| Date |
Text |
| 2008-05-24 19:33:59 | *****DENIED***** |
| | |
| | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE |
| | PLAN REVIEWS STILL NEED TO BE ADDRESSED: |
| | |
| | |
| | 03.PLEASE PROVIDE A CLEAR DETAIL REGARDING |
| | SUPERVISING EQUIPMENT ON DOUBLE DETECTOR CHECK ASSEMBLY |
| | ON SHEET C-8.YOUR RESPONSE INDICATED THAT DETAILS |
| | WERE NOW SHOWN ON SHEET C-8, HOWEVER NO CIVIL DRAWINGS |
| | WERE FOUND |
| | |
| | 11.SMOKE/PRESSURIZATION AND VENTILATION INDICATES |
| | THAT SYSTEM IS SIZED FOR MAXIMUM OF FIVE STORIES. |
| | PLEASE ADVISE NOW THAT THE PROJECT IS EIGHT STORIES. |
| | DISPLAY/SHOW THAT THE SYSTEM IS CAPABLE OF ADEQUATE |
| | FUNCTIONING FOR THE EIGHT STORY BUILDING. |
| | |
| | 12.THE DRAWING ON SHEET AC-8 (REGARDING THE SMOKE |
| | CONTROL PANEL) APPEARS TO NEED MORE DETAIL.PLEASE |
| | CALL/CONTACT THE BUREAU OF FIRE PREVENTION AT |
| | 561-804-4724 TO PROVIDE A DRAWING FOR REVIEW BY THIS |
| | OFFICE.PROVIDE DOCUMENTATION THAT THIS ARRANGEMENT |
| | WAS APPROVED BY BATTALION CHIEF MIKE CARSILLO ON |
| | 03/12/08 |
| | |
| | 13.FIRE ALARM AND FIRE SPRINKLER PLANS WILL NEED TO |
| | BE UPDATED ILLUSTRATING NEW BATTERY CALCULATIONS AND |
| | SPRINKLER MODIFICATION FOR NEW PROPOSED FLOORS AT TIME |
| | OF PERMIT APPLICATION FOR REFERENCED SYSTEMS.PROVIDE |
| | DOCUMENTATION THAT THIS ARRANGEMENT WAS APPROVED BY |
| | BATTALION CHIEF MIKE CARSILLO ON 03/12/08 |
| | |
| | |
| | |
| | PLEASE PROVIDE A RESPONSE LETTER TO FIRE PLAN REVIEW |
| | ADDRESSING THESE COMMENTS.IT WOULD BE HELPFUL TO |
| | INDICATE WHERE ON THE PLANS THE CHANGE IS ADDRESSED. |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |