Plan Review Notes
Plan Review Notes For Permit 05031185
Permit Number 05031185
Review Stop E
Sequence Number 6
Notes
Date Text
2008-04-23 11:53:51** DENIED 4TH TIME FOR REVISIONS **
  
 ** PLEASE SEE SOME OF THE NOTES FROM THE PREVIOUS
 REVIEW ARE STILL IN NEED OF ADDRESSING.
 ** PLEASE ALSO SEE NEW COMMENTS BASED ON DOCUMENTS
 FINALLY SUBMITTED FOR REVIEW WHICH WERE NOT SUBMITTED
 PREVIOUSLY.
 ** PLEASE ALSO SEE NEW COMMENTS WITH RESPECT TO SIGNED
 AND SEALED DOCUMENTS SUBMITTED WITHOUT ORIGINAL
 SIGNATURES.
  
 1) NOTE: PLEASE SE PREVIOUS REVIEW WITH RESPECT TO
 PHOTO-METRICS AND COORDINATION OF FIXTURES. PLEASE SEE
 SOME EXAMPLES GIVEN ONCE AGAIN AS THERE ARE FIXTURES ON
 PLANS WHICH ARE NOT ON THE PHOTO-METRICS OR FIXTURES ON
 PHOTO-METRICS WHICH ARE NOT THE SAME AS THE LIGHTING
 PLANS. SOME EXAMPLES ARE GIVEN BELOW.
 FOR EXAMPLE:
 PLEASE SEE SHEET E-1 WHICH SHOWS FE FIXTURES ON PLANS
 AND PHOTO-METRICS YET THE FIXTURE SCHEDULE ON THAT SAME
 SHEET STATES FIXTURES F1E.
 FOR EXAMPLE:
 PLEASE SEE SHEET E-4 WHICH SHOWS COMPLETELY DIFFERENT
 LIGHT FIXTURES AND DIFFERENT LIGHT FIXTURE LOCATIONS
 THAN THE LIGHTING SHOWN ON THE PHOTO-METRIC SHEET E-4A
 FOR THIS SAME ROOF-TOP PLAN.
 PLEASE SEE THE FIXTURE TYPES ON E-4A ARE NOT THE SAME
 AND MUCH COORDINATION IS NEEDED.
 PLEASE SEE LS 101 7.8, 7.9
 FBC 106.1.23 FOR COORDINATION AND ADDITIONAL
 INFORMATION.
  
 2) NOTE: PLEASE SEE THERE ARE SIX SETS OF ENERGY
 CALCULATIONS SUBMITTED. (3-OLD SETS AND 3-NEWS SETS)
 PLEASE SEE IN EITHER CASE NONE OF THESE CONTAIN
 ORIGINAL SIGNATURES BY THE ENGINEER OF RECORD. IN FACT
 FOUR OF THE 6 SUBMITTED CONTAIN A RAISED SEAL OVER
 PHOTO-COPIED SIGNATURES WHICH ARE IN VIOLATION OF
 FLORIDA STATUTES 471.025 AND FLORIDA ADMINISTRATIVE
 CODE 61G15-23.002. PLEASE KNOW THESE MAY BE RETAINED BY
 THIS OFFICE AND FORWARDED TO THE FLORIDA BOARD OF
 ENGINEERS AND LEGAL COUNSEL TO THE BOARD. *SHALL NOT
 PLACE A RAISED SEAL OVER PHOTO-COPIED SIGNATURES IN ANY
 SITUATION.*
  
 3) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED
 DO NOT COORDINATE WITH THE LIGHTING AS SHOWN ON PLANS.
 PLEASE SEE 2001 FBC 13-400.1.A, 13-415.2 ETC
 PLEASE SEE THE FOLLOWING IS AN EXAMPLE FOR ITEMS WHICH
 DO NOT COMPLY OR COORDINATE WITH PLANS. THE INPUT DATA
 REPORT WILL BE NOTED AS IDR
 FOR EXAMPLE:
 PLEASE SEE THE LIGHTING SHOWN FOR EXTERIOR ON PLANS IS
 SUBSTANTIALLY MORE THAN THE LIGHTING SHOWN ON THE IDR.
 THE WATTAGES OF THE FIXTURES SHOWN ON PLANS IN
 FOLLOWING AREAS SUCH AS PARKING LOT, DRIVEWAY, POOL
 AREA, DECK, OUTSIDE WALL LIGHTS ON GROUND FLOOR AND
 UPPER ROOF AREAS ETC IS WAY MORE THAN THE LIGHTING
 SHOWN ON THE IDR. PLEASE SEE THE TOTAL WATTAGE ON THE
 IDR FOR EXTERIOR LIGHTS SHOWS 887WATTS, YET THE
 LIGHTING FOR DRIVE AREA ALONE IS 1800WATTS.
 FOR EXAMPLE:
 PLEASE SEE THE LIGHTING ON E-1 FOR THE EXTERIOR OF THE
 BUILDING. WHERE ARE THESE FIXTURES ON THE IDR? THEY ARE
 NOT PLACED IN THE IDR.
 THIS DOES NOT EVEN INCLUDED DOZENS AND DOZENS OF OTHER
 FIXTURES WHICH ARE MISSING FROM THE IDR ALTOGETHER.
 HOW IS THIS POSSIBLE?
 PLEASE SEE THE CODE REQUIRES THESE FIXTURES TO BE
 PLACED INTO THE IDR.
  
 4) NOTE: PLEASE SEE THE PREVIOUS REVIEWS REQUESTED THE
 MANUFACTURES SPECS/CUT SHEETS FOR THE FIRE PUMP AND
 FIRE PUMP CONTROLLER. THIS IS THE FIRST REVIEW IN WHICH
 THESE DOCUMENTS WERE SUBMITTED.
 PLEASE SEE THE LISTING STATED ON THESE DOCUMENTS
 INDICATE A ULC LISTING WHICH IS UNDERWRITERS
 LABORATORIES OF CANADA.
 PLEASE KNOW THIS LISTING IS NOT A RECOGNIZED EQUIPMENT
 TO BE USED IN THE UNITED STATES. THE LISTING WOULD BE
 REQUIRED TO SHOW A C UL US LISTED OR OTHER NATIONALLY
 RECOGNIZED TESTING LABORATORY (NRTL). PLEASE SEE OSHA
 FOR LATEST LISTING FOR PRODUCTS AND LISTINGS WHICH ARE
 ACCEPTABLE IN THE US.
 WE HAVE ATTACHED A COPY OF THE INFORMATION FROM UL
 WHICH CLEARLY SHOWS THE ULC IS NOT AN APPROVED LISTING
 IN THE US.
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  