| | 1, 2, 3 CLOUDS STILL SHOWN ON PLANS). |
| | |
| | 4B. SHT P-7 RISER S/8 DOES NOT REFLECT THE FLOOR PLAN. |
| | SHT P-5 SHOWS AN ICE MAKER & A FLOOR SINK ON THE FLOOR |
| | PLAN, BUT THE RISER SHOWS NO FLOOR SINK. PLEASE |
| | CORRELATE RISER AND FLOOR PLAN INFORMATION. SECTION |
| | 106.1.1. |
| | |
| | 5B. P-7 RISER S/6 WASTE LINES FOR TUBS TO BE CONNECTED |
| | TO THE STACK BELOW THE FLOOR UNLESS THE TUBS ARE TO BE |
| | RAISED ABOVE THE FLOOR LEVEL. PLEASE CLARIFY. SECTION |
| | 106.1.1. |
| | |
| | 6B. SHT P-7 WATER RISER DIAGRAMS FOR MEN & WOMEN TOILET |
| | ROOMS: SHUT OFF VALVES ARE REQUIRED FOR THE W/H'S PER |
| | SECTION 606.2(2). PLEASE INDICATE ON RISER. |
| | |
| | 7B. SHT P-7 WATER PIPING ISOMETRICS FOR UNITS 100, 101, |
| | 102, 104, 105, 106 & 108 HAVE A REVISION #4. NO CHANGE |
| | IS NOTED. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 8B. SHT P-8 REVISION #4 ON THE STAMPED PLANS SIGNED, |
| | SEALED & DATED 07-06-05 HAS BEEN CHANGED TO 07-24-06. |
| | SINCE THE REVISIONS #4 HAS ITS OWN REVISION, A NEW |
| | REVISION NUMBER IS REQUIRED FOR ALL NEW REVISIONS. ALSO |
| | REVISIONS INDICATED ON 07-24-06 HAS NOT BEEN FOUND OR |
| | APPROVED. |
| | |
| | 9B. SHT P-9 REVISION #4 NOT FOUND OR APPROVED. |
| | |
| | 10B. SHT P-9 GAS SYSTEM #1 PER TABLE 402.4(6) MINIMUM |
| | SIZE IS 2-1/2". 2" IS SHOWN.--SUBMIT MANUF |
| | SPECIFICATION SHEETS FOR THE WATER HEATERS TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA-54, NFPA-58 AND FBC-2004 |
| | FUEL GAS SEC. 402.2. |
| | |
| | 11B. SHT P-9 LOBBY REST-ROOMS WATER ISOMETRIC RISER |
| | DIAGRAM IS A REVISION & SHALL BE INDICATED AS SUCH WITH |
| | A CLOUD & A REVISION NUMBER ASSIGNED TO IT. SECTION |
| | 106.1.3. |
| | |
| | 12B. SHT P-10 REVISION #3 WAS DATED 07-06-05 AND HAS |
| | NOT BEEN CHANGED TO 07-24-06. THIS REVISION HAS NOT |
| | BEEN FOUND OR APPROVED. NEW REVISIONS SHALL HAVE NEW |
| | REVISION NUMBERS. EXISTING REVISIONS SHALL REMAIN AS |
| | APPROVED FOR CONFORMITY TO RECORD RETENTION.-- |
| | REVISION #4 WAS DATED 09-16-05 AND NOW CHANGED TO DATE |
| | 02-16-07. REVISION HAS NOT BEEN APPROVED. NEW REVISIONS |
| | SHALL HAVE NEW REVISION NUMBERS. TURN OFF ALL |
| | PREVIOUSLY APPROVED REVISION CLOUDS AND REVISION |
| | NUMBERS ON THE PLANS TO HELP EXPEDITE THE REVISION |
| | REVIEW. LEAVE REVISION INDEX NUMBER HISTORY CURRENT |
| | FROM FIRST REVISION THRU TO THE NEWEST REVISION. |
| | |
| | 13B. SHT P-11 CONDENSATE DRAIN PIPING ISOMETRIC RISER |
| | DIAGRAM RISER C/1 SHOWS 2" RISER DRAINING INTO 1-1/2" |
| | BRANCH LINE. THIS IS NOT APPROVED PER SECTION 704.2. |
| | PLEASE CORRECT RISER DIAGRAM. |
| | |
| | 14B. SHT P-12 GAS WATER HEATERS HAVE CHANGED. SUBMIT |
| | MANUF. SPECIFICATIONS FOR GAS APPROVAL. SECTION 402.2. |
| | |
| | 15B. GENERAL NOTE: ALL SHEETS, TURN OFF ALL PREVIOUS |
| | REVISION CLOUDS & NUMBERED TRIANGLES THAT HAVE BEEN |
| | PREVIOUSLY APPROVED FROM THE FLOOR PLAN, ISOMETRICS |
| | ETC. LEAVING THESE ON CREATS CONFUSION AND ADDS TO THE |
| | PLAN REVIEW TIME AND TURN AROUND. LEAVE THE REVISION |
| | INDEX NUMBERS AND REVISION DATES AS APPROVED AND NEW |
| | REVISION NUMBERS SHALL BE ADDED FOR NEW REVISIONS |
| | WITHOUT DUPLICATING THE REVISIONS NUMBERS. SECTION |
| | 106.1.3. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |