Plan Review Notes
Plan Review Notes For Permit 05031185
Permit Number 05031185
Review Stop B
Sequence Number 7
Notes
Date Text
2008-05-24 14:31:19BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 4TH REVIEW OF REVISION FOR INCREASE IN NUMBER OF
 STORIES FROM 5 TO 8 STORIES.
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS ARE NUMBERED AS
 PER THE BUILDING PLAN REVIEW OF 3/4/08:
  
 3)IMPACT FEES. COMMENT RESPONSE, STATING THAT THE
 OWNER WILL PAY IMPACT FEES, IS NOTED AND THIS OFFICE
 WILL DROP THIS COMMENT ONCE THE FEES ARE PAID. PREVIOUS
 COMMENT (RE-STATED HERE FOR INFORMATION):THE PROPOSED
 INCREASE IN BUILDING AREA WILL INCREASE THE IMPACT FEES
 DUE.THE PLANS SHALL BE TAKEN TO PALM BEACH COUNTY
 BUILDING DEPARTMENT FOR CALCULATION OF THE ADDITIONAL
 IMPACT FEES. THEY SHALL BE STAMPED AT THAT OFFICE AND A
 COPY OF THE PAID RECEIPT SUBMITTED TO THE CITY OF WEST
 PALM BEACH DEPT OF CONSTRUCTION SERVICES BEFORE THE
 REVISED PLANS CAN BE STAMPED.
  
 4) FBC TABLE 500ALLOWABLE BUILDING HEIGHT.FBC
 503.2.6 STATES THAT THE HEIGHT OF RESIDENTIAL
 OCCUPANCY, IN BUILDINGS OF TYPE II CONSTRUCTION, CAN BE
 UNLIMITED PROVIDED THE FIRE RESISTANCE OF ALL COLUMNS
 IS NOT LESS THAN 3 HOURS.YOUR COMMENT MOST RECENT
 RESPONSE LETTER HAS BEEN NOTED, HOWEVER COLUMN TC-5 ON
 SHEET S-9 DOES NOT HAVE TWO PARALLEL SIDES AT LEAST 36
 INCHES LONG. EVEN ALLOWING FOR BOTH LEGS OF THIS
 L-SHAPED COLUMN, ON SIDE IS 32 INCHES LONG.PREVIOUS
 COMMENT (RE-STATED HERE FOR INFORMATION):CONCRETE
 COLUMNS: SECTION 709.2.4 OF FBC 2001 REQUIRES A MINIMUM
 CONCRETE COLUMN DIMENSION OF 12 INCHES FOR A 3 HOUR
 FIRE RESISTANCE RATING, OR A MINIMUM CONCRETE COLUMN
 DIMENSION OF 8 INCHES IF TWO PARALLEL SIDES ARE AT
 LEAST 36 INCHES LONG.COLUMN TC-5, SHOWN ON SHEET S-9,
 DOES NOT COMPLY WITH EITHER REQUIREMENT OPTION.REVISE
 THE SIZE OF COLUMN TC-5 TO COMPLY WITH SECTION IS
 709.2.4 OF FBC 2001
  
 13) FBC 13-103.1.2THIS COMMENT HAS STILL NOT BEEN
 ADDRESSED.THE SIGNATURE OF RAFAEL PENA IS STILL A
 PHOTOCOPIED SIGNATURE.AN ORIGINAL (WET) SIGNATURE
 MUST BE PUT ON THESE ENERGY CALCULATIONS BY RAFAEL
 PENA.WE NEED THREE COPIES OF THE ENERGY CODE
 COMPLIANCE FORM, EACH WITH RAFAEL PENA'S ORIGINAL (WET)
 SIGNATURE AND RAISED SEAL.
  
 15) FBC 1606.1WIND LOADS ON PARKING STRUCTURE.THE
 COMMENT RESPONSE, STATING THAT HARDING STEEL IS
 CURRENTLY PRODUCING WIND LOAD CALCULATIONS, IS NOTED.
 THE WIND LOAD DESIGN CRITERIA/CALCULATIONS SHALL BE
 SUBMITTED FOR REVIEW.PREVIOUS COMMENT (RE-STATED HERE
 FOR INFORMATION):THE SUBMITTAL FOR THE HARDING STEEL,
 INC. PARKING STRUCTURE DOES NOT INCLUDE ANY WIND LOAD
 DESIGN CRITERIA.THE STRUCTURE MUST BE DESIGNED TO
 WITHSTAND A WIND SPEED OF 140 MPH (3 SECOND GUST).
 SUBMIT WIND LOAD DESIGN CRITERIA/CALCULATIONS.ALL
 STRUCTURAL SUBMITTALS MUST BE REVIEWED BY THE
 STRUCTURAL ENGINEER OF RECORD FOR THE PROJECT AND
 INCLUDE THE SHOP DRAWING REVIEW STAMP OF THAT
 ENGINEER.
  
 NOTE: TO EXPEDITE REVIEW OF A RESUBMITTAL WHICH
 REQUIRES NEW PLANS IN ORDER TO ADDRESS THE ABOVE
 COMMENTS, THE OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD SHEET SHOULD BE
 STAPLED/CLIPPED TO THE REMAINING OLD SHEETS, TO FORM A
 SET OF 'OLD/VOID SHEETS', FOR COMPARISON OF REVISIONS
 WHEN REVIEWING THE RESUBMITTED PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE:
 (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]