Plan Review Notes
Plan Review Notes For Permit 05031185
Permit Number 05031185
Review Stop P
Sequence Number 6
Notes
Date Text
2007-05-17 08:02:51REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
  
 1. SHTS P-1, P-4, P-5, P-7, P-8, P-9 & P-10 REVISIONS
 ARE INDICATED AS REVISIONS 1 & 2. REVISIONS 1 & 2 ARE
 ALREADY SUBMITTED. THE NEW REVISIONS NUMBERS SHALL STAY
 IN SEQUENCE ALREADY ESTABLISHED ON THESE PLANS AND, FOR
 EXAMPLE, SHT P-1 HAS REVISIONS 1 THRU 5, SO THE NEXT
 REVISIONS SHALL BE 6 & 7. PLEASE INDICATE THE CORRECT
 REVISION NUMBERS ON EACH REVISED SHEET ACCORDING TO
 PREVIOUS REVISIONS. SECTION 106.1.3.
  
 2. SHTS P-1 & P-5, (NEW) REVISION 1 NOT FOUND.
  
 3. SHT P-8 DRAINAGE PIPING SHALL NOT BE REDUCED IN THE
 DIRECTION OF FLOW PER SECTION 704.2. SEE RISER "F"
 SHOWS 4" ON THE HORIZONTAL & 3" AT THE TOP OF THE RISER
 ON THE VERTICAL. PLEASE CORRELATE PIPE SIZES.
  
 4. SHT P-9 GAS SYSTEM SHOWS THE SERVICE SIZE TO BE
 2-1/2", BUT THE ISOMETRIC SHOWS 2" PIPE. TABLE 402.4(7)
 INDICATES 2-1/2" REQUIRED. ALSO 2" IS REQUIRED TO EACH
 WATER HEATER PER TABLE 402.4(7).PLEASE CORRECT THE
 PIPE SIZING ON THE ISOMETRIC. ALSO INDICATE THE CHANGE
 OF MATERIAL FROM SCHED. 40 TO SEMIRIGID COPPER.
  
 5. SHT P-9 WATER RISER DIAGRAM SHOWS THE 8TH FLOOR
 BETWEEN THE 4TH & 5TH FLOORS. ALSO SHOWN IS 3/4" WATER
 SUPPLY TO THE 5TH FLOOR AND 1" FROM THE 4TH FLOOR UP TO
 THE 8TH FLOOR. THE WATER RISER DIAGRAM SHALL REFLECT
 WHAT WILL BE INSTALLED. IF SOME FLOORS ARE TYPICAL FOR
 PIPE SIZES, (EXAMPLE 2ND THRU 4TH FLOORS 2 INCH PIPE),
 THAT CAN BE INDICATED ON THE RISER. PLEASE SUBMIT
 CALCULATIONS FOR THE WATER PIPING PER SECTION 604.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved